2011-01-28 14:10:25 | MASTER PLAN (MODEL A.2) FOR NEW SINGLE FAMILY RESIDENCE |
| (R3), BUILDING REVIEW CHECKLIST. |
| 2007 FLORIDA RESIDENTIAL CODE WITH 2009 SUPPLEMENTS. |
| |
| 1- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. |
| N1100.3 OF 2007 FLORIDA RESIDENTIAL CODE. |
| |
| 2- PROVIDE 2 COPIES OF PRODUCT APPROVALS AS REQUIRED BY |
| DCA RULE 9B-72 FOR: |
| A) ROOF SHINGLES. NOA 07-1120.14 SUBMITTED WAS |
| SUPERSEDED ON THE MIAMI DADE WEBSITE. PROVIDE CURRENT |
| NOA. |
| |
| B) SINGLE HUNG WINDOWS. NOA 07-0322.06 SUBMITTED |
| EXPIRES ON MARCH 23, 2011. MASTER PLAN WILL HAVE TO BE |
| REVISED FOR FUTURE SUBMITTAL AFTER THIS DATE. |
| |
| C) WINDOW MULLIONS. NOA 06-0125.06 SUBMITTED EXPIRES ON |
| JUNE 28, 2011. MASTER PLAN WILL HAVE TO BE REVISED FOR |
| FUTURE SUBMITTAL AFTER THIS DATE. |
| |
| D) ENTRY DOOR. TWO DIFFERENT NOA'S WERE SUBMITTED. NOA |
| 06-0501.02 WHICH REQUIRES SHUTTERS AND NOA 07-0629.10 |
| WHICH DOESN'T REQUIRE SHUTTERS. CLARIFY WHICH ONE IS |
| GOING TO BE USED. |
| |
| E) REAR DOOR BY KITCHEN AREA AS SHOWN ON PLANS. |
| |
| F) STORAGE DOUBLE DOORS AS SHOWN ON PLANS. |
| |
| G) PRECAST LINTELS AS SPECIFIED ON PLANS. |
| |
| H) STORM SHUTTERS. COORDINATE WITH ITEM # 2D ABOVE. AND |
| PROVIDE COMPLETE INSTALLATION SCHEDULE. ALSO, MARK ON |
| SHUTTERS DRAWING SPECIFIC MOUNTING CONDITION AND ANCHOR |
| TYPE AND SPACING. |
| |
| I) TRUSS CONNECTORS. PROVIDE ONLY THE FRONT PAGE OF |
| PRODUCT APPROVAL AND PAGE SHOWING THE CONNECTOR. |
| |
| 3- ARCHITECT OF RECORD TO REVIEW AND APPROVE IN WRITING |
| (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC. |
| |
| 4- DESIGN CRITERIA: BUILDING EXPOSURE WAS REVISED TO |
| EXPOSURE "C" BUT THE DESIGN PRESSURES ON SHEETS A-3.0, |
| A-4.0, A-5.0 AND A-7.0 WERE NOT CHANGED TO REFLECT |
| EXPOSURE "C". |
| |
| 5- TRUSS PACKAGE: |
| A) REVISE BUILDING EXPOSURE. NEED TO DESIGN TRUSSES TO |
| EXPOSURE "C". REVISE TRUSS LAYOUT PAGE AND INDIVIDUAL |
| TRUSSES ACCORDINGLY. |
| |
| B) TRUSS COVER SHEET TO PROVIDE ALL THE INFORMATION, |
| INCLUDING THE ARCHITECT OF RECORD INFORMATION. |
| |
| C) TRUSS ENGINEER TO PROVIDE ORIGINAL SIGNATURE (NOT |
| COPY) AS REQUIRED BY CHAPTER 471 FLORIDA STATUTES. |
| |
| 6- SHEET A-2.0: |
| A) WALL SECTION A: SPECIFY CORRECT SECTION FOR THE |
| ATTIC VENTILATION. SEE 2007 FLORIDA RESIDENTIAL CODE. |
| |
| B) REVISE NOTE REGARDING TRUSS ANCHORS. USING SIMPSON |
| NOT USP, AND REFER TO CORRECT SHEET. |
| |
| C) DETAIL 1, DETAIL 5 AND WALL SECTION A SPECIFY 10 MIL |
| VAPOR BARRIER, WHILE FOUNDATION PLAN SPECIFIES 6 MIL |
| VAPOR BARRIER. REVISE AS REQUIRED TO MATCH. |
| |
| 7- REVISE HANDRAIL DETAIL #2 ON SHEET A-5.0. GUARDS |
| CAN'T BE LOWER THAN 36" IN HEIGHT. SEE SEC. R312.1. |
| |
| 8- SHEET A-6.0: |
| A) COORDINATE DETAIL 4/A-6.0 WITH CONNECTORS SPECIFIED |
| ON STRUCTURAL CONNECTORS SCHEDULE. REVISE AS REQUIRED |
| TO MATCH. |
| |
| B) CONNECTOR SPECIFIED ON DETAIL 5/A-6.0 CAN'T BE USED |
| BECAUSE IT DOESN'T PROVIDE ANY UPLIFT LOADS. SEE |
| CATALOG AND REVISE AS REQUIRED. |
| |
| C) DETAILS 2/A-6.0, 3/A-6.0 AND 5/A-6.0 SHOWN ON THE |
| GABLE END SIDE OF THE ROOF FRAMING PLAN DON'T |
| CORRESPOND TO THIS MODEL. REVISE AS REQUIRED. |
| |
| D) PROVIDE DETAIL 5/A-6.0 THAT REFLECTS ACTUAL |
| CONNECTION AS SHOWN ON THE ROOF FRAMING PLAN. GABLE END |
| TRUSS AND TRUSS GIRDERS FTG1A AND FTG2A ARE RESTING ON |
| AN 8"X8" CONCRETE COLUMN BELOW. DETAIL 5/A-6.0 SHOWN |
| DOESN'T REFLECT THIS CONDITION. REVISE AS REQUIRED. |
| |
| E) CLEARLY SPECIFY HOW IS THE GABLE END TRUSS ANCHORED |
| TO ALL THE FRONT PORCH COLUMNS. SEC. 106.1.1 CITY |
| AMENDMENTS TO FBC. |
| |
| JULIO GOMEZ |
| COMBINATION COMMERCIAL PLANS EXAMINER |
| (561)805-6712 |