Plan Review Notes
Plan Review Notes For Permit 10080396
Permit Number 10080396
Review Stop M
Sequence Number 3
Notes
Date Text
2011-03-30 14:44:03REVIEW #: 2ND (FOR NEWLY DESIGNED BUILDING)
 ACTION:DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THESE COMMENTS ARE NUMBERED TO CORRESPOND WITH PREVIOUS
 REVIEW FOR CONTINUITY. ANY ADDITIONAL NEW COMMENTS WILL
 BE ADDED TO THE END OF THE REVIEW.
  
 1. OK
  
 2. OK
  
 3. OK
  
 4. EF-3 AND EF-5 ON PAGE M6-1 APPEAR TO HAVE THE ROOM
 NUMBER AND THE CFM REVERSED. PLEASE CORRECT TO
 CORRESPOND WITH THE FLOOR PLAN. FBC-M 304.11.
  
 5. OK
  
 6. OK
  
 7. OK
  
 8. OK
  
 9. OK
  
 10. OK
  
 11. OK
  
 12. OK
  
 13. NOT ADEQUATELY ADDRESSED: FBC-M SECTION 404
 REQUIRES A MINIMUM VENTILATION RATE OF 1.5 CFM/SQ.FT.
 THE VENTILATION RATE IS ALLOWED TO BE INTERMITTENT IF
 THE FAN IS CONTROLLED BY CARBON MONOXIDE SENSORS. PAGE
 M2-1 SHOWS THE FAN BEING CONTROLLED BY CARBON DIOXIDE
 SENSORS. THIS DOES NOT MEET THE REQUIREMENT OF THE CODE
 FOR AN ENCLOSED PARKING GARAGE. ALSO, SECTION 404
 REQUIRES THAT IF INTERMITTENT VENTILATION IS USED, A
 MINIMUM CONTINUOUS VENTILATION RATE OF 0.05 CFM/SQ.FT
 BE PROVIDED. SHOW HOW THIS MINIMUM CONTINUOUS RATE IS
 TO BE PROVIDED. IN ADDITION, WHAT IS THE SIZE OF THE
 INTAKE LOUVER? NO SIZE IS GIVEN ON THE PLANS. THE SIZE
 MUST BE LARGE ENOUGH TO PROVIDE AT LEAST 1000 CFM OF
 MAKE-UP AIR FOR THE EXHAUST FAN BEING PROPOSED.
  
 NOTE: PROVIDE SIZES FOR ALL OUTDOOR LOUVERS.
  
 14. NEW COMMENT: AHU-10 RETURN AIR SYSTEM IS
 REDESIGNED, ELIMINATING DUCTED RETURN AND UTILIZING
 TRANSFER DUCTS FROM OFFICES INTO ADJACENT HALL 37.
 THERE DOES NOT APPEAR TO BE A CENTRALIZED R/A INTAKE
 ASSOCIATED WITH AHU-10 LARGE ENOUGH TO DRAW ALL THE
 RETURN AIR FROM THESE TRANSFER DUCTS BACK TO THE AHU.
 PLEASE SHOW HOW BALANCED RETURN IS TO BE ACHIEVED IN
 THIS AREA PER FBC-M 601.4. ALSO, THE TRANSFER DUCTS
 FROM THE OFFICE ARE NOT SIZED PER THE BALANCED RETURN
 AIR EXCEPTIONS UNDER FBC-M 601.4. THE TRANSFER DUCT
 MUST BE MINIMUM 1.5 TIMES THE SIZE OF THE SUPPLY DUCT.
 IN MOST CASES THE PLAN SHOWS A DUCT WITH APPROXIMATELY
 THE SAME SQUARE INCHES. SHOW HOW COMPLIANCE WITH FBC-M
 601.4 IS TO BE ACHIEVED IN THESE AREAS.
  
 NOTE: THE KITCHEN HOOD EXHAUST SYSTEM IS EXCLUDED FROM
 THE SCOPE OF THIS REVIEW. SEPARATE PLANS AND PERMIT
 APPLICATIONS ARE REQUIRED FOR THE HOOD SYSTEM AND THE
 FIRE SUPPRESSION SYSTEM.
  
  