Date |
Text |
2010-09-23 10:10:48 | 1000 45TH STREET |
| HOMELESS SHELTER |
| PERMIT #10080589 |
| |
| SHEET LSP-2: |
| |
| -PROVIDE VISUAL FIRE ALARM NOTIFICATION APPLIANCES IN |
| ALL RESTROOMS. |
| |
| -PROVIDE ADDITIONAL INFORMATION ON DETEX DOOR HARDWARE. |
| |
| -SINGLE STATION SMOKE ALARMS ARE REQUIRED IN EVERY |
| GUEST ROOM, LIVING AREA AND SLEEPING ROOM WITHIN A |
| GUEST SUITE PER 28.3.4.5 (FFPC). |
| |
| -BUILDING #3: TRAVEL DISTANCE WITHIN A GUEST SUITE TO A |
| CORRIDOR SHALL NOT EXCEED 75 FEET IN BUILDINGS |
| PROTECTED BY AN AUTOMATIC SPRINKLER SYSTEM PER 28.2.6.2 |
| (FFPC). |
| |
| -PERMANENTLY LOCKED DOORS SHALL BE LABELED WITH ???NO |
| EXIT??? SIGNS. |
| |
| WESLEY JOLIN |
| CITY OF WEST PALM BEACH |
| FIRE & LIFE SAFETY PLAN REVIEW |
| 561-805-6730 |
| |
| |
2010-09-13 12:04:39 | HOMELESS RESOURCE CENTER |
| PERMIT NUMBER 10080589 |
| 1000 BLOCK OF 45TH STREET |
| |
| 1. THE BUILDINGS PRIOR TO THE SUBMITTAL OF THESE PLANS |
| WERE BEING USED AS A GROUP "B" OR BUSINESS USE. THE |
| PROPOSED BUILDINGS AND DESIGNS ARE DIFFERENT FROM |
| PREVIOUSLY USES WHICH SEEMS TO SUGGEST A CHANGE OF USE |
| OF SOME OF THESE FACILITIES. |
| |
| 2. KNOX-BOXES WILL BE NEEDED FOR THE BUILDINGS. PLEASE |
| GO TO WWW.KNOXBOX.COM TO ORDER THE BOXES. |
| |
| 3. DEBRIS SHALL BE REMOVED FROM THE SITE DAILY OR AS |
| OFTEN AS NECESSARY. |
| |
| 4. TACTILE SIGNAGE REQUIRED AT EXIT DOOR LOCATIONS. |
| |
| 5. ALL CONSTRUCTION, DEMOLITION, AND RENOVATION TO |
| COMPLY WITH NFPA 241. |
| |
| 6. SMOKE DETECTION EQUIPMENT SHALL BE INSTALLED A |
| MINIMUM OF AT LEAST THREE FEET FROM AIR CONDITIONER |
| DIFFUSERS. |
| |
| 7. ELEVATOR WARNING SIGNS ARE NEEDED. |
| |
| 8. SEPARATE PLANS AND PERMITS REQUIRED FOR FIRE ALARM |
| AND FIRE SPRINKLER INSTALLATIONS. |
| |
| 9. AN EMERGENCY PLAN IS TO BE SUBMITTED TO THIS OFFICE. |
| THIS EMERGENCY PLAN SHALL BE DEVELOPED USING AN "ALL |
| HAZARDS" APPROACH AND SHOULD INCLUDE PLANNING AND |
| TRAINING FOR FIRES, INCLEMENT WEATHER, MEDICAL |
| EMERGENCIES, ETC. |
| |
| 10. CARD READERS SHALL NOT INTERFERE WITH ANY EXITING |
| FROM THE BUILDINGS. |
| |
| 11. ON PAGE E-4 AN ADDITIONAL EXIT SIGN APPEARS TO BE |
| NEEDED ON THE OUTSIDE OF THE ADULT INTAKE AREA 1-136. |
| |
| 12. ON PAGE E-7 NO ILLUMINATED EXIT SIGNS OR EMERGENCY |
| LIGHTING SHOWN FOR THE BUSINESS AREA. |
| |
| 13. ON SHEET LSP-1 DOORS "THAT ARE TO REMAIN LOCKED AT |
| ALL TIMES" ARE PROVIDED WITH EGRESS CAPACITIES BUT ARE |
| NOT EQUIPPED WITH EXIT SIGNS. IF THEY ARE NOT REQUIRED |
| EXITS, THEN EGRESS CAPACITIES SHOULD NOT BE CALLED OUT. |
| |
| 14. AN EGRESS DOOR APPEARS TO BE IN CLOSE PROXIMITY TO |
| AN UNPROTECTED WINDOW OPENING FROM AN ADJACENT BUILDING |
| ON PAGE LSP-1. |
| |
| 15. PLEASE INDICATE THE COMBUSTIBILITY FACTOR FOR THE |
| PROPOSED MATTRESSES. |
| |
| 16. ALL RATED FIRE DOORS ARE TO BE PROPERLY LABELED AND |
| BE EQUIPPED WITH SELF-CLOSING DEVICES TO CAUSE THE |
| DOORS TO POSITIVELY LATCH WHEN OPENED. |
| |
| 17. PLEASE INDICATE THE LOCATIONS OF "NO SMOKING" SIGNS |
| AND AREAS AND THE LOCATIONS OF DESIGNATED SMOKING AREAS |
| AND SIGNAGE. |
| |
| 18. PLEASE EXPLAIN THE TERM "LANDING KITCHEN" AS |
| ILLUSTRATED ON THE PLANS. |
| |
| 19. GAS SERVICES SHALL COMPLY WITH NFPA 54, 2006 |
| EDITION. |
| |
| 20. PLEASE INDICATE CONTENTS AND AMOUNT OF MATERIALS IN |
| THE BUFFER TANK ON SHEET M-12. |
| |
| 21. ON LSP-1 "FAMILY ROOMS" ARE NOTED. PLEASE INDICATE |
| PURPOSE AND FURNISHINGS PLANNED FOR THESE ROOMS. ARE |
| ANY SLEEPING PURPOSES PLANNED FOR THESE ROOMS. |
| |
| 22. FAMILY ROOM # 3 HAS TRAVEL DISTANCE GOING THROUGH A |
| DOOR THAT IS NOT IDENTIFIED AS AN EXIT. |
| |
| 23. ON THE LIFE SAFETY SHEETS, SOME SLEEPING ROOMS ARE |
| RATED AND EQUIPPED WITH FIRE DOORS AND OTHERS ARE NOT. |
| PLEASE EXPLAIN RATIONALE. |
| |
| 24. PLEASE EXPLAIN CHILDREN'S/RECREATION (2-220) AREA. |
| |
| 25. ON THE FIRE SPRINKLER DRAWINGS CHECK VALVES FOR THE |
| FIRE DEPARTMENT CONNECTIONS COULD NOT BE LOCATED. ALSO |
| THE NEW FIRE HYDRANT IS TO BE LOCATED NO FARTHER THAN |
| 150 FEET FROM THE FIRE DEPARTMENT CONNECTIONS. PLEASE |
| EXPLAIN PURPOSE OF DRY FIRE DEPARTMENT CONNECTION |
| LINES. |
| |
| 26. TAMPER SWITCHES, CHAIN AND LOCKS ARE REQUIRED ON |
| FIRE LINE BACKFLOW DEVICE. |
| |
| 27. HOW WILL FURNITURE AND CLOTHING BE ARRANGED AND |
| MAINTAINED AND PLEASE DOCUMENT STORAGE HEIGHTS IN THE |
| STORAGE OR GROUP "S" BUILDING. |
| |
| 28. PLEASE INDICATE PURPOSE AND DURATION OF EXPECTED |
| OCCUPANCY OF THE INTAKE AREAS. |
| |
| 29. THE PLANS SEEM TO SUGGEST SMOKE DETECTOR |
| INSTALLATIONS WITH NO MENTION OF SMOKE ALARM |
| INSTALLATIONS. SMOKE DETECTORS ARE USUALLY CONNECTED TO |
| FIRE ALARM SYSTEMS AND SMOKE ALARMS ARE CONNECTED ONLY |
| TO THE ELECTRICAL SYSTEM. PLEASE CLARIFY ALL SMOKE |
| DETECTION EQUIPMENT. |
| |
| 30. SHEET FP-2 IS NOT VERY CLEAR. IT APPEARS THAT MORE |
| THAN TWELVE FIRE SPRINKLER HEADS WILL BE NEEDED. |
| |
| 31. THE PLANS DO NOT SEEM TO CALL OR IDENTIFY |
| PROTECTION FROM HAZARDS. ROOMS THAT CAN BE CONSIDERED |
| MORE HAZARDOUS SUCH AS BOILER, FURNACE, ELECTRICAL |
| ROOMS, ETC. NEED TO BE PROTECTED FROM OTHER PORTIONS OF |
| THE BUILDINGS. PLEASE INDICATE HOW THIS IS BEING |
| ACCOMPLISHED. |
| |
| 32. PLEASE REVIEW SECTION 310 OF THE FLORIDA BUILDING |
| CODE FOR EXPLANATIONS OF R-1 AND R-2 OCCUPANCY TYPES. |
| R-1 OCCUPANCIES ARE TRANSIENT AND R-2 OCCUPANCIES ARE |
| PERMANENT. IT HAS BEEN SUGGESTED IN MEETINGS THAT |
| OCCUPANCY AT THIS FACILITY IS MORE TRANSIENT IN NATURE |
| (90) DAYS. |