2011-01-10 09:34:38 | PROVIDE (RESPOND TO COMMENTS IN WRITING) : |
| |
| # 1 STORMWATER POLLUTION PREVENTION PLAN (COULD BE A |
| SIGNED AND SEALED SET OF INSTRUCTIONS PROTECTING |
| STORMDRAINS, OUTFALLS, ETC.) |
| # 2. SURFACE WATER CALCULATION - 2 COPIES SIGNED AND |
| SEALED (INCLUDE SURFACE WATER MANAGEMENT CALCULATIONS |
| IN ACRES AND S.F.) |
| TOTAL PERVIOUS AND IMPERVIUOUS, THIS INFORMATION WILL |
| UPDATE YOUR STORMWATER ACCOUNT AT CITY OF WEST PALM |
| BEACH. |
| #3. ADDRESS IF ANY WATER OR SEWER OR DRAINAGE FROM |
| DEMOLISHED BUILDING NEEDS CAPPING AND/OR REMOVAL. |
| |
| ******************************************************* |
| ********** |
| |
| CITY ORDINANCE 3132-98, SECTION 32-18(A): "...IT SHALL |
| BE UNLAWFUL FOR ANY PERSON TO DIRECTLY OR INDIRECTLY |
| DEPOSIT, DISCHARGE, SPILL, OR DUMP INTO ANY OF THE |
| PUBLIC WATERS OR MUNICIPAL SEPARATE STORM SEWER SYSTEM |
| WITHIN THE CITY, ANY SUBSTANCE OTHER THAN THAT COMPOSED |
| ENTIRELY OF STORM WATER." AND, SECTION 32-18(C): "NO |
| PERSON MAY MAINTAIN, USE OR ESTABLISH ANY DIRECT OR |
| INDIRECT CONNECTION TO THE STORM WATER SYSTEM THAT |
| RESULTS IN ANY DISCHARGE IN VIOLATION OF THIS |
| ORDINANCE. THIS PROHIBITION IS RETROACTIVE AND APPLIES |
| TO CONNECTIONS MADE IN THE PAST, REGARDLESS OF WHETHER |
| MADE UNDER A PERMIT, OR OTHER AUTHORIZATION, OR WHETHER |
| PERMISSIBLE UNDER LAWS OR PRACTICES APPLICABLE OR |
| PREVAILING AT THE TIME THE CONNECTION WAS MADE." |
| |
| CHAPTER 62.302, F.A.C. EFFECTIVELY STATES THAT THE SITE |
| IS NOT ALLOWED TO DISCHARGE ANY QUANTITY OF WATER THAT |
| VIOLATES STATE WATER QUALITY STANDARDS. CITY ORDINANCE |
| 3132-98, SECTION 32-18(A) STATES THAT IT IS A VIOLATION |
| TO DISCHARGE ANYTHING EXCEPT STORM WATER INTO THE |
| CITY'S MS4. THE CITY HAS THE AUTHORITY AND OBLIGATION |
| TO ENFORCE THESE RESTRICTIONS. IF THE APPLICANT'S |
| PROPOSED SYSTEM IS NOT PROVIDING SUFFICIENT WATER |
| QUALITY TREATMENT (SO THAT ANY DISCHARGE IS FREE OF ALL |
| BUT STORM WATER RUNOFF), THEN APPLICANT MUST RE-DESIGN |
| THE SYSTEM. |
| |
| ******************************************************* |
| ********** |
| |
| MANUEL JULIAN GONZALEZ |
| CONSTRUCTION SERVICE DEPARTMENT ENGINEERING REVIEW |
| ENGINEERING SERVICES DEPARTMENT |
| 401 CLEMATIS STREET, 4TH FLOOR |
| WEST PALM BEACH, FL 33401 |
| (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402) |
| MAIN PHONE: (561) 822-1200 |
| DIRECT: (561) 494-1085 |
| FAX: (561) 494-1116 |
| MOBILE: (561) 644-7301 |
| EMAIL: [email protected] |
| WWW.WPB.ORG/ENGINEERING |
| |