2010-08-23 14:17:38 | RESIDENTIAL (R3) RE-ROOF, BUILDING REVIEW CHECKLIST. | | 2007 FBC WITH 2009 REVISIONS. | | | | 1- FLAT ROOF: | | A) SPECIFY WHICH APPROVED ASSEMBLY FROM NOA 09-0224.01 | | SUBMITTED IS GOING TO BE INSTALLED. PRODUCT APPROVAL | | SUBMITTED IS MISSING THE PAGE SHOWING THE APPROVED | | ASSEMBLY. | | ***NOTE: DON'T SELECT ASSEMBLIES WHICH ARE LIMITED BY | | GENERAL LIMITATION #9 BECAUSE THEY DON'T MEET THE | | DESIGN PRESSURES REQUIRED BY SEC. R301. | | | | B) PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS FOR | | NAIL ENHANCING AT PERIMETER AND CORNER AREAS AS | | REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE OF NOA | | SUBMITTED. | | ***NOTE: DESIGN PROFESSIONAL DOING THE CALCULATIONS TO | | TAKE INTO CONSIDERATION THAT THIS BUILDING IS LOCATED | | ON EXPOSURE "C". SEE SEC. R301.2.1.4.3 OF 2007 FLORIDA | | RESIDENTIAL CODE. | | | | 2- ACCORDING TO THE MIAMI-DADE WEBSITE THE SHINGLES NOA | | 07-0306.04 SUBMITTED IS SUPERSEDED. NEED TO PROVIDE | | CURRENT NOA. | | | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561)805-6712 |
|