Plan Review Notes For Permit 10080589 |
Permit Number |
10080589 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2010-09-17 09:33:48 | FBC PLUMBING PLAN REVIEW #1 | | DENIED: | | | | SHEETS P-7 & P-10 SHOW A KITCHEN WITH A POT SINK, ETC | | FBC PLUMBING 1003.3.1 GREASE INTERCEPTORS AND AUTOMATIC | | GREASE REMOVAL DEVICES REQUIRED. A GREASE INTERCEPTOR | | OR AUTOMATIC GREASE REMOVAL DEVICE SHALL BE REQUIRED TO | | RECEIVE THE DRAINAGE FROM FIXTURES AND EQUIPMENT WITH | | GREASE-LADEN WASTE LOCATED IN FOOD PREPARATION AREAS, | | SUCH AS IN RESTAURANTS, HOTEL KITCHENS, HOSPITALS, | | SCHOOL KITCHENS, BARS, FACTORY CAFETERIAS AND CLUBS. | | FIXTURES AND EQUIPMENT SHALL INCLUDE POT SINKS, | | PRERINSE SINKS; SOUP KETTLES OR SIMILAR DEVICES; WOK | | STATIONS; FLOOR DRAINS OR SINKS INTO WHICH KETTLES ARE | | DRAINED; AUTOMATIC HOOD WASH UNITS AND DISHWASHERS | | WITHOUT PRERINSE SINKS. | | | | GREASE INTERCEPTORS AND AUTOMATIC GREASE REMOVAL | | DEVICES SHALL RECEIVE WASTE ONLY FROM FIXTURES AND | | EQUIPMENT THAT ALLOW FATS, OILS OR GREASE TO BE | | DISCHARGED. | | | | 1003.3.4.1 GREASE INTERCEPTOR CAPACITY. GREASE | | INTERCEPTORS AND GREASE TRAPS SHALL HAVE THE GREASE | | RETENTION CAPACITY INDICATED IN TABLE 1003.3.4.1 FOR | | THE FLOW-THROUGH RATES INDICATED. | | | | |
|