2010-09-16 17:03:54REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 REVIEW COMMENTS:
  
 1. PG M1.01A: OFFICE 107 SHOWS A TRANSFER DUCT FOR
 BALANCED RETURN. WHILE THE TRANSFER DUCT IS PROPERLY
 SIZED UNDER EXCEPTION 1 OF FBC-M 601.4, A ONE INCH
 UNDERCUT DOOR IS ALSO REQUIRED. THE LOCATION OF THE
 DOOR IN THIS ROOM DOES NOT COMMUNICATE WITH THE
 CENTRALIZED RETURN OF THE AHU SERVING THIS ROOM. SHOW
 HOW BALANCED RETURN IS TO BE ACHIEVED IN THIS AREA PER
 FBC-M 601.4.
  
 2. PG M1.01A: BREAK ROOM 111 SHOWS A TRANSFER DUCT FOR
 BALANCED RETURN. THE TRANSFER DUCT SHOWN IS NOT
 PROPERLY SIZED UNDER ECEPTION 1 OF FBC-M 601.4, WHICH
 REQUIRES THE TRANSFER DUCT TO BE MINIMUM 1.5 TIMES THE
 AREA OF THE SUPPLY DUCT. THE TWO 10 INCH SUPPLY DUCTS
 SERVING THIS ROOM HAVE A TOTAL OF 157 SQUARE INCHES. IN
 ORDER TO MEET THE EXCEPTION, THE TRANSFER DUCT MUST
 HAVE A MINIMUM CROSS-SECTIONAL AREA OF 235.5 SQUARE
 INCHES, PLUS A 1 INCH UNDERCUT AT THE DOOR. SHOW HOW
 BALANCED RETURN IS TO BE ACHIEVED IN THIS ROOM PER
 FBC-M 601.4.
  
 3. PG M1.01A AND P1.01A: CONDENSATE FOR AHU-5 IS SHOWN
 DISCHARGING ONTO A CONCRETE WALKWAY. THIS LOCATION WILL
 CAUSE A NUISANCE AND A HAZARDOUS CONDITION FOR
 PEDESTRIANS. CONDENSATE SHALL BE CONVEYED FROM THE
 DRAIN PAN OUTLET TO AN APPROVED PLACE OF DISPOSAL.
 CONDENSATE SHALL NOT DISCHARGE INTO A STREET, ALLEY OR
 OTHER AREAS SO AS TO CAUSE A NUISANCE PER FBC-M
 307.2.1.
  
 4. PG M1.02A: VESTIBULE 200 IS SERVING AS PART OF A
 FIRE RATED EXIT ACCESS CORRIDOR. THE 18X10 AND 16X10
 SUPPLY DUCT PENETRATIONS AT THIS LOCATION ARE REQUIRED
 TO BE PROTECTED BY FIRE AND SMOKE DAMPERS. ONLY FIRE
 DAMPERS ARE CURRENTLY SHOWN ON THE PLAN. SHOW
 COMPLIANCE WITH FBC-M 607.5.4.
  
 5. PG M1.02A: LOBBY 204 IS SERVING AS PART OF A FIRE
 RATED EXIT ACCESS CORRIDOR. THE 22X14 SUPPLY DUCT
 PENETRATION AT THIS LOCATION IS REQUIRED TO BE
 PROTECTED BY FIRE AND SMOKE DAMPERS. ONLY A FIRE DAMPER
 IS CURRENTLY SHOWN ON THE PLAN. SHOW COMPLIANCE WITH
 FBC-M 607.5.4.
  
 6. PG M1.02B: GALLERY IS SERVING AS PART OF A FIRE
 RATED EXIT ACCESS CORRIDOR. THE 18X14 AND 14X12 RETURN
 DUCT PENETRATIONS AT THIS LOCATION ARE REQUIRED TO BE
 PROTECTED BY FIRE AND SMOKE DAMPERS. ONLY FIRE DAMPERS
 ARE CURRENTLY SHOWN ON THE PLAN. SHOW COMPLIANCE WITH
 FBC-M 607.5.4.
  
 7. PG M1.02B: LOBBY 204 IS SERVING AS PART OF A FIRE
 RATED EXIT ACCESS CORRIDOR. THE 20X14 SUPPLY DUCT
 PENETRATION AT THIS LOCATION IS REQUIRED TO BE
 PROTECTED BY FIRE AND SMOKE DAMPERS. ONLY A FIRE DAMPER
 IS CURRENTLY SHOWN ON THE PLAN. SHOW COMPLIANCE WITH
 FBC-M 607.5.4.
  
 8. PG M1.02B: VESTIBULE 211 IS SERVING AS PART OF A
 FIRE RATED EXIT ACCESS CORRIDOR. THE 12X12 SUPPLY DUCT
 PENETRATION AT THIS LOCATION IS REQUIRED TO BE
 PROTECTED BY FIRE AND SMOKE DAMPERS. ONLY A FIRE DAMPER
 IS CURRENTLY SHOWN ON THE PLAN. SHOW COMPLIANCE WITH
 FBC-M 607.5.4.
  
 9. PG M1.02B: VESTIBULE 211 IS SERVING AS PART OF A
 FIRE RATED EXIT ACCESS CORRIDOR. THE TWO 8 INCH ROUND
 AND ONE 4 INCH ROUND SUPPLY DUCT PENETRATIONS AT THIS
 LOCATION ARE REQUIRED TO BE PROTECTED BY A FIRE DAMPER
 PER FBC-M 607.5.3 OR A THROUGH-PENETRATION FIRESTOP
 SYSTEM PER FBC-M 607.1.1. THEY ALSO REQUIRE SMOKE
 DAMPERS PER FBC-M 607.5.4.
  
 10. PG M1.102B: THE 4 INCH ROUND EXHAUST DUCT SERVING
 CUSTODIAL 214 SHALL BE PROTECTED WITH A FIRE DAMPER PER
 FBC-M 607.5.3 OR A THROUGH-PENETRATION FIRESTOP SYSTEM
 PER FBC-M 607.1.1.
  
 11. PG ME1.01: ELEVATIONS SHOWN ON PLAN INDICATE THAT
 IT WOULD BE NECESSARY TO CLIMB A HEIGHT OF AT LEAST 4
 FEET (OVER A PARAPET) TO GET FROM THE LOWER ROOF WHERE
 THE ROOF ACCESS HATCH IS LOCATED TO THE MAIN ROOF WHERE
 THE MECHANICAL APPLIANCES ARE LOCATED. SUCH ACCESS
 SHALL NOT REQUIRE CLIMBING OVER OBSTRUCTIONS GREATER
 THAN 30 INCHES HIGH PER FBC-M 306.5. PROVIDE A
 PERMANENT MEANS OF ACCESS OVER THIS OBSTRUCTION.
  
 12. PG ME1.01: CU-6 AND EF-2 ARE BOTH SHOWN LESS THAN
 10 FEET FROM THE ROOF EDGE. THE ROOF HATCH OPENING IS
 ALSO LESS THAN 10 FEET FROM THE ROOF EDGE. GUARDS SHALL
 BE PROVIDED AT THESE LOCATIONS IN ACCORDANCE WITH FBC-M
 304.10.
  
 13. PG M2.02: PROVIDE WIND RESISTANT INSTALLATION
 DETAIL FOR ROOF MOUNTED EXHAUST FAN(S) PER FBC-M
 301.12.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: