Date |
Text |
2011-02-11 14:38:05 | BUILDING PLAN REVIEW |
| PERMIT: 10080396 |
| ADD: 2100 N FLORIDA MANGO |
| CONT: TO BE DETERMINED |
| CONTACT: PBA JOINT VENTURE INC |
| TEL: (561)689-3745 |
| |
| FL BLD CODE= 2007 FLORIDA BUILDING CODE |
| W/ 2009 FBC SUPPLEMENTS |
| * WEST PALM BEACH AMENDMENTS |
| |
| FEB. 11/ 2011 |
| 2ND REVIEW/ 1ST REVIEW OF 1 STORY BUILDING |
| |
| ACTION: DENIED |
| |
| 1) COVERSHEET: |
| |
| 1A) PLANS INDICATE THIS BUILDING TO BE FULLY FIRE |
| SPRINKLERED BUT NO PLANS WERE SUBMITTED FOR THIS |
| REVIEW. THE LIFE SAFETY REQUIREMENTS |
| INDICATE THAT AREA INCREASES WERE TAKEN UNDER 2007 |
| FBC-B 506.3. |
| |
| 1B) THE COVER SHEET LIFE SAFETY REQUIREMENTS UNDER THE |
| HEADING OCCUPANCY INDICATE THIS TO BE A MIXED USE, |
| NON-SEPARARTED OCCUPANCY. THE PLANS DO INDICATE A 1 |
| HOUR RATED CORRIDOR FOR THE ASSEMBLY OCCUPANCY, BUT |
| FAIL TO TAKE INTO ACCOUNT : |
| 1B)(1) NO FIRE SPRINKLER PLANS SUBMITTED TO BE ABLE TO |
| TAKE CREDIT FOR INCIDENTAL USE AREAS, (FBC-BTABLE 502). |
| 1B)(2) THE PLANS DO NOT ADDRESS THE REQUIREMENTS FOR |
| STORAGE ROOM > 100 SQ FT TO RESIST THE PASSAGE OF |
| SMOKE, THE DOORS ARE TO BE SELF CLOSING OR AUTOMATIC |
| CLOSING UPON DETECTION OF SMOKE IN ACCORDANCE WITH |
| SECTION 715.4.7.3. |
| |
| 1C)THE COVER SHEET LIFE SAFETY REQUIREMENTS UNDER THE |
| HEADING OCCUPANCY INDICATE THIS TO BE A MIXED USE, |
| NON-SEPARARTED OCCUPANCY. THE PLANS DO INDICATE A 1 |
| HOUR RATED CORRIDOR FOR THE ASSEMBLY OCCUPANCY, BUT |
| FAIL TO TAKE INTO ACCOUNT : |
| 1B)(1) NO FIRE SPRINKLER PLANS SUBMITTED TO BE ABLE TO |
| TAKE CREDIT FOR INCIDENTAL USE AREAS, (FBC-BTABLE 502). |
| 1B)(2) THE PLANS DO NOT ADDRESS THE REQUIREMENTS FOR |
| STORAGE ROOM > 100 SQ FT TO RESIST THE PASSAGE OF |
| SMOKE, THE DOORS ARE TO BE SELF CLOSING OR AUTOMATIC |
| CLOSING UPON DETECTION OF SMOKE IN ACCORDANCE WITH |
| SECTION 715.4.7.3. |
| |
| |
| 2) SURVEY THE FLOOD DATA IS BLANK, FBC BUILDING |
| 3110.1.2 / CITY OF WPB CODE OF ORDINANCES SECTION |
| 94-546. STRUCTURE IS LOCATED IN AN "A-9" FLOOD ZONE. A |
| FLOOD ELEVATION CERTIFICATE WILL BE REQUIRED. MINIMUM |
| ELEVATION FOR FINISH FLOOR TO BE ELEVATION 13'-6" NGVD. |
| |
| FEMA FORM OMB NO. 1660-0008 EXPIRES: |
| MARCH 31, 2012. |
| FEMA'S NEW ELEVATION CERTIFICATE (EC) WAS APPROVED FOR |
| USE, EFFECTIVE MARCH 16, 2009, THROUGH MARCH 31, 2012. |
| THE NEW EC WILL BE PHASED IN ON A VOLUNTARY BASIS UNTIL |
| MARCH 31, 2010. ALTHOUGH THE OLD VERSION OF THE FORM IS |
| NO LONGER AVAILABLE FOR DISTRIBUTION, EXISTING COPIES |
| MAY BE USED UNTIL MARCH 31, 2010. ELEVATIONS CERTIFIED |
| ON OR AFTER APRIL 1, 2010, MUST BE SUBMITTED ON THE NEW |
| FORM. |
| |
| ADDITIONAL INFORMATION ON THE DIFFERENCES, THE NEW |
| FORM, AND INSTRUCTIONS ARE AVAILABLE AT: |
| HTTP://WWW.FEMA.GOV/BUSINESS/NFIP/ELVINST.SHTM |
| |
| 3A) PLEASE REVIEW SP-1 THE PLANS INDICATE A PASSENGER |
| LOADING ZONE VERSES A FLARED CURB 2007/ 2009 FBC-B |
| 11-4.6.6 SEE FIGURE 11-10. |
| PLEASE SEE 11-6.3 ACCESS AISLE SHALL BE STRIPED |
| DIAGONALLY TO DESIGNATE IT AS A NO-PARKING ZONE.CURB |
| RAMPS MUST BE LOCATED OUTSIDE OF THE DISABLED PARKING |
| SPACES AND ACCESS AISLES. PLEASE BE AWARE OF 11-4.29.5 |
| DETECTABLE WARNINGS AT HAZARDOUS VEHICLAR AREAS. |
| |
| 3B) SHEET SP-1 ALSO INDICATES 2 HANDICAPPED SPACES BUT |
| THERE IS NO CUT DETAILS FROM THE ACCESS AISLE TO |
| SIDEWALK AND CURB CUTS, SHEET SP-2 INDICATES TWO STYLES |
| OF CURB CUTS, WHICH TYPE IS TO BE USED FOR THIS |
| INSTALATION, PLEASE KEEP IN MIND CROSS SLOPE OF AN |
| ACCESSIBLE ROUTE SHALL NOT EXCEED 1:50. 2007/ 2009 |
| FBC-B 11-4.3.7. PLEASE BE AWARE OF 11-4.29.5 DETECTABLE |
| WARNINGS AT HAZARDOUS VEHICLAR AREAS. |
| |
| 4) SHEET A-4.0; |
| 4A) DETAILS 3 & 4 BOTH INDICATE THE USE OF GALVANIZED |
| WIRE LATH OVER TYVAK WRAP, PLEASE REVIEW FBC-B 1404.2.1 |
| NEW TO THE 2007 FBC A BOND BREAK WILL BE REQUIRED |
| BETWEEN THE WIRE LATH AND TYVAK WRAP. PLEASE REVIEW THE |
| THREE METHODS OF ACHIVING THIS, A PAPER BACK LATH AND |
| TYVAK SYSTEM WILL ACHIEVE THIS REQUIREMENT. |
| |
| 4B) THE PLANS INDICATE THE USE OF USE OF HORIZONTAL |
| RIB-LATH BEING ATTACHED TO METAL HIGH HAT, PLEASE |
| PROVIDE TYPE OF FASTENER AND SPACING, FBC-B 2510.3. |
| ASTM C 926 AND ASTM C 1063. |
| |
| 4C) R-19 UNFACED BATT INSULATION VERSES THE ENERGY |
| CALCS CELOUSE R-20 INSULATION. PLEASE ALSO REVIEW A-8.2 |
| THE REQUIREMENTSPACING FOR HIHAT WHEN INSULATION BATT |
| OR BLANKET IS LAIDED DIRECTLY ON TOP OF THE HI-HAT. |
| |
| 5) SHEET A8-0 DETAIL# 3 A 1 HOUR RATED WALL DETAIL |
| INDICATES THE ROOF DECK TO BE A METAL DECK, PLEASE |
| CORRECT AND PROVIDE A DETAIL FOR SYSTEM UL DESIGN NO. |
| HW-D-0011 . |
| |
| 6) THE PLANS DO NOT PROVIDE THE MEAN ROOF HEIGHT IN |
| EITHER S.01 WIND DESIGN CRITERIA NOR ON S0.2 THE DESIGN |
| PRESSURE TABLES, HAS THE HEIGHT FACTOR BEEN TAKEN INTO |
| ACCOUNT IN THE DESIGN PRESSURES? |
| |
| 7) PRODUCT APPROVALS: |
| 7A) FL 11727 PLEASE PROVIDE WHICH SUB-SYSTEM WILL |
| INSTALLED CIRCLE SYSTEM. |
| 7B) NOA 06-0417.09 PLEASE PROVIDE WHICH SUB-SYSTEM TO |
| BE INSTALLED. NOTE ONLY PAGE 15 IS A NON-INSULATED ROOF |
| THERE ARE THREE OPTIONS . OPTION# 1 HAS LOW PRESSURES |
| AND LIMITATION #9. OPTIONS 2& 3 LIMITATION# 7 WHICH |
| ALLOWS FOR ENHANCED FASTENING, PLEASE CICCLE WHICH |
| SYSTEM TO BE INSTALLED ANAD PROVIDE CALCULATIONS FOR |
| ZONES 2 & 3. |
| |
| 8) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| INFORMATION. |
| |
| INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. |
| A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| JAMES A. WITMER C.B.O. |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: (561)805-6715 |
| FAX:(561)805-6731 |
| E-MAIL: [email protected] |
| |
| CONSTRUCTION SERVICES HOME PAGE |
| HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |