Plan Review Notes For Permit 10080589 |
Permit Number |
10080589 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2010-10-04 16:52:21 | ***************ELECTRICAL PLAN REVIEW | | FAIL*************** | | | | 1) LIGHTING POWER DENSITIES REQUIRED FOR ALL NON | | RESIDENTIAL AREAS OF ALL THREE BUILDINGS AS PER CHAPTER | | 13 2007 FLORIDA BUILDING CODE | | | | 2) LIGHTING POWER DENSITIES REQUIRED FOR PARKING LOT | | LIGHTING, AS PER CHAPTER 13 2007 FLORIDA BUILDING CODE | | | | 3) PLAN SHOWES PARALLEL FEEDS TO PANEL DH-3, EQUIPMENT | | GROUNDING CONDUCTORS ARE REQUIRED TO BE FULL SIZE IN | | EACH CONDUIT AS PER SIZE OF OVERCURRENT PROTECTIVE | | DEVICE AS PER ARTICLE 250.122(F) 2008 NEC | | | | | | JOHN DICKINSON CONTRACT PLAN REVIEWER LICENSE NUMBER | | PX3182 | | CELL NUMBER 561 718 3230 |
|