Plan Review Notes
Plan Review Notes For Permit 10080589
Permit Number 10080589
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2010-10-29 10:10:45PALM BEACH COUNTY HOMELESS RESOURCE CENTER
 1000-45TH STREET
 PERMIT NUMBER 10080589
  
  
 1. BUILDING ADDRESSES ARE REQUIRED TO BE POSTED ON THE
 BUILDINGS. THE BUILDING ADDRESS ONLY ON THE MARQUEE
 SIGN DOES NOT MEET CODE REQUIREMENTS. BUILDING
 ADDRESSES SHALL BE A MINIMUM OF AT LEAST 6" HIGH AND AT
 LEAST 1" WIDE THAT CONTRAST TO THE BACKGROUND THAT THEY
 ARE AFFIXED TO.
  
 2. ENSURE THAT EMERGENCY LIGHTS EXIST IN STAIRWELL
 3-125 AND 3-128.
  
 3. INTERIOR FINISH CLASSIFICATIONS FOR WALLS AND
 CEILINGS SHALL COMPLY WITH THE FLORIDA BUILDING CODE
 AND THE FLORIDA FIRE PREVENTION CODE.
  
 4. ENSURE PANIC HARDWARE IS PRESENT ON EXIT DOORS IN
 DINING AREA IF OCCUPANT LOADS ARE EXPECTED TO 100 OR
 MORE PERSONS.
  
 5. THE CHILDREN'S WAITING AREA SHALL BE EQUIPPED WITH
 DUPLEX OUTLETS PROTECTIVE COVERS.
  
 6. SEPARATE PLANS AND PERMITS REQUIRED FOR FIRE
 SPRINKLER AND FIRE ALARM SYSTEMS.
  
 7. THE FIRE ALARM SYSTEM SHALL BE MONITORED BY A THIRD
 PARTY APPROVED FOR CENTRAL STATION SERVICE
 REQUIREMENTS.
  
 8. ELECTRONIC LOCKING DEVICES USED ON EXIT DOORS SHALL
 COMPLY WITH CHAPTER 7 OF THE FLORIDA FIRE PREVENTION
 CODE (101 THE LIFE SAFETY CODE, 2006 EDITION)
  
 9. SUBJECT TO FIELD INSPECTION AND APPROVAL.
  
  
  
 APPROVED PROVISO
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION