2010-09-02 12:20:14 | *****REVIEW COMMENTS - FIRE***** | | | | 1) PROVIDE VISUAL NOTIFICATION APPLIANCES FOR WORKROOMS | | #609 AND #614. | | | | 2) PROVIDE NOTIFICATION APPLIANCE CIRCUIT WIRING, | | CANDELA RATINGS ETC. | | | | 3) "SCOPE OF JOB" NOTE STATES THREE HORN STROBE UNITS | | ARE BEING ADDED. THESE DEVICES SHOULD BE | | SPEAKER-STROBES. | | | | 4) DRAWING SCALE NOT FOUND. | | | | 5) PROVIDE MANUAL PULL STATION AT EACH EXIT. | | | | MIKE CARSILLO, BATTALION CHIEF | | & WESLEY JOLIN | | WPB FIRE PLAN REVIEW | | 561-805-6730 |
|