1 |
|
Notes |
Date |
Text |
2011-01-28 09:53:11 | MASTER FOR NEW SINGLE FAMILY RESIDENCE (R3) MECHANICAL | | REVIEW CHECKLIST. | | 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS. | | | | 1- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. | | N1100.3 OF 2007 FLORIDA RESIDENTIAL CODE. | | | | 2- PROVIDE COOLING AND HEATING LOAD CALCULATIONS AS | | REQUIRED BY SEC. N1107.AB OF 2007 FLORIDA RESIDENTIAL | | CODE. | | | | 3- SPECIFY SUPPLY AND RETURN CFM'S ON EACH ROOM ROOM. | | COORDINATE WITH THE HEATING AND COOLING CALCULATIONS | | REQUIRED BY SEC. N1100.AB. | | | | 4- SHEET A-8.0: | | A) REVISE MECHANICAL NOTE #3:. REVISE MINIMUM SEER AND | | COORDINATE EQUIPMENT MODEL WITH LOAD CALCULATIONS | | REQUIRED ON ITEM #2 ABOVE. | | | | B) REVISE OUTSIDE AIR CALCULATIONS NOTE: SEE 2007 | | FLORIDA RESIDENTIAL CODE. CITE CORRESPONDING SECTION | | AND MAKE SURE CONDITIONED FLOOR AREA MATCHES FLOOR AREA | | SPECIFIED ON THE ARCHITECTURAL PLANS. CLARIFY WHY | | CITING THIS CODE SECTION. USING NATURAL OR MECHANICAL | | VENTILATION? | | | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561)805-6712 |
|