Plan Review Notes
Plan Review Notes For Permit 10080589
Permit Number 10080589
Review Stop M
Sequence Number 1
Notes
Date Text
2010-08-30 15:35:49REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 PLAN REVIEW COMMENTS:
  
 1. PG M-6 PLAN NOTE #1 CALLS FOR DRYER BOOSTER FAN.
 PROVIDE DRYER MANUFACTURER'S INSTALLATION INSTRUCTIONS
 SHOWING THE USE OF A BOOSTER FAN IS APPROVED BY THE
 DRYER MANUFACTURER. CLOTHES DRYERS SHALL BE EXHAUSTED
 IN ACCORDANCE WITH THE DRYER MANUFACTURER'S
 INSTRUCTIONS PER FBC-M 504.1.
  
 2. PG M-6 AND M-7 PLAN NOTES 2 AND/OR 3 CALL FOR
 OUTSIDE AIR INTAKE LOUVERS. PROVIDE FULL PRODUCT
 APPROVAL DOCUMENTATION WITH INSTALLATION INSTRUCTIONS
 FOR LOUVERS IN ACCORDANCE WITH FBC-B 106.3.3 AND FBC-M
 304.1.
  
 3. PG M-6 BUILDINGS 1 AND 2: EXHAUST AIR FROM SOME FANS
 AND CLOTHES DRYERS ARE SHOWN DISCHARGING DIRECTLY OVER
 SIDEWALKS (SEE DRAWING MARK-UPS). EXHAUST AIR SHALL NOT
 BE DIRECTED ONTO WALKWAYS PER FBC-M 401.4.2.
  
 4. PG M-7 PLAN NOTE #8 ON FIRST FLOOR AND PLAN NOTE #6
 ON SECOND FLOOR CALL FOR DRYER BOOSTER FAN. PROVIDE
 DRYER MANUFACTURER'S INSTALLATION INSTRUCTIONS SHOWING
 THE USE OF A BOOSTER FAN IS APPROVED BY THE DRYER
 MANUFACTURER. CLOTHES DRYERS SHALL BE EXHAUSTED IN
 ACCORDANCE WITH THE DRYER MANUFACTURER'S INSTRUCTIONS
 PER FBC-M 504.1.
  
 5. PG M-13: DETAIL #8 CALLS FOR RUSKIN IBD2 FIRE DAMPER
 AT RATED SUB-CEILING. BASED ON MANUFACTURER'S
 INSTRUCTIONS, THIS DAMPER IS NOT COMPATIBLE WITH THE
 SINGLE-MEMBRANE CEILING ASSEMBLY SHOWN ON PLANS. FIRE
 DAMPERS SHALL BE INSTALLED IN ACCORDANCE WITH THEIR
 LISTING AND MANUFACTURER'S INSTRUCTIONS PER FBC-M
 607.2.
  
 6. PG M-13 DETAIL #8 NOTE: FLEXIBLE DUCT CONNECTIONS
 ARE REQUIRED TO BE SEALED AND MECHANICALLY FASTENED.
 THEY ARE NOT INTENDED FOR REMOVAL AND USE FOR FIRE
 DAMPER ACCESS. PROVIDE RIGID DUCT WITH DUCT ACCESS
 DOOR. A SERVICE OPENING SHALL BE PROVIDED IN AIR DUCTS
 ADJACENT TO EACH FIRE DAMPER PER NFPA 90A SECTION
 4.3.4.1.
  
 7. ON ALL FLOOR PLANS: ADDITIONAL RATED SEPARATIONS ARE
 LIKELY AROUND SLEEPING ROOMS AND POSSIBLY EGRESS
 CORRIDORS (SEE BUILDING REVIEW COMMENTS). VERIFY THAT
 ALL PENETRATIONS OF ADDITIONAL RATED ASSEMBLIES ARE
 PROTECTES IN ACCORDANCE WITH FBC-M 607.5.
  
 8. PG M-7: FLOOR PLAN SHOWS RETURN AIR GRILL IN LANDING
 KITCHEN 3-117. RETURN AIR INTAKE IS PROHIBITED IN
 NON-DEDICATED KITCHEN HVAC SYSTEMS PER FBC-M 407.1.
  
 9. PG M-7 FIRST FLOOR PLAN NOTE #5 CALLS FOR FLY FAN AT
 EXTERIOR DOOR FOR LANDING KITCHEN 3-117. THIS FAN IS
 NOT IDENTIFIED ON PLANS TO CORRELATE WITH FAN SCHEDULE.
 PROVIDE MISSING INFORMATION PER FBC-B 106.1.1.
  
 10. PG M-8 THRU M-11: PLAN NOTE #6 CALLS FOR CONDENSATE
 TO DISCHARGE INTO HUB DRAIN. CONDENSATE SHALL NOT
 DISCHARGE INTO SANITARY SEWER PER CITY ORDINANCE AND
 FBC-M 307.2.1.
  
 11. PG M-8 THRU M-11: PLAN NOTE #4 CALLS FOR SMOKE
 DETECTOR TO BE PROVIDED IN SUPPLY AND RETURN DUCTS.
 PLAN AND SECTION VIEWS SHOW SMOKE DETECTORS ONLY IN THE
 SUPPLY DUCT. PLEASE COORDINATE PLANS, SECTIONS AND
 NOTES TO SHOW THE LOCATION OF ALL DUCT SMOKE DETECTORS
 PER FBC-M 106.1.1.
  
 12. PG M-8 THRU M-11: DUCT ACCESS DOOR REQUIRED AT
 SMOKE DETECTORS PER FBC-M 301.15 AND NFPA 90A SECTION
 4.3.4.1.
  
 13. PG M-14 DETAIL #7: FIRE DAMPERS SHALL BE INSTALLED
 IN ACCORDANCE WITH THE MANUFACTURER'S INSTALLATIONS AND
 LISTING PER FBC-M 607.2. PROVIDE MANUFACTURER'S
 INSTRUCTIONS IN THE FIELD AND REMOVE ANY CONFLICTIONG
 INFORMATION FROM PLANS.
  
 14. PG M-17 THRU M-19: SEQUENCE FOR FIRE/SMOKE CONTROL
 CALL FOF FAN TO BE SHUT DOWN BY DUCT SMOKE DETECTORS
 ONLY WHILE NOTE #4 ON PAGES M-8 THRU M-11 CALLS FOR
 FANS TO SHUT-DOWN UPON ACTIVATION OF ANY FIRE ALARM
 STATION. PLEASE COORDINATE AND CLARIFY PER FBC-B
 106.1.1.
  
 15. NO ENERGY CODE COMPLIANCE FORM OR COOLING LOAD
 CALCULATIONS PROVIDED FOR REVIEW. FBC-B CHAPTER 13.
  
 16. NO INFORMATION PROVIDED REGARDING KITCHEN EXHAUST
 AND VENTILATION SYSTEMS. PROVIDE SEPARATE PLANS AND
 PERMIT APPLICATION FOR THESE SYSTEMS.
  
 PLEASE RESPOND TO EACH COMMENT IN WRITING, INDICIATING
 HOW EACH COMMENT HAS BEEN ADDRESSED AND WHERE THE
 REQUIRED INFORMATION CAN BE FOUND. RESPONSE LETTER MAY
 BE UPLOADED TO THE "SUPPORTING DOCUMENTS" FOLDER UPON
 RESUBMISSION OF CORRECTED PLANS.
  