2010-09-01 15:07:38 | FBC PLUMBING 2007 |
| REVIEW #1 |
| DENIED: |
| |
| 1. SHEET A-2.2 FBC BUILDING 11-4.17.3 (2) THE |
| ACCESSIBLE WATER CLOSET SHALL BE LOCATED IN THE CORNER, |
| DIAGONAL TO THE DOOR. WOMENS ROOM #213 |
| |
| 2.SHEET A-2.2 11-4.17.3 2ND FLOOR MENS ROOM #212 ADA |
| COMPARTMENT DOES NOT CONFORM WITH FIGURE 30E TOILET |
| STALL NEW CONSTRUCTION. |
| |
| 3. SHEET P 1.01 A - SHOWS ELEVATOR SUMP LINE CONNECTED |
| TO THE SITE DRAINAGE. THE ELEVATOR SUMP SHALL NOT |
| CONNECT TO THE SITE DRAINAGE DUE TO THE POSSIBILITY OF |
| HYDRAULIC FLUID CONTAMINATION. ONE OPTION WOULD BE TO |
| ROUTE THE PUMP LINE TO THE SANITARY THROUGH AN OIL |
| INTERSEPTOR SIZED TO CONTAIN THE OIL |
| FBC PLUMBING 701.4 SEWAGE TREATMENT. SEWAGE OR OTHER |
| WASTE FROM A PLUMBING SYSTEM THAT IS DELETERIOUS TO |
| SURFACE OR SUBSURFACE WATERS SHALL NOT BE DISCHARGED |
| INTO THE GROUND OR INTO ANY WATERWAY UNLESS IT HAS |
| FIRST BEEN RENDERED INNOCUOUS THROUGH SUBJECTION TO AN |
| APPROVED FORM OF TREATMENT |
| FBC BUILDING 3004.4 PLUMBING AND MECHANICAL SYSTEMS. |
| PLUMBING AND MECHANICAL SYSTEMS SHALL NOT BE LOCATED IN |
| AN ELEVATOR SHAFT. |
| EXCEPTION: FLOOR DRAINS, SUMPS AND SUMP PUMPS SHALL BE |
| PERMITTED AT THE BASE OF THE SHAFT PROVIDED THEY ARE |
| INDIRECTLY CONNECTED TO THE PLUMBING SYSTEM. |
| 701.5 DAMAGE TO DRAINAGE SYSTEM OR PUBLIC SEWER. WASTES |
| DETRIMENTAL TO THE PUBLIC SEWER SYSTEM OR TO THE |
| FUNCTIONING OF THE SEWAGE-TREATMENT PLANT SHALL BE |
| TREATED AND DISPOSED OF IN ACCORDANCE WITH SECTION 1003 |
| AS DIRECTED BY THE CODE OFFICIAL. |
| |
| 4. SHEET P 1.01B PLUMBING 314.2.2 CONDENSATE DRAIN PIPE |
| MATERIALS AND SIZES. WHERE THE DRAIN PIPES FROM MORE |
| THAN ONE UNIT ARE MANIFOLDED TOGETHER FOR CONDENSATE |
| DRAINAGE, THE PIPE OR TUBING SHALL BE SIZED IN |
| ACCORDANCE WITH AN APPROVED METHOD. 3/4" PIPE APPEARS |
| TO BE TOO SMALL FOR 7 TONS OF CONDENSATE. |
| A 3.0 ROOF DETAIL |
| |
| 5. SHEET P 1.02 B & P 2.01 THE CIRCUIT VENT FOR THE |
| RESTROOMS REQUIRES A DRY VENT BETWEEN THE LAST TWO MOST |
| UPSTREAM WC'S PLUMBING 911.2 VENT CONNECTION. THE |
| CIRCUIT VENT CONNECTION SHALL BE LOCATED BETWEEN THE |
| TWO MOST UPSTREAM FIXTURE DRAINS. THE VENT SHALL |
| CONNECT TO THE HORIZONTAL BRANCH AND SHALL BE INSTALLED |
| IN ACCORDANCE WITH SECTION 905. THE CIRCUIT VENT PIPE |
| SHALL NOT RECEIVE THE DISCHARGE OF ANY SOIL OR WASTE. |
| |
| 6. SHEET P 2.01 4" SANITARY PIPE IS REQUIRED UP TO THE |
| LAST 4 WATER CLOSETS. TABLE 710.1(2) |
| |
| 7. IRRIGATION PLAN - IF IRRIGATION IS CONNECTING TO THE |
| DOMESTIC WATER SERVICE DOWNSTREAM OF THE RPZ BACKFLOW |
| PREVENTOR, THE IRRIGATION LINE WILL REQUIRE A PRESSURE |
| VACUUM BREAKER OR AN RPZ BACKFLOW PREVENTOR 608.16.5 |
| |
| ****NOTE***** FROM SHEET P1.01A - A SEPERATE |
| APPLICATION, DRAWINGS, AND GAS PERMIT WILL BE REQUIRED |
| FOR THE RELOCATED GENERATOR. |
| |
| REVIEW BY LARRY WAGNER |
| CHIEF PLUMBING INSPECTOR |
| (561) 805-6692 |
| FAX (561) 653-2692 |