2010-09-01 13:38:04*****APPROVED W/ COMMENTS*****
  
 1) NFPA 13D, SECTION 6.3(2) REQUIRES SMOKE DETECTORS TO
 BE PROVIDED WHEN THE SPRINKLER SYSTEM IS TIED INTO THE
 DOMESTIC WATER SUPPLY.
  
 2) THE "DESIGN CRITERIA" INFORMATION BOX SHOULD REFER
 TO A K-FACTOR OF 4.9 FOR THE PENDENT STYLE SPRINKLERS
 USED IN THE CALCULATION.
  
 3) THE "TYPES OF SPRINKLERS" INFORMATION BOX SHOULD
 SHOW THE ORIFICE SIZES AS 7/16-INCH (K=4.9) AND
 3/8-INCH (K=4.3).
  