Plan Review Notes For Permit 10080396 |
Permit Number |
10080396 |
|
Review Stop |
FIRE |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2011-02-16 14:22:27 | 2100 NORTH FLORIDA MANGO ROAD | | PERMIT NUMBER 10080396 | | | | | | 1. TACTILE SIGNAGE REQUIRED AT ALL EXIT DOOR LOCATIONS. | | | | 2. A KNOX-BOX AND KNOX LOCKING CAPS WILL BE REQUIRED | | FOR THE PROJECT. | | | | 3. SEPARATE PLANS AND PERMITS REQUIRED FOR FIRE ALARM | | SYSTEM INSTALLATION. THE FIRE SPRINKLER SYSTEM AND FIRE | | ALARM SYSTEM SHALL BE MONITORED BY A THIRD PARTY | | APPROVED FOR CENTRAL STATION SERVICE. | | | | 4. FIRE ALARM STROBE MISSING FROM RESTROOM 44. | | | | 5. NOTE # 17 IS INCORRECT ON SHEET FAO.1. DUCT SMOKE | | DETECTORS WHEN ACTIVATED SHALL CAUSE THE BUILDING FIRE | | ALARM TO ACTIVATE. | | | | 6. SEPARATE PLANS AND PERMITS REQUIRED FOR THE HOOD, | | DUCT, AND FIRE SUPPRESSION SYSTEM. | | | | 7. ALL NEW FIRE AND SMOKE DAMPERS ARE TO BE DROP TESTED | | AFTER INSTALLATION TO ENSURE PROPER FUNCTION. | | | | 8. THE KEYPAD/ACCESS CONTROL FOR DOOR DEVICES SHOWN ON | | SHEET A-1.O SHALL NOT INTERFERE WITH EXITING. | | | | 9. SEPARATE PLANS AND PERMITS REQUIRED FOR GENERATOR. | | | | 10. A MALTESE CROSS IDENTIFIED WITH THE LETTER R IS TO | | BE PROVIDED NEAR THE MAIN DOOR SIGNIFYING THAT A WOOD | | TRUSS IS PRESENT. | | | | | | MIKE CARSILLO, BATTALION CHIEF | | BUREAU OF FIRE PREVENTION |
|