Plan Review Notes For Permit 10080576 |
Permit Number |
10080576 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2010-09-13 14:26:02 | FBC 2007 PLUMBING PLAN REVIEW #1 | | DENIED: | | | | 1.RESTROOM #115 & EWC ARE MISSING FROM SANITARY RISER. | | | | 2. FBC PLUMBING 406.3 AUTOMATIC CLOTHES WASHERS- WASTE | | CONNECTION: THE TRAP AND FIXTURE DRAIN SHALL BE A | | MINIMUM 2". | | THE FIXTURE DRAIN SHALL CONNECT TO A BRANCH OR STACK OF | | 3". | | | | 3. 1" COLD WATER PIPE WOULD BE REQUIRED UP TO THE 2ND | | RESTROOM BRANCH - 604.1 AND TABLE 603.1 | | | | REVIEW BY LARRY WAGNER | | CHIEF PLUMBING INSPECTOR | | (561) 805-6692 | | FAX (561) 653-2692 | | E-MAIL [email protected] | | |
|