2011-01-28 09:53:11MASTER FOR NEW SINGLE FAMILY RESIDENCE (R3) MECHANICAL
 REVIEW CHECKLIST.
 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 1- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC.
 N1100.3 OF 2007 FLORIDA RESIDENTIAL CODE.
  
 2- PROVIDE COOLING AND HEATING LOAD CALCULATIONS AS
 REQUIRED BY SEC. N1107.AB OF 2007 FLORIDA RESIDENTIAL
 CODE.
  
 3- SPECIFY SUPPLY AND RETURN CFM'S ON EACH ROOM ROOM.
 COORDINATE WITH THE HEATING AND COOLING CALCULATIONS
 REQUIRED BY SEC. N1100.AB.
  
 4- SHEET A-8.0:
 A) REVISE MECHANICAL NOTE #3:. REVISE MINIMUM SEER AND
 COORDINATE EQUIPMENT MODEL WITH LOAD CALCULATIONS
 REQUIRED ON ITEM #2 ABOVE.
  
 B) REVISE OUTSIDE AIR CALCULATIONS NOTE: SEE 2007
 FLORIDA RESIDENTIAL CODE. CITE CORRESPONDING SECTION
 AND MAKE SURE CONDITIONED FLOOR AREA MATCHES FLOOR AREA
 SPECIFIED ON THE ARCHITECTURAL PLANS. CLARIFY WHY
 CITING THIS CODE SECTION. USING NATURAL OR MECHANICAL
 VENTILATION?
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712