2010-09-13 14:26:02FBC 2007 PLUMBING PLAN REVIEW #1
 DENIED:
  
 1.RESTROOM #115 & EWC ARE MISSING FROM SANITARY RISER.
  
 2. FBC PLUMBING 406.3 AUTOMATIC CLOTHES WASHERS- WASTE
 CONNECTION: THE TRAP AND FIXTURE DRAIN SHALL BE A
 MINIMUM 2".
 THE FIXTURE DRAIN SHALL CONNECT TO A BRANCH OR STACK OF
 3".
  
 3. 1" COLD WATER PIPE WOULD BE REQUIRED UP TO THE 2ND
 RESTROOM BRANCH - 604.1 AND TABLE 603.1
  
 REVIEW BY LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 (561) 805-6692
 FAX (561) 653-2692