2010-09-01 15:07:38FBC PLUMBING 2007
 REVIEW #1
 DENIED:
  
 1. SHEET A-2.2 FBC BUILDING 11-4.17.3 (2) THE
 ACCESSIBLE WATER CLOSET SHALL BE LOCATED IN THE CORNER,
 DIAGONAL TO THE DOOR. WOMENS ROOM #213
  
 2.SHEET A-2.2 11-4.17.3 2ND FLOOR MENS ROOM #212 ADA
 COMPARTMENT DOES NOT CONFORM WITH FIGURE 30E TOILET
 STALL NEW CONSTRUCTION.
  
 3. SHEET P 1.01 A - SHOWS ELEVATOR SUMP LINE CONNECTED
 TO THE SITE DRAINAGE. THE ELEVATOR SUMP SHALL NOT
 CONNECT TO THE SITE DRAINAGE DUE TO THE POSSIBILITY OF
 HYDRAULIC FLUID CONTAMINATION. ONE OPTION WOULD BE TO
 ROUTE THE PUMP LINE TO THE SANITARY THROUGH AN OIL
 INTERSEPTOR SIZED TO CONTAIN THE OIL
 FBC PLUMBING 701.4 SEWAGE TREATMENT. SEWAGE OR OTHER
 WASTE FROM A PLUMBING SYSTEM THAT IS DELETERIOUS TO
 SURFACE OR SUBSURFACE WATERS SHALL NOT BE DISCHARGED
 INTO THE GROUND OR INTO ANY WATERWAY UNLESS IT HAS
 FIRST BEEN RENDERED INNOCUOUS THROUGH SUBJECTION TO AN
 APPROVED FORM OF TREATMENT
 FBC BUILDING 3004.4 PLUMBING AND MECHANICAL SYSTEMS.
 PLUMBING AND MECHANICAL SYSTEMS SHALL NOT BE LOCATED IN
 AN ELEVATOR SHAFT.
 EXCEPTION: FLOOR DRAINS, SUMPS AND SUMP PUMPS SHALL BE
 PERMITTED AT THE BASE OF THE SHAFT PROVIDED THEY ARE
 INDIRECTLY CONNECTED TO THE PLUMBING SYSTEM.
 701.5 DAMAGE TO DRAINAGE SYSTEM OR PUBLIC SEWER. WASTES
 DETRIMENTAL TO THE PUBLIC SEWER SYSTEM OR TO THE
 FUNCTIONING OF THE SEWAGE-TREATMENT PLANT SHALL BE
 TREATED AND DISPOSED OF IN ACCORDANCE WITH SECTION 1003
 AS DIRECTED BY THE CODE OFFICIAL.
  
 4. SHEET P 1.01B PLUMBING 314.2.2 CONDENSATE DRAIN PIPE
 MATERIALS AND SIZES. WHERE THE DRAIN PIPES FROM MORE
 THAN ONE UNIT ARE MANIFOLDED TOGETHER FOR CONDENSATE
 DRAINAGE, THE PIPE OR TUBING SHALL BE SIZED IN
 ACCORDANCE WITH AN APPROVED METHOD. 3/4" PIPE APPEARS
 TO BE TOO SMALL FOR 7 TONS OF CONDENSATE.
 A 3.0 ROOF DETAIL
  
 5. SHEET P 1.02 B & P 2.01 THE CIRCUIT VENT FOR THE
 RESTROOMS REQUIRES A DRY VENT BETWEEN THE LAST TWO MOST
 UPSTREAM WC'S PLUMBING 911.2 VENT CONNECTION. THE
 CIRCUIT VENT CONNECTION SHALL BE LOCATED BETWEEN THE
 TWO MOST UPSTREAM FIXTURE DRAINS. THE VENT SHALL
 CONNECT TO THE HORIZONTAL BRANCH AND SHALL BE INSTALLED
 IN ACCORDANCE WITH SECTION 905. THE CIRCUIT VENT PIPE
 SHALL NOT RECEIVE THE DISCHARGE OF ANY SOIL OR WASTE.
  
 6. SHEET P 2.01 4" SANITARY PIPE IS REQUIRED UP TO THE
 LAST 4 WATER CLOSETS. TABLE 710.1(2)
  
 7. IRRIGATION PLAN - IF IRRIGATION IS CONNECTING TO THE
 DOMESTIC WATER SERVICE DOWNSTREAM OF THE RPZ BACKFLOW
 PREVENTOR, THE IRRIGATION LINE WILL REQUIRE A PRESSURE
 VACUUM BREAKER OR AN RPZ BACKFLOW PREVENTOR 608.16.5
  
 ****NOTE***** FROM SHEET P1.01A - A SEPERATE
 APPLICATION, DRAWINGS, AND GAS PERMIT WILL BE REQUIRED
 FOR THE RELOCATED GENERATOR.
  
 REVIEW BY LARRY WAGNER