2010-10-29 10:10:45 | PALM BEACH COUNTY HOMELESS RESOURCE CENTER |
| 1000-45TH STREET |
| PERMIT NUMBER 10080589 |
| |
| |
| 1. BUILDING ADDRESSES ARE REQUIRED TO BE POSTED ON THE |
| BUILDINGS. THE BUILDING ADDRESS ONLY ON THE MARQUEE |
| SIGN DOES NOT MEET CODE REQUIREMENTS. BUILDING |
| ADDRESSES SHALL BE A MINIMUM OF AT LEAST 6" HIGH AND AT |
| LEAST 1" WIDE THAT CONTRAST TO THE BACKGROUND THAT THEY |
| ARE AFFIXED TO. |
| |
| 2. ENSURE THAT EMERGENCY LIGHTS EXIST IN STAIRWELL |
| 3-125 AND 3-128. |
| |
| 3. INTERIOR FINISH CLASSIFICATIONS FOR WALLS AND |
| CEILINGS SHALL COMPLY WITH THE FLORIDA BUILDING CODE |
| AND THE FLORIDA FIRE PREVENTION CODE. |
| |
| 4. ENSURE PANIC HARDWARE IS PRESENT ON EXIT DOORS IN |
| DINING AREA IF OCCUPANT LOADS ARE EXPECTED TO 100 OR |
| MORE PERSONS. |
| |
| 5. THE CHILDREN'S WAITING AREA SHALL BE EQUIPPED WITH |
| DUPLEX OUTLETS PROTECTIVE COVERS. |
| |
| 6. SEPARATE PLANS AND PERMITS REQUIRED FOR FIRE |
| SPRINKLER AND FIRE ALARM SYSTEMS. |
| |
| 7. THE FIRE ALARM SYSTEM SHALL BE MONITORED BY A THIRD |
| PARTY APPROVED FOR CENTRAL STATION SERVICE |
| REQUIREMENTS. |
| |
| 8. ELECTRONIC LOCKING DEVICES USED ON EXIT DOORS SHALL |
| COMPLY WITH CHAPTER 7 OF THE FLORIDA FIRE PREVENTION |
| CODE (101 THE LIFE SAFETY CODE, 2006 EDITION) |
| |
| 9. SUBJECT TO FIELD INSPECTION AND APPROVAL. |
| |
| |
| |
| APPROVED PROVISO |
| |
| |
| MIKE CARSILLO, BATTALION CHIEF |
| BUREAU OF FIRE PREVENTION |