Plan Review Notes For Permit 10080533 |
Permit Number |
10080533 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2010-09-01 13:38:04 | *****APPROVED W/ COMMENTS***** | | | | 1) NFPA 13D, SECTION 6.3(2) REQUIRES SMOKE DETECTORS TO | | BE PROVIDED WHEN THE SPRINKLER SYSTEM IS TIED INTO THE | | DOMESTIC WATER SUPPLY. | | | | 2) THE "DESIGN CRITERIA" INFORMATION BOX SHOULD REFER | | TO A K-FACTOR OF 4.9 FOR THE PENDENT STYLE SPRINKLERS | | USED IN THE CALCULATION. | | | | 3) THE "TYPES OF SPRINKLERS" INFORMATION BOX SHOULD | | SHOW THE ORIFICE SIZES AS 7/16-INCH (K=4.9) AND | | 3/8-INCH (K=4.3). | | | | MIKE CARSILLO, BATTALION CHIEF | | & WESLEY JOLIN | | WBP FIRE PLAN REVIEW | | 561-805-6730 | | | | | | |
|