Date |
Text |
2010-11-08 10:44:45 | FBC PLUMBING PLAN REVIEW #2 | | APPROVED WITH EXCEPTION: | | REVISION REQUIRED | | | | SHEETS P-7 - P-10 AND FS-3 SHOW A KITCHEN WITH A POT | | SINK, MOP SINK, AREA FLOOR DRAINS, AND DISH WASHER | | WITHOUT A PRE-RINSE SINK. | | FBC PLUMBING 1003.3.1 GREASE INTERCEPTORS AND AUTOMATIC | | GREASE REMOVAL DEVICES REQUIRED. A GREASE INTERCEPTOR | | OR AUTOMATIC GREASE REMOVAL DEVICE SHALL BE REQUIRED TO | | RECEIVE THE DRAINAGE FROM FIXTURES AND EQUIPMENT WITH | | GREASE-LADEN WASTE LOCATED IN FOOD PREPARATION AREAS, | | SUCH AS IN RESTAURANTS, HOTEL KITCHENS, HOSPITALS, | | SCHOOL KITCHENS, BARS, FACTORY CAFETERIAS AND CLUBS. | | FIXTURES AND EQUIPMENT SHALL INCLUDE POT SINKS, | | PRERINSE SINKS; SOUP KETTLES OR SIMILAR DEVICES; WOK | | STATIONS; FLOOR DRAINS OR SINKS INTO WHICH KETTLES ARE | | DRAINED; AUTOMATIC HOOD WASH UNITS AND DISHWASHERS | | WITHOUT PRERINSE SINKS. | | | | GREASE INTERCEPTORS AND AUTOMATIC GREASE REMOVAL | | DEVICES SHALL RECEIVE WASTE ONLY FROM FIXTURES AND | | EQUIPMENT THAT ALLOW FATS, OILS OR GREASE TO BE | | DISCHARGED. | | | | 1003.3.4.1 GREASE INTERCEPTOR CAPACITY. GREASE | | INTERCEPTORS AND GREASE TRAPS SHALL HAVE THE GREASE | | RETENTION CAPACITY INDICATED IN TABLE 1003.3.4.1 FOR | | THE FLOW-THROUGH RATES INDICATED. | | | | REVIEW BY LARRY WAGNER | | CHIEF PLUMBING INSPECTOR | | (561) 805-6692 | | FAX (561) 653-2692 | | E-MAIL [email protected] | | | | |
|