Date |
Text |
2010-10-05 10:27:58 | FAILED: |
| |
| #1 TRUNCATED DOMES MISSING IN CRITICAL AREAS PLEASE |
| REVISE PER MARK-UP. (SEE C2.1) |
| #2 CLEAN UP C1.1 AS MARKED (ANY WORK TO BE PERFORMED IN |
| WINDSOR AVE ROW WILL REQUIRE A ROW PERMIT. |
| SEE INTERNET LINK: |
| HTTP://WWW.CITYOFWPB.COM/ENGINEERING/ENG_FORMS.PHP |
| SEE ROW PARMIT APPLICATION DOCUMENT |
| #3 DCDA FOR FIRELINE NEEDS TO BE AT PROPERTY LINE. (SEE |
| C5.1) |
| #4 FIRE HYDRANT ON-SITE WILL BE CONSIDERED "PRIVATE", |
| YOU MAY BE REQUIRED TO INSTALL NEW HYDRANT AT PROPERTY |
| LINE IF CLOSEST HYDRANT IS MORE THAT 150' FROM FDC |
| LOCATION. |
| #4A CITY STANDARD DETAIL P-8 IS MISSING. AFTER |
| REVISION, FIRE MARSHALL MUST APPROVE PLAN PRIOR TO |
| ENGINEERING PASS. |
| #5 HYDRANT TEST REQUIRED AT NEAREST FIRE HYDRANT AS |
| PART OF THE NEXT REVISION SUBMITTAL. |
| TEST CAN BE SCHEDULED THRU THE CITY OF WPB FIRE |
| MARSHALL'S OFFICE (561) 822-1200. |
| #6 PARKING COUNT IN PARKING AREA CLOSES TO WINDSOR |
| AVENUE IS LOWER THAN SHOWN. RECOUNT SPACES. SHT C2.1 |
| #8 ENTRANCE AT 45TH STREET NEEDS TO BE CLARIFIED OR |
| STRIPED TO ACCOMODATE TRAFFIC OPERATION. 1 DRIVE IN 1 |
| DRIVE OUT. STRIPPING NEEDS TO BE WITHIN A CERTAIN WIDTH |
| TO AVOID TWO VEHICLES EXITING AT THE SAME TIME. |
| ANY CHANGES FROM THE 1 DRIVE IN AND 1 DRIVE OUT PATTERN |
| SHOULD BE DISCUSSED WITH PALM BEACH COUNTY ROADWAY. |
| #9 TRUNCATED DOMES AND ADA WILL BE REQUIRED AS THE |
| DRIVEWAY IS PART OF YOUR DESIGN RESPONSABILITY. |
| (DEPARTMENT OF JUSTICE, ADA |
| ACCESSIBILITY GUIDELINES -ADAAG, ACCESSIBLE |
| RIGHTS-OF-WAY, CHAPTER 3, SUBSECTION |
| 3.2) |
| #10 STRIPPING HAS BEEN MARKED UP ON SHEET C2.1 |
| #11 SHEET C3.1 (NEEDS TO REFLECT PERVIOUS AND |
| IMPERVIOUS AREAS. TOTAL SITE SF. ALSO) |
| #12 CITY STANDARD TAPPING VALVE DETAIL IS MISSING. |
| #13 POLLUTION PREVENTION PLAN MISSING WITH DETAILS. |
| |
| MANUEL JULIAN GONZALEZ |
| ENGINEERING PROJECT COORDINATOR |
| ENGINEERING SERVICES DEPARTMENT |
| 401 CLEMATIS STREET, 4TH FLOOR |
| WEST PALM BEACH, FL 33401 |
| (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402) |
| MAIN PHONE: (561) 822-1200 |
| DIRECT: (561) 494-1085 |
| FAX: (561) 494-1116 |
| MOBILE: (561) 644-7301 |
| EMAIL: [email protected] |
| WWW.WPB.ORG/ENGINEERING |
| |