2010-10-05 10:27:58FAILED:
  
 #1 TRUNCATED DOMES MISSING IN CRITICAL AREAS PLEASE
 REVISE PER MARK-UP. (SEE C2.1)
 #2 CLEAN UP C1.1 AS MARKED (ANY WORK TO BE PERFORMED IN
 WINDSOR AVE ROW WILL REQUIRE A ROW PERMIT.
 SEE INTERNET LINK:
 HTTP://WWW.CITYOFWPB.COM/ENGINEERING/ENG_FORMS.PHP
 SEE ROW PARMIT APPLICATION DOCUMENT
 #3 DCDA FOR FIRELINE NEEDS TO BE AT PROPERTY LINE. (SEE
 C5.1)
 #4 FIRE HYDRANT ON-SITE WILL BE CONSIDERED "PRIVATE",
 YOU MAY BE REQUIRED TO INSTALL NEW HYDRANT AT PROPERTY
 LINE IF CLOSEST HYDRANT IS MORE THAT 150' FROM FDC
 LOCATION.
 #4A CITY STANDARD DETAIL P-8 IS MISSING. AFTER
 REVISION, FIRE MARSHALL MUST APPROVE PLAN PRIOR TO
 ENGINEERING PASS.
 #5 HYDRANT TEST REQUIRED AT NEAREST FIRE HYDRANT AS
 PART OF THE NEXT REVISION SUBMITTAL.
 TEST CAN BE SCHEDULED THRU THE CITY OF WPB FIRE
 MARSHALL'S OFFICE (561) 822-1200.
 #6 PARKING COUNT IN PARKING AREA CLOSES TO WINDSOR
 AVENUE IS LOWER THAN SHOWN. RECOUNT SPACES. SHT C2.1
 #8 ENTRANCE AT 45TH STREET NEEDS TO BE CLARIFIED OR
 STRIPED TO ACCOMODATE TRAFFIC OPERATION. 1 DRIVE IN 1
 DRIVE OUT. STRIPPING NEEDS TO BE WITHIN A CERTAIN WIDTH
 TO AVOID TWO VEHICLES EXITING AT THE SAME TIME.
 ANY CHANGES FROM THE 1 DRIVE IN AND 1 DRIVE OUT PATTERN
 SHOULD BE DISCUSSED WITH PALM BEACH COUNTY ROADWAY.
 #9 TRUNCATED DOMES AND ADA WILL BE REQUIRED AS THE
 DRIVEWAY IS PART OF YOUR DESIGN RESPONSABILITY.
 (DEPARTMENT OF JUSTICE, ADA
 ACCESSIBILITY GUIDELINES -ADAAG, ACCESSIBLE
 RIGHTS-OF-WAY, CHAPTER 3, SUBSECTION
 3.2)
 #10 STRIPPING HAS BEEN MARKED UP ON SHEET C2.1
 #11 SHEET C3.1 (NEEDS TO REFLECT PERVIOUS AND
 IMPERVIOUS AREAS. TOTAL SITE SF. ALSO)
 #12 CITY STANDARD TAPPING VALVE DETAIL IS MISSING.
 #13 POLLUTION PREVENTION PLAN MISSING WITH DETAILS.
  
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved