2011-01-28 14:40:45 | MASTER FOR NEW SINGLE FAMILY RESIDENCE (R3) MECHANICAL |
| REVIEW CHECKLIST. |
| 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS. |
| |
| 1- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. |
| N1100.3 OF 2007 FLORIDA RESIDENTIAL CODE. |
| |
| 2- PROVIDE COOLING AND HEATING LOAD CALCULATIONS AS |
| REQUIRED BY SEC. N1107.AB OF 2007 FLORIDA RESIDENTIAL |
| CODE. |
| |
| 3- SPECIFY SUPPLY AND RETURN CFM'S ON EACH ROOM ROOM. |
| COORDINATE WITH THE HEATING AND COOLING CALCULATIONS |
| REQUIRED BY SEC. N1100.AB. |
| |
| 4- SHEET A-8.0: |
| A) REVISE MECHANICAL NOTE #3:. REVISE MINIMUM SEER AND |
| COORDINATE EQUIPMENT MODEL WITH LOAD CALCULATIONS |
| REQUIRED ON ITEM #2 ABOVE. |
| |
| B) REVISE OUTSIDE AIR CALCULATIONS NOTE: SEE 2007 |
| FLORIDA RESIDENTIAL CODE. CITE CORRESPONDING SECTION |
| AND MAKE SURE CONDITIONED FLOOR AREA MATCHES FLOOR AREA |
| SPECIFIED ON THE ARCHITECTURAL PLANS. CLARIFY WHY |
| CITING THIS CODE SECTION. USING NATURAL OR MECHANICAL |
| VENTILATION? |
| |
| 5- REVISE DUCTWORK LAYOUT. FLOOR PLAN IS MISSING SOME |
| DUCTWORK CONNECTIONS. SEE SUPPLY DUCTWORK ON BEDROOM |
| #2. THERE ARE 2 RETURN AIR GRILLS ON BEDROOM #3. |
| MISSING DUCTWORK ON BEDROOM #1 BATHROOM. REVISE AS |
| REQUIRED TO PROVIDE COMPLETE A/C LAYOUT. |
| |
| 6- MISSING RETURN AIR GRILL ON BEDROOM #1. |
| |
| JULIO GOMEZ |
| COMMERCIAL COMBINATION PLANS EXAMINER |