2011-04-01 09:14:55 | BUILDING PLAN REVIEW |
| PERMIT: 10080396 |
| ADD: 2100 N FLORIDA MANGO |
| CONT: TO BE DETERMINED |
| CONTACT: PBA JOINT VENTURE INC |
| TEL: (561)689-3745 |
| |
| FL BLD CODE= 2007 FLORIDA BUILDING CODE |
| W/ 2009 FBC SUPPLEMENTS |
| * WEST PALM BEACH AMENDMENTS |
| |
| APRIL 01/2011 |
| 3RD REVIEW/ 2ND REVIEW OF 1 STORY BUILDING |
| |
| ACTION: DENIED |
| |
| 1) COVERSHEET: |
| |
| 1A-C) COMPLIED. |
| |
| 2) SECOND REQUEST THE SURVEY THE FLOOD DATA IS |
| BLANK!!!!!! |
| , FBC BUILDING 3110.1.2 / CITY OF WPB CODE OF |
| ORDINANCES SECTION 94-546. STRUCTURE IS LOCATED IN AN |
| "A-9" FLOOD ZONE. A FLOOD ELEVATION CERTIFICATE WILL BE |
| REQUIRED. |
| |
| MINIMUM ELEVATION FOR FINISH FLOOR TO BE ELEVATION |
| 13'-6" NGVD. |
| |
| FEMA FORM OMB NO. 1660-0008 EXPIRES: |
| MARCH 31, 2012. |
| FEMA'S NEW ELEVATION CERTIFICATE (EC) WAS APPROVED FOR |
| USE, EFFECTIVE MARCH 16, 2009, THROUGH MARCH 31, 2012. |
| THE NEW EC WILL BE PHASED IN ON A VOLUNTARY BASIS UNTIL |
| MARCH 31, 2010. ALTHOUGH THE OLD VERSION OF THE FORM IS |
| NO LONGER AVAILABLE FOR DISTRIBUTION, EXISTING COPIES |
| MAY BE USED UNTIL MARCH 31, 2010. ELEVATIONS CERTIFIED |
| ON OR AFTER APRIL 1, 2010, MUST BE SUBMITTED ON THE NEW |
| FORM. |
| |
| ADDITIONAL INFORMATION ON THE DIFFERENCES, THE NEW |
| FORM, AND INSTRUCTIONS ARE AVAILABLE AT: |
| HTTP://WWW.FEMA.GOV/BUSINESS/NFIP/ELVINST.SHTM |
| |
| 3A) SECOND REQUEST!!!!! THIS AREA IS THE FRONT ENTRY, |
| AND THE CANOPY MAY HAVE BEEN A ZONING REQUIREMENT BUT |
| WILL ALSO BE USED AS A DROP OFF ZONE AS A PASSENGER |
| LOADING ZONE. PLEASE REVIEW SP-1 THE PLANS INDICATE A |
| PASSENGER LOADING ZONE VERSES A FLARED CURB 2007/ 2009 |
| FBC-B 11-4.6.6 SEE FIGURE 11-10. |
| PLEASE SEE 11-6.3 ACCESS AISLE SHALL BE STRIPED |
| DIAGONALLY TO DESIGNATE IT AS A NO-PARKING ZONE.CURB |
| RAMPS MUST BE LOCATED OUTSIDE OF THE DISABLED PARKING |
| SPACES AND ACCESS AISLES. PLEASE BE AWARE OF 11-4.29.5 |
| DETECTABLE WARNINGS AT HAZARDOUS VEHICLAR AREAS. |
| |
| 3B) COMPLIED. |
| |
| 4) SHEET A-4.0; |
| 4A) SECOND REQUEST!!! DETAILS 3 & 4 BOTH INDICATE THE |
| USE OF GALVANIZED WIRE LATH OVER TYVAK WRAP, PLEASE |
| REVIEW FBC-B 1404.2.1 NEW TO THE 2007 FBC A BOND BREAK |
| WILL BE REQUIRED BETWEEN THE WIRE LATH AND TYVAK WRAP. |
| PLEASE REVIEW THE THREE METHODS OF ACHIVING THIS, A |
| PAPER BACK LATH AND TYVAK SYSTEM WILL ACHIEVE THIS |
| REQUIREMENT. |
| |
| 4B) SECOND REQUEST!!!! THE PLANS INDICATE THE USE OF |
| USE OF HORIZONTAL RIB-LATH BEING ATTACHED TO METAL HIGH |
| HAT, PLEASE PROVIDE TYPE OF FASTENER AND SPACING, FBC-B |
| 2510.3. ASTM C 926 AND ASTM C 1063. |
| |
| 4C)COMPLIED. |
| |
| 5-6) COMPLIED. |
| |
| 7) PRODUCT APPROVALS: |
| 7A) SEMI-COMPLIED ENGLERT METAL ROOFING FL 11727. |
| MISSING THE INSTALATION PORTION OF THE REPORT. |
| |
| 7B) SEMI-COMPLIED JOHNMANVILLE NOA 06-0417.09 THE SAME |
| REPORT IS FILED TWICE IN THE BACK UP DOCUMENT FOLDER. |
| THE ONE REPORT THAT HAS IDENTIFIED WHICH SUB-SYSTEM IS |
| TO BE INSTALLED ON PAGE 15. PLEASE PROVIDE WHICH OPTION |
| FOUND ON PAGE 15 IS A NON-INSULATED ROOF WILL BE |
| INSTALLED. THERE ARE THREE OPTIONS . OPTION# 1 HAS LOW |
| PRESSURES AND LIMITATION #9. OPTIONS 2& 3 LIMITATION# 7 |
| WHICH ALLOWS FOR ENHANCED FASTENING, PLEASE CICCLE |
| WHICH SYSTEM TO BE INSTALLED ANAD PROVIDE CALCULATIONS |
| FOR ZONES 2 & 3. |
| |
| 8) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| INFORMATION. |
| |
| INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. |
| A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| JAMES A. WITMER C.B.O. |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: (561)805-6715 |
| FAX:(561)805-6731 |
| E-MAIL: [email protected] |
| |