2011-02-24 09:16:21SHEET 053 E1-2
 PLEASE PROVIDE A SPECIFICATION FOR THE LIGHT POLE
 DESIGN AND FOUNDATION.
  
 SHEET 055 E3-1
 GFCI PROTECTION IS REQUIRED FOR RECEPTACLES WITHIN 6
 FEET OF THE BAR SINK. NEC 210.8(B)(5)
  
 SHEET 056 E5-1
 MINIMUM SIZE SERVICE GROUNDING ELECTRODE CONDUCTOR HAS
 BEEN MISLABELED ON THE RISER DIAGRAM. NEC T. 250.66
 PANEL A AND B FEEDER OVERCURRENT PROTECTION SHOULD BE
 NO GREATER THAN THE PANELBOARD RATING. NEC 408.36
  
  
 ROBERT LECKY, ELECTRICAL PLAN REVIEW, 561-805-6718
  