2011-02-01 11:57:53PROVIDE THE INTERRUPTING (AIC) CURRENT RATING FOR THE
 SERVICE. NEC 110.9
 CORRECT NOTES TO REFLECT THE CURRENT ELECTRIC CODE:
 2008 NEC
 PROVIDE A BONDING BAR AT THE SERVICE. NEC 250.94
 RECEPTACLE REQUIRED IN HALLWAY. NEC 210.52 (H)
 A GFCI PROTECTED OUTLET IS REQUIRED AT THE REAR
 ELEVATION. NEC 210.8, 210.52 (E) (1)
 NOTE ON THE PLAN THE REQUIREMENT FOR TAMPER RESISTANT
 RECEPTACLES. NEC 406.11
 AT LEAST ONE SWITCH CONTROLLED LIGHTING OUTLET SHALL BE
 PROVIDED ON THE EXTERIOR SIDE OF THE REAR ENTRANCE. NEC
 210.70 (A) (2) (B).
 BEDROOM RECEPTACLES MUST BE PROTECTED WITH COMBINATION
 - TYPE AFCI'S. NEC 210.12 (B)
  
 ROBERT LECKY, ELECTRIC PLAN REVIEW, 561-805-6718
  