Plan Review Notes For Permit 10080587 |
Permit Number |
10080587 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2010-10-26 12:00:17 | RESIDENTIAL (R3) REPAIRS/RENOVATION BUILDING REVIEW | | SECOND CHECKLIST. | | 2007 FBC WITH 2009 REVISIONS. | | | | 1- PROVIDE PRODUCT APPROVALS (2 COPIES) AS REQUIRED BY | | DCA RULE 9B-72 FOR: | | | | A) GLASS BLOCK. (REPEAT COMMENT. NOT SUBMITTED). | | | | B) WINDOW MULLIONS. AND, CLEARLY MARK ON DRAWINGS | | SPECIFIC MULLION SIZE AND FASTENERS TO BE USED TO | | VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. | | R301 OF 2007 FLORIDA RESIDENTIAL CODE. (REPEAT COMMENT. | | NOT SUBMITTED). | | | | 2- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING | | ( NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS | | REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC. | | | | ***NOTE: ENGINEER LETTER SUBMITTED DOESN'T IDENTIFY | | WHICH SPECIFIC PRODUCT APPROVALS WERE REVIEWED. AND IS | | MISSING THE REVIEW OF THE OTHER PRODUCT APPROVALS LIKE | | THE SINGLE HUNG WINDOWS AND EXTERIOR DOORS. ENGINEER TO | | CLEARLY LIST EACH PRODUCT APPROVAL NUMBER AND SPECIFIC | | MODEL OR USE STANDARD REVIEW STAMP ON EACH PRODUCT | | APPROVAL. | | | | 3- OWNER/AGENT TO SIGN AND DATE THE BOTTOM OF ENERGY | | CALCULATIONS FORM. | | | | 4- PROVIDE RECORDED NOTICE OF COMMENCEMENT AS REQUIRED | | BY SEC. 713.13 FLORIDA STATUTE. | | ***NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK | | UP. | | | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561)805-6712 | | |
|