2010-08-26 13:37:22BUILDING PLAN REVIEW
 PERMIT: 10080396
 ADD: 2100 N FLORIDA MANGO
 CONT: TO BE DETERMINED
 CONTACT: PBA JOINT VENTURE INC
 TEL: (561)689-3745
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 AUGUST 26/2010
 1ST REVIEW
 ACTION: DENIED
  
 1) NOTE PAARKING, LANDSCAPE, GENERATORS AND COVERED
 PARKING STRUCTURE REQUIRE SEPERATE PERMITS, REVIEWS,
 FEES AND APPLICATIONS.
  
 2) A/C CONDENSOR PADS AND GENERATOR PADS ARE LOCATED
 WITHIN A A-9 FLOOD ZONE REQUIRING A MINIMUM BASE FLOOD
 ELEVATION OF 13'-6", TO BE INCLUDED ON THE FINAL
 SURVEY.
 THE FIRST FLOOR ELEVATION TO BE AT A MINIMUM OF 13'-6"
 AND WILL REQUIRE SURVEYS WITH ELEVATION OF THE FIRST
 FLOOR LEVEL AT TIME OF FIRST FLOOR SLAB POUR AND AT
 FINAL BEFORE A C.C. OR C.O CAN BE ISSUED.
  
 3) SHEET LS1 THE SOUTH EXIT STAIR #102 IS WITHIN A 1
 HOUR ENCLOSURE THAT EXITS INTO A UNRATED LOBBY# 100 AND
 CONTAINING A ELEVATOR. AS DISCUSSED WITH B O DOUG WISE
 THIS CONDITION DOES MEET THE EXCEPTION 1020.1 EXCEPTION
 # 8. WE CONTACTED GS&P OFFICE MIKE ROSSIN ABOUT THE
 ISSUE OF THE LOBBY STILL REQUIRING A ONE HOUR FIRE
 RATING BECAUSE OF IT BEING THE EXIT CORRIDOR FOR THE
 LOUGE #112. THE LOUGE HAS AN ASSEMBLY OCCUPANT LOAD OF
 GREATER THAN 30 WHICH REQUIRES A 1 HR FIRE RATING PER
 TABLE 1017.1.
 WHEN WE SPOKE WITH MR. ROSSIN HE SUGESTED THEY WILL
 MAKE ONE OF THE TWO WINDOWS INTO THE 2ND EXIT FOR THIS
 SPACE ALLOWING THE LOBBY TO REMAIN UNRATED, PLANS WILL
 NEED TO BE UPDATED TO REFLECT THIS CHANGE. PLEASE BE
 AWARE OF A ONE FOOT ELEVATION CHANGE FROM THE NEW EXIT
 LANDING CREATED BY THIS DOORWAY AND SIDEWALK AND THE
 ELECTRICAL ROOM 136 LOCATED AT ELEVATION 14.91 NGVD.
 SHEET A1.1.
  
 4) PLEASE NOTE 11-4.1.3(8)(II) ACCESSIBLE ENTRANCES
 MUST BE PROVIDED IN A NUMBER AT LEAST EQUIVALENT TO THE
 NUMBER OF EXITS REQUIRED BY THE APPLICABLE BUILDING /
 FIRE CODES.
  
 5) ANOTHER AREA OF CONCERN IS THE FRONT ENTRY SHEET
 A1.1. PLEASE REVIEW THTE CROSS SLOPE, THE AREA JUST IN
 FRONT OF THE EGRESS DOORS INDICATES A ELEVATION OF
 15.91 NGVD AND A SECOND ELEVATION OF THE SIDEWALK
 12'-0" AWAY ADJACENT TO THE CURB A ELEVATION OF 15'-41"
 OR A GRADE CHANGE OF 6 INCHES IN 12'-0". 11-4.3.7 CROSS
 SLOPE ONLY ALLOWS A CROSS SLOPE 0F 1:50.
  
 6) SHEET A.20 PORTABLE STAGE DOE NOT INDICATE VERTICAL
 ACCESSIBLITY,11-4.1.6(1)(K)(III).
  
 7) SHEET A2.1 & A2.2 DORRWAYS LEADING TO EXTERIOR DECKS
 INDICATE A CUT SECTION 3/A6.1 WHEN YOU GO THERE IT
 REFERES YOU TO DETAIL 8/A3.0 A WALL SECTION , PLEASE
 PROVIDE A SECTION THROUGH AT TTHE DOOR FOR ACCESSIBILTY
 REQUIREMENTS. PLEASE ALSO INCLUDE WHICH OF THE PRODUCT
 APPROVALS THIS WILL BE. 11-4.13.8.
  
 8) SHEET A-3.0 THE ROOF PLAN AND DETAILS INDICATE TWO
 WALKABLE DECKS WITH ROOF DRAINS & NO OVER FLOWS THE
 DETAILS INDICATE THE ROOF DRAIN IS AT ELEVATION 17'-8"
 AS WELL AS THE PARAPET WALL WHICH WOULD ALLOW THE WATER
 TO OVERFLOW DOWN THE SIDE OF THE WALL. PLEASE SEE FBC-B
 1503.6. GUTTERS WITH DOWNSPOUTS ARE REQUIRED ON ALL
 BUILDINGS WITH EAVES OF LESS THAN 6 INCHES (152 MM)
 HORIZONTAL PROJECTION EXCEPT FOR GABLE END RAKES OR ON
 A ROOF ABOVE ANOTHER ROOF.
  
 9) SHEET A-6.1 NOTE UPPER RIGHT HAND CORNER OF PLAN
 INDICATES "LIGHT -WEIGHT CONCRETE ON METAL DECK W/
 AVERAGE R-30 VALUE. THE TERM AVERAGE CAN NOT BE USED.
 THERE ARE THREE INFORMAL INTERPRETATIONS THROUGH BOAF (
 BUILDING OFFICIALS ASSOCIATION OF FLORIDA THAT ARE
 RECOGNIZED THROUGH THE DEPARTMENT OF COMMUNITY AFFAIRS
 THAT IS EXPLICITE THE MINIMUM R-VALUE IS TO OCCUR AT
 THE ROOF DRAINS NOT A AVERAGE.
 SECTION 13-404.1ABCD.1 REPORT 3746
 SECTION 13-404 REPORT 3731
 SECTION 13-404.1.A REPORT 5438
  
 10) SHEET A-6.0 & A-6.1 BOTH HAVE WALL SECTIONS THAT
 INDICATE THE USE OF WIRE LATH OVER GRACE ICE/WATER
 MEMBRANE, THE CODE INDICATES A CHANGE IN 1404.2.1
 REQUIRING A SEPERATE BOND BREAK BETWEEN THE WATER
 RESISTIVE BARRIER AND THE CEMENT PLASTER (STUCCO).
 PLEASE REVIEW THE 3 OPTIONS.
  
 11) SHEET A-6.4 PLEASE PROVIDE COMPLIANCE WITH 11-4.4.2
 WHEN THERE IS LESS THAN 80 INCHES ( VERTICAL NOMINAL
 DIMENSION) HEAD ROOM, A BARRIER TO WARN BLIND OR
 VISUALLY - IMPAIRED PERSONS.
  
 12) THIS SAME SHEET A-6.4 INDICATES A HANDRAIL AT THE
 BOTTOM OF THE STAIR THE HANDRAIL THAT IS NOT ATTACHED
 TO THE WALL, THE HORIZONTAL EXTENSION WILL NEED TO WRAP
 BACK ONTO ITSELF AS PER 11-4.8.5(6) ENDS OF HANDRAILS
 SHALL BE EITHER ROUNDED OR RETURNED SMOOTHLY TO FLOOR,
 WALL, OR POST. ALSO SEE 11-4.4.1 PROTRUDING OBJECTS.
  
 13) IN NONE OF THE STAIR DETAILS IN A-6.2, A-6.3 &
 A-6.4 INDICATE ROOF DRAINS WITHIN THE STAIRWELL, THE
 PLUMBING PLANS INDICATE A 3" RAIN WATER PIPE. THE
 ARCHITECTURAL SHEETS INDICATE A LAY IN CEILING SYSTEM.
 FBC-B 1020.1.2 PENETRATIONS INTO THE STAIRWELL CAN ONLY
 WHAT IS REQUIRED FOR THE STAIRWELL. PLEASE PROVIDE
 DOCUMENTATION THAT THE LAY IN CEILING WILL HAVE A 1
 HOUR FIRE RATING, PROVIDE MANUFACTURERS SPEC ON THE
 CEILING TILE AND GRID SYSTEM FOR RATING.
  
 14) PRODUCT APPROVAL: YKK "#%" ALUMINUM OUTSWING
 ENTRANCE DOOR NOA 09-0518.09 PLEASE CIRCLE TYPE OF
 GLASS TO BE INSTALLED, NOTE DESIGN PRESSURES TO BE
 DIVIDED BY 1.33.
  
 15) PRODUCT APPROVAL SIPLAST NOA 09-0901.14 PLEASE
 PROVIDE WHICH SUB-SYSTEM IS TO BE INSTALLED ON THE
 ROOF, PLEASE ALSO BE AWARRE OF LIMITATIONS WITHIN EACH
 SUB-SYSTEM.
 LIMITATION #7 INDICATES ENHANCED FASTENING CAN OCCUR
 USING RAS 117 BY DESIGN PROFESSIONAL.
 LIMITATION #9 THE MAXIMUM DESIGN PRESSURES INDICATED
 ARE FOR ALL ROOF ZONES, NO ENHANCED FASTENING ALLOWED.
  
 16) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES
 DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER
 NOTICE.
  
 OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM
 - 5:00 PM.
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  