Plan Review Notes
Plan Review Notes For Permit 10080639
Permit Number 10080639
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2010-09-17 11:23:282510 BROADWAY
 PERMIT NUMBER 10080639
  
 1. TACTILE SIGNAGE REQUIRED AT EXIT DOOR LOCATIONS.
  
 2. BUILDING ADDRESS NOT SHOWN ON ELEVATION DRAWINGS.
 THE BUILDING ADDRESS SHALL BE A MINIMUM OF AT LEAST 6"
 HIGH AND AT LEAST 1" WIDE AND IT SHALL CONTRAST WITH
 THE BACKGROUND THAT IT IS AFFIXED TO.
  
 3. SINCE NO COOKING EQUIPMENT IS SHOWN, NO COOKING IS
 ALLOWED. ANY COOKING THAT PRODUCES SMOKE OR GREASE
 LADEN VAPORS SHALL BE PROTECTED BY A HOOD,DUCT, AND
 FIRE SUPPRESSION SYSTEM. SEPARATE PLANS AND PERMITS
 REQUIRED.
  
 4. INTERIOR FINISH CLASSIFICATIONS FOR WALLS AND
 CEILINGS SHALL BE CLASS A OR B AND NOT C AS LISTED ON
 THE PLANS.
  
 DENIED
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION