Plan Review Notes
Plan Review Notes For Permit 10080615
Permit Number 10080615
Review Stop B
Sequence Number 1
Notes
Date Text
2010-08-23 14:17:38RESIDENTIAL (R3) RE-ROOF, BUILDING REVIEW CHECKLIST.
 2007 FBC WITH 2009 REVISIONS.
  
 1- FLAT ROOF:
 A) SPECIFY WHICH APPROVED ASSEMBLY FROM NOA 09-0224.01
 SUBMITTED IS GOING TO BE INSTALLED. PRODUCT APPROVAL
 SUBMITTED IS MISSING THE PAGE SHOWING THE APPROVED
 ASSEMBLY.
 ***NOTE: DON'T SELECT ASSEMBLIES WHICH ARE LIMITED BY
 GENERAL LIMITATION #9 BECAUSE THEY DON'T MEET THE
 DESIGN PRESSURES REQUIRED BY SEC. R301.
  
 B) PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS FOR
 NAIL ENHANCING AT PERIMETER AND CORNER AREAS AS
 REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE OF NOA
 SUBMITTED.
 ***NOTE: DESIGN PROFESSIONAL DOING THE CALCULATIONS TO
 TAKE INTO CONSIDERATION THAT THIS BUILDING IS LOCATED
 ON EXPOSURE "C". SEE SEC. R301.2.1.4.3 OF 2007 FLORIDA
 RESIDENTIAL CODE.
  
 2- ACCORDING TO THE MIAMI-DADE WEBSITE THE SHINGLES NOA
 07-0306.04 SUBMITTED IS SUPERSEDED. NEED TO PROVIDE
 CURRENT NOA.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712