Plan Review Notes For Permit 10080506 |
Permit Number |
10080506 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2011-02-01 11:57:53 | PROVIDE THE INTERRUPTING (AIC) CURRENT RATING FOR THE | | SERVICE. NEC 110.9 | | CORRECT NOTES TO REFLECT THE CURRENT ELECTRIC CODE: | | 2008 NEC | | PROVIDE A BONDING BAR AT THE SERVICE. NEC 250.94 | | RECEPTACLE REQUIRED IN HALLWAY. NEC 210.52 (H) | | A GFCI PROTECTED OUTLET IS REQUIRED AT THE REAR | | ELEVATION. NEC 210.8, 210.52 (E) (1) | | NOTE ON THE PLAN THE REQUIREMENT FOR TAMPER RESISTANT | | RECEPTACLES. NEC 406.11 | | AT LEAST ONE SWITCH CONTROLLED LIGHTING OUTLET SHALL BE | | PROVIDED ON THE EXTERIOR SIDE OF THE REAR ENTRANCE. NEC | | 210.70 (A) (2) (B). | | BEDROOM RECEPTACLES MUST BE PROTECTED WITH COMBINATION | | - TYPE AFCI'S. NEC 210.12 (B) | | | | ROBERT LECKY, ELECTRIC PLAN REVIEW, 561-805-6718 | | |
|