2010-09-14 18:26:50*****REVIEW COMMENTS - FIRE*****
  
 WATER PLAN 6 OF 9: SHIFT FIRE HYDRANT, BACKFLOW
 PREVENTER, AND FDC 30-FEET TO THE SOUTH TO AVOID
 DAMAGED FIRE PROTECTION EQUIPMENT IN A WALL COLLAPSE
 EVENT SINCE 40-FEET OF CLEARANCE CANNOT BE MAINTAINED
 BETWEEN THE BUILDING AND EQUIPMENT. POSSIBLE SHIFT MAY
 AFFECT LANDSCAPE PLANS.
  
 WATER PLAN 7 OF 9: ADDRESS SHOULD READ "2100 NORTH
 FLORIDA MANGO ROAD."
  
 WATER DETAILS 8 OF 9: BACKFLOW PREVENTER SHALL BE UL
 LISTED FOR FIRE PROTECTION SYSTEMS. PROVIDE TAMPER
 SWITCHES ON GATES VALVES. CHAIN/LOCK GATE VALVES IN
 OPEN POSITION. PROVIDE CHECK VALVE AND LOCKABLE KNOX
 CAPS ON FIRE DEPARTMENT CONNECTION.
  
 SHEET D-1.0: DEMOLITION SHALL COMPLY WITH NFPA 241.
  
 SHEET LS-1:
 - FLORIDA FIRE PREVENTION CODE SHOULD BE THE 2007
 EDITION.
 - DOOR SWINGS BLOCK MORE THAN 50% OF EXISTING CORRIDORS
 #116 AND #124 PER 7.2.1.4.4 OF NFPA 101.
 - NORTH STAIR INTERMEDIATE LANDING DECREASES IN WIDTH
 NEAR LOWER LANDING.
 - PROVIDE TACTILE SIGNAGE AT FIRST FLOOR EXITS.
  
 SHEET LS-2: IF BOTH DOORS OF ROOMS #219 AND #220 ARE
 OPEN AT THE SAME TIME, MORE THAN 50% OF THE GALLERY
 CORRIDOR IS OBSTRUCTED.
  
 SHEET A-2:
 - FESTIVAL SEATING IN ASSEMBLY OCCUPANCIES WITH
 OCCUPANT LOADS GREATER THAN 250 PERSONS REQUIRE AN
 APPROVED LIFE SAFETY EVALUATION PER 12.2.5.4 OF NFPA
 101.
 - MOVEABLE CHAIRS ARE REQUIRED TO BE SECURED TOGETHER
 IN GROUPS OF 3-7 PER 12.7.9.1.1 OR IF CHAIRS ARE NOT
 SECURED TOGETHER, AN AREA OF 15 SQ.FT. PER SEAT IS
 REQUIRED PER 12.7.9.2.2 OF NFPA 101.
 - ASSEMBLY OCCUPANCIES GREATER THAN 250 OCCUPANTS
 REQUIRE CROWD MANAGERS PER 12.7.6 AND FIRE DRILLS PER
 12.7.7 OF NFPA 101.
 - THE OCCUPANT LOAD OF THE ASSEMBLY SPACE SHALL BE
 POSTED NEAR THE MAIN ENTRANCE/EXIT OF THE ROOM PER
 12.7.9.3 OF NFPA 101.
  
 SHEET E1.01A: MAIN ENTRANCE FEATURES A "REQUEST TO
 EXIT" BUTTON. ALL THE REQUIREMENTS OF 7.2.1.6.2 (NFPA
 101) TO BE MET FOR ACCESS-CONTROLLED EGRESS DOORS.
  
 SHEET FA1.01A:
 - THE FIRE ALARM CONTROL PANEL (ELECTRICAL #136) IS
 SHOWN IN A DIFFERENT LOCATION FROM ELECTRICAL SHEET
 E1.02B (ROOM #216). COORDINATE LOCATION.
 - DUCT SMOKE DETECTORS SHALL INITIATE A GENERAL FIRE
 ALARM CONDITION.
 - SMOKE DETECTOR AT TOP OF ELEVATOR SHAFT NOT PERMITTED
 UNLESS AUTOMATIC SPRINKLER IS PROTECTING TOP OF
 ELEVATOR SHAFT.
  
 GENERAL:
 - SIGNED/SEALED FIRE PROTECTION ENGINEERING DOCUMENTS
 PER FAC 61G15-32.001 ARE REQUIRED FOR A BUILDING
 PERMIT.
 - PROVIDE KNOX KEY SWITCH TO ALLOW FIRE DEPARTMENT
 ACCESS THROUGH ELECTRIC GATE
  
 MIKE CARSILLO, BATTALION CHIEF
 & WESLEY JOLIN
 WPB FIRE PLAN REVIEW