2010-09-14 18:26:50 | *****REVIEW COMMENTS - FIRE***** |
| |
| WATER PLAN 6 OF 9: SHIFT FIRE HYDRANT, BACKFLOW |
| PREVENTER, AND FDC 30-FEET TO THE SOUTH TO AVOID |
| DAMAGED FIRE PROTECTION EQUIPMENT IN A WALL COLLAPSE |
| EVENT SINCE 40-FEET OF CLEARANCE CANNOT BE MAINTAINED |
| BETWEEN THE BUILDING AND EQUIPMENT. POSSIBLE SHIFT MAY |
| AFFECT LANDSCAPE PLANS. |
| |
| WATER PLAN 7 OF 9: ADDRESS SHOULD READ "2100 NORTH |
| FLORIDA MANGO ROAD." |
| |
| WATER DETAILS 8 OF 9: BACKFLOW PREVENTER SHALL BE UL |
| LISTED FOR FIRE PROTECTION SYSTEMS. PROVIDE TAMPER |
| SWITCHES ON GATES VALVES. CHAIN/LOCK GATE VALVES IN |
| OPEN POSITION. PROVIDE CHECK VALVE AND LOCKABLE KNOX |
| CAPS ON FIRE DEPARTMENT CONNECTION. |
| |
| SHEET D-1.0: DEMOLITION SHALL COMPLY WITH NFPA 241. |
| |
| SHEET LS-1: |
| - FLORIDA FIRE PREVENTION CODE SHOULD BE THE 2007 |
| EDITION. |
| - DOOR SWINGS BLOCK MORE THAN 50% OF EXISTING CORRIDORS |
| #116 AND #124 PER 7.2.1.4.4 OF NFPA 101. |
| - NORTH STAIR INTERMEDIATE LANDING DECREASES IN WIDTH |
| NEAR LOWER LANDING. |
| - PROVIDE TACTILE SIGNAGE AT FIRST FLOOR EXITS. |
| |
| SHEET LS-2: IF BOTH DOORS OF ROOMS #219 AND #220 ARE |
| OPEN AT THE SAME TIME, MORE THAN 50% OF THE GALLERY |
| CORRIDOR IS OBSTRUCTED. |
| |
| SHEET A-2: |
| - FESTIVAL SEATING IN ASSEMBLY OCCUPANCIES WITH |
| OCCUPANT LOADS GREATER THAN 250 PERSONS REQUIRE AN |
| APPROVED LIFE SAFETY EVALUATION PER 12.2.5.4 OF NFPA |
| 101. |
| - MOVEABLE CHAIRS ARE REQUIRED TO BE SECURED TOGETHER |
| IN GROUPS OF 3-7 PER 12.7.9.1.1 OR IF CHAIRS ARE NOT |
| SECURED TOGETHER, AN AREA OF 15 SQ.FT. PER SEAT IS |
| REQUIRED PER 12.7.9.2.2 OF NFPA 101. |
| - ASSEMBLY OCCUPANCIES GREATER THAN 250 OCCUPANTS |
| REQUIRE CROWD MANAGERS PER 12.7.6 AND FIRE DRILLS PER |
| 12.7.7 OF NFPA 101. |
| - THE OCCUPANT LOAD OF THE ASSEMBLY SPACE SHALL BE |
| POSTED NEAR THE MAIN ENTRANCE/EXIT OF THE ROOM PER |
| 12.7.9.3 OF NFPA 101. |
| |
| SHEET E1.01A: MAIN ENTRANCE FEATURES A "REQUEST TO |
| EXIT" BUTTON. ALL THE REQUIREMENTS OF 7.2.1.6.2 (NFPA |
| 101) TO BE MET FOR ACCESS-CONTROLLED EGRESS DOORS. |
| |
| SHEET FA1.01A: |
| - THE FIRE ALARM CONTROL PANEL (ELECTRICAL #136) IS |
| SHOWN IN A DIFFERENT LOCATION FROM ELECTRICAL SHEET |
| E1.02B (ROOM #216). COORDINATE LOCATION. |
| - DUCT SMOKE DETECTORS SHALL INITIATE A GENERAL FIRE |
| ALARM CONDITION. |
| - SMOKE DETECTOR AT TOP OF ELEVATOR SHAFT NOT PERMITTED |
| UNLESS AUTOMATIC SPRINKLER IS PROTECTING TOP OF |
| ELEVATOR SHAFT. |
| |
| GENERAL: |
| - SIGNED/SEALED FIRE PROTECTION ENGINEERING DOCUMENTS |
| PER FAC 61G15-32.001 ARE REQUIRED FOR A BUILDING |
| PERMIT. |
| - PROVIDE KNOX KEY SWITCH TO ALLOW FIRE DEPARTMENT |
| ACCESS THROUGH ELECTRIC GATE |
| |
| MIKE CARSILLO, BATTALION CHIEF |
| & WESLEY JOLIN |
| WPB FIRE PLAN REVIEW |
| 561-805-6730 |
| |