2011-02-15 15:54:09 | REVIEW #: 1ST (FOR NEWLY DESIGNED BUILDING) |
| ACTION:DENIED |
| |
| FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS |
| FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| |
| 1. SOME DUCTS PENETRATING THE SMOKE PARTITION AT |
| STORAGE ROOM 18 AND A/V 17 ARE SHOWN WITH SMOKE DAMPERS |
| WHILE OTHERS ARE NOT. DESIGN INTENT IS NOT CLEAR. IN |
| SMOKE PARTITIONS, SMOKE DAMPERS ARE ONLY REQUIRED IN |
| AIR TRANSFER OPENINGS AND ARE NOT REQUIRED AT DUCT |
| PENETRATIONS PER FBC-B 710.7. |
| |
| 2. RETURN DUCT SERVING ROOM A/V 17 IS MISSING SIZE, CFM |
| AND GRILL DESIGNATION. PROVIDE MISSING INFO ON PLANS |
| PER FBC-M 603.1. |
| |
| 3. DUCTS PENETRATING THE FIRE RATED CORRIDOR SHALL BE |
| PROTECTED WITH FIRE AND SMOKE DAMPERS PER FBC-M 607.5.3 |
| AND 607.5.4. |
| |
| 4. TWO FANS MARKED AS EF-3 ON FLOOR PLAN AND ON THE FAN |
| SCHEDULE, BUT THEY DO NOT SHOW THE SAME CFM ON THE |
| FLOOR PLAN. PLEASE COORDINATE FLOOR PLANS AND |
| SCHEDULES. CONSIDER NAMING EACH FAN INDIVIDUALLY TO |
| INDICATE THE AREAS BEING SERVED BY EACH PER FBC-M |
| 304.11. |
| |
| 5. RESTROOMS 39 AND 40 SERVE A LARGE ASSEMBLY SPACE AND |
| SHALL BE CAPABLE OF PROVIDING A HIGHER VENTILATION RATE |
| DURING PEAK USAGE TIMES OF 70 CFM PER WATER CLOSET |
| AND/OR URINAL PER ASHRAE 62.1 TABLE 6-4, NOTE D. THE |
| SIX FIXTURES IN THE MEN'S WOULD REQUIRE 420 CFM AND THE |
| 7 IN THE WOMEN'S WOULD REQUIRE 490 CFM DURING PEAK |
| USAGE TIMES. A LOWER RATE OF 50 CFM PER FIXTURE MAY BE |
| PROVIDED (300 CFM MEN'S AND 350 CFM WOMEN'S) DURING |
| LOWER USAGE TIMES. |
| |
| 6. THE EXHAUST FAN SERVING ROOM JANITOR 22 HAS NO DATA, |
| IS NOT LABELED ON PLANS AND DOES NOT APPEAR ON FAN |
| SCHEDULE. PROVIDE MISSING DATA PER FBC-M 501.1. |
| |
| 7. AHU-5 ON SCHEDULE CALLS FOR 1800 CFM WHILE THE FLOOR |
| PLAN CALLS FOR 1925 CFM. WHICH IS CORRECT? COORDINATE |
| FLOOR PLANS AND SCHEDULES. FBC-M 603.1. |
| |
| 8. AHU-7 ON SCHEDULE CALLS FOR 1800 CFM WHILE THE FLOOR |
| PLAN CALLS FOR 1975 CFM. WHICH IS CORRECT? COORDINATE |
| FLOOR PLANS AND SCHEDULES. FBC-M 603.1. |
| |
| 9. AHU-7 ON FLOOR PLAN SHOWS 1975 CFM OF SUPPLY AND |
| 2000 CFM OF RETURN. HOW WILL OUTSIDE AIR BE INTRODUCED |
| IF THE SYSTEM IS DESIGNED TO RETURN 100% OF THE SUPPLY |
| QUANTITY? THIS CONDITION APPEARS ON SEVERAL SYSTEMS. |
| THIS WOULD ALSO CREATE A NEGATIVE PRESSURE. BUILDINGS |
| SHALL BE PRESSURIZEDIN ACCORDANCE WITH FBC-B |
| 13-409.AB.2. SHOW HOW VENTILATION AIR IS TO BE |
| INTRODUCED INTO EACH OF THESE SYSTEMS PER FBC-M 401.1. |
| |
| 10. AHU-8 ON SCHEDULE CALLS FOR 1800 CFM WHILE THE |
| FLOOR PLAN CALLS FOR 2075 CFM. WHICH IS CORRECT? |
| COORDINATE FLOOR PLANS AND SCHEDULES. FBC-M 603.1. |
| ALSO, SUPPLY AIR SYSTEMS EXCEEDING 2000 CFM SHALL BE |
| PROVIDED WITH FAN SHUT-DOWN BY SMOKE DETECTOR PER FBC-M |
| 606.2.1. |
| |
| 11. AHU-9 ON SCHEDULE CALLS FOR 1800 CFM WHILE THE |
| FLOOR PLAN CALLS FOR 2000 CFM PLUS ONE GRILL SERVING |
| ROOM RECEPTION 49 WHICH IS MISSING CFM AND GRILL |
| DESIGNATION. WHICH IS CORRECT? COORDINATE FLOOR PLANS |
| AND SCHEDULES. PROVIDE MISSING GRILL DATA. FBC-M 603.1. |
| ALSO, SUPPLY AIR SYSTEMS EXCEEDING 2000 CFM SHALL BE |
| PROVIDED WITH FAN SHUT-DOWN BY SMOKE DETECTOR PER FBC-M |
| 606.2.1. |
| |
| 12. AHU-11 ON SCHEDULE CALLS FOR 1800 CFM WHILE THE |
| FLOOR PLAN CALLS FOR 2075 CFM. WHICH IS CORRECT? |
| COORDINATE FLOOR PLANS AND SCHEDULES. FBC-M 603.1. |
| ALSO, SUPPLY AIR SYSTEMS EXCEEDING 2000 CFM SHALL BE |
| PROVIDED WITH FAN SHUT-DOWN BY SMOKE DETECTOR PER FBC-M |
| 606.2.1. |
| |
| 13. STORAGE ROOM 19 IS CONFIGURED FOR VEHICLE |
| ENTRY/PARKING. ENCLOSED PARKING GARAGE SHALL BE |
| PROVIDED WITH MECHANICAL VENTILATION IN ACCORDANCE WITH |
| FBC-M SECTION 404. |
| |
| NOTE: THE KITCHEN HOOD EXHAUST SYSTEM IS EXCLUDED FROM |
| THE SCOPE OF THIS REVIEW. SEPARATE PLANS AND PERMIT |
| APPLICATIONS ARE REQUIRED FOR THE HOOD SYSTEM AND THE |
| FIRE SUPPRESSION SYSTEM. |
| |
| |