2011-02-01 13:18:26PROVIDE INTERRUPTING (AIC) CURRENT RATING FOR THE
 ELECTRICAL SERVICE. NEC 110.9
 CORRECT NOTES TO REFLECT THE CURRENT ELECTRIC CODE:
 2008 NEC
 PROVIDE AN INTERSYSTEM BONDING BAR AT THE SERVICE. NEC
 250.94
 THREE RECEPTACLES REQUIRED IN TWO HALLWAYS. NEC 210.52
 (H)
 A GFCI PROTECTED OUTLET IS REQUIRED AT THE REAR
 ELEVATION. NEC 210.8, 210.52 (E) (1)
 NOTE ON THE PLAN THE REQUIREMENT FOR TAMPER RESISTANT
 RECEPTACLES. NEC 406.11
 AT LEAST ONE SWITCH CONTROLLED LIGHTING OUTLET SHALL BE
 PROVIDED ON THE EXTERIOR SIDE OF THE SIDE ENTRANCE. NEC
 210.70 (A) (2) (B).
 BEDROOM RECEPTACLES MUST BE PROTECTED WITH COMBINATION
 - TYPE AFCI'S. NEC 210.12 (B)
 NOTE ON THE PLAN THAT THE SMOKE DETECTORS ARE TO BE
 INTERCONNECTED. FBC R313.2
  
 ROBERT LECKY, ELECTRIC PLAN REVIEW, 561-805-6718
  
  