2011-02-15 15:54:09REVIEW #: 1ST (FOR NEWLY DESIGNED BUILDING)
 ACTION:DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. SOME DUCTS PENETRATING THE SMOKE PARTITION AT
 STORAGE ROOM 18 AND A/V 17 ARE SHOWN WITH SMOKE DAMPERS
 WHILE OTHERS ARE NOT. DESIGN INTENT IS NOT CLEAR. IN
 SMOKE PARTITIONS, SMOKE DAMPERS ARE ONLY REQUIRED IN
 AIR TRANSFER OPENINGS AND ARE NOT REQUIRED AT DUCT
 PENETRATIONS PER FBC-B 710.7.
  
 2. RETURN DUCT SERVING ROOM A/V 17 IS MISSING SIZE, CFM
 AND GRILL DESIGNATION. PROVIDE MISSING INFO ON PLANS
 PER FBC-M 603.1.
  
 3. DUCTS PENETRATING THE FIRE RATED CORRIDOR SHALL BE
 PROTECTED WITH FIRE AND SMOKE DAMPERS PER FBC-M 607.5.3
 AND 607.5.4.
  
 4. TWO FANS MARKED AS EF-3 ON FLOOR PLAN AND ON THE FAN
 SCHEDULE, BUT THEY DO NOT SHOW THE SAME CFM ON THE
 FLOOR PLAN. PLEASE COORDINATE FLOOR PLANS AND
 SCHEDULES. CONSIDER NAMING EACH FAN INDIVIDUALLY TO
 INDICATE THE AREAS BEING SERVED BY EACH PER FBC-M
 304.11.
  
 5. RESTROOMS 39 AND 40 SERVE A LARGE ASSEMBLY SPACE AND
 SHALL BE CAPABLE OF PROVIDING A HIGHER VENTILATION RATE
 DURING PEAK USAGE TIMES OF 70 CFM PER WATER CLOSET
 AND/OR URINAL PER ASHRAE 62.1 TABLE 6-4, NOTE D. THE
 SIX FIXTURES IN THE MEN'S WOULD REQUIRE 420 CFM AND THE
 7 IN THE WOMEN'S WOULD REQUIRE 490 CFM DURING PEAK
 USAGE TIMES. A LOWER RATE OF 50 CFM PER FIXTURE MAY BE
 PROVIDED (300 CFM MEN'S AND 350 CFM WOMEN'S) DURING
 LOWER USAGE TIMES.
  
 6. THE EXHAUST FAN SERVING ROOM JANITOR 22 HAS NO DATA,
 IS NOT LABELED ON PLANS AND DOES NOT APPEAR ON FAN
 SCHEDULE. PROVIDE MISSING DATA PER FBC-M 501.1.
  
 7. AHU-5 ON SCHEDULE CALLS FOR 1800 CFM WHILE THE FLOOR
 PLAN CALLS FOR 1925 CFM. WHICH IS CORRECT? COORDINATE
 FLOOR PLANS AND SCHEDULES. FBC-M 603.1.
  
 8. AHU-7 ON SCHEDULE CALLS FOR 1800 CFM WHILE THE FLOOR
 PLAN CALLS FOR 1975 CFM. WHICH IS CORRECT? COORDINATE
 FLOOR PLANS AND SCHEDULES. FBC-M 603.1.
  
 9. AHU-7 ON FLOOR PLAN SHOWS 1975 CFM OF SUPPLY AND
 2000 CFM OF RETURN. HOW WILL OUTSIDE AIR BE INTRODUCED
 IF THE SYSTEM IS DESIGNED TO RETURN 100% OF THE SUPPLY
 QUANTITY? THIS CONDITION APPEARS ON SEVERAL SYSTEMS.
 THIS WOULD ALSO CREATE A NEGATIVE PRESSURE. BUILDINGS
 SHALL BE PRESSURIZEDIN ACCORDANCE WITH FBC-B
 13-409.AB.2. SHOW HOW VENTILATION AIR IS TO BE
 INTRODUCED INTO EACH OF THESE SYSTEMS PER FBC-M 401.1.
  
 10. AHU-8 ON SCHEDULE CALLS FOR 1800 CFM WHILE THE
 FLOOR PLAN CALLS FOR 2075 CFM. WHICH IS CORRECT?
 COORDINATE FLOOR PLANS AND SCHEDULES. FBC-M 603.1.
 ALSO, SUPPLY AIR SYSTEMS EXCEEDING 2000 CFM SHALL BE
 PROVIDED WITH FAN SHUT-DOWN BY SMOKE DETECTOR PER FBC-M
 606.2.1.
  
 11. AHU-9 ON SCHEDULE CALLS FOR 1800 CFM WHILE THE
 FLOOR PLAN CALLS FOR 2000 CFM PLUS ONE GRILL SERVING
 ROOM RECEPTION 49 WHICH IS MISSING CFM AND GRILL
 DESIGNATION. WHICH IS CORRECT? COORDINATE FLOOR PLANS
 AND SCHEDULES. PROVIDE MISSING GRILL DATA. FBC-M 603.1.
 ALSO, SUPPLY AIR SYSTEMS EXCEEDING 2000 CFM SHALL BE
 PROVIDED WITH FAN SHUT-DOWN BY SMOKE DETECTOR PER FBC-M
 606.2.1.
  
 12. AHU-11 ON SCHEDULE CALLS FOR 1800 CFM WHILE THE
 FLOOR PLAN CALLS FOR 2075 CFM. WHICH IS CORRECT?
 COORDINATE FLOOR PLANS AND SCHEDULES. FBC-M 603.1.
 ALSO, SUPPLY AIR SYSTEMS EXCEEDING 2000 CFM SHALL BE
 PROVIDED WITH FAN SHUT-DOWN BY SMOKE DETECTOR PER FBC-M
 606.2.1.
  
 13. STORAGE ROOM 19 IS CONFIGURED FOR VEHICLE
 ENTRY/PARKING. ENCLOSED PARKING GARAGE SHALL BE
 PROVIDED WITH MECHANICAL VENTILATION IN ACCORDANCE WITH
 FBC-M SECTION 404.
  
 NOTE: THE KITCHEN HOOD EXHAUST SYSTEM IS EXCLUDED FROM
 THE SCOPE OF THIS REVIEW. SEPARATE PLANS AND PERMIT
 APPLICATIONS ARE REQUIRED FOR THE HOOD SYSTEM AND THE
 FIRE SUPPRESSION SYSTEM.
  
  