2010-09-28 17:00:37 | RESIDENTIAL (R3) REPAIRS/RENOVATION BUILDING REVIEW |
| CHECKLIST. |
| 2007 FBC WITH 2009 REVISIONS. |
| |
| 1- A) BOTH SETS OF PLANS NEED TO BE SIGNED AND SEALED |
| BY THE ENGINEER OF RECORD AS REQUIRED BY CHAPTER 471 |
| FLORIDA STATUTE AND SEC. 61G15-23.002 OF FLORIDA |
| ADMINISTRATIVE CODE.. ONLY ONE SET WAS SIGNED AND |
| SEALED. |
| |
| B) ENGINEER TO HAVE HIS/HER ADDRESS ON THE TITLE BLOCK |
| AS REQUIRED BY SEC. 61G15-23.002 OF FLORIDA |
| ADMINISTRATIVE CODE AND CHAPTER 471 FLORIDA STATUTE. |
| |
| 2- PROVIDE PRODUCT APPROVALS (2 COPIES) AS REQUIRED BY |
| DCA RULE 9B-72 FOR: |
| |
| A) GLASS BLOCK. |
| |
| B) WINDOW MULLIONS. AND, CLEARLY MARK ON DRAWINGS |
| SPECIFIC MULLION SIZE AND FASTENERS TO BE USED TO |
| VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. |
| R301 OF 2007 FLORIDA RESIDENTIAL CODE. |
| |
| 3- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| ( NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC. |
| |
| 4- REVISE THE ENERGY CALCULATIONS: |
| A) R-19 INSULATION DOESN'T FIT ON 2X4 WALLS. REVISE |
| INSULATION ON ITEM #9(A) AS REQUIRED. |
| |
| B) CLARIFY CAPACITY OF HOT WATER TANK. WHY 5 GALLONS |
| ONLY? |
| |
| C) REVISE BUILDER NAME. SEE PERMIT APPLICATION FOR NAME |
| OF CONTRACTOR. |
| |
| 5- SHEET 2.1: R-19 INSULATION DOESN'T FIT ON 2X4 WALLS. |
| REVISE ALL DETAILS THAT SPECIFY R-19 ON THE 2X4 WALL. |
| |
| 6- PROVIDE RECORDED NOTICE OF COMMENCEMENT AS REQUIRED |
| BY SEC. 713.13 FLORIDA STATUTE. |
| ***NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK |
| UP. |
| |
| JULIO GOMEZ |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| (561)805-6712 |
| |