Plan Review Notes
Plan Review Notes For Permit 10080370
Permit Number 10080370
Review Stop B
Sequence Number 1
Notes
Date Text
2010-08-12 12:29:06RESIDENTIAL (R3) RE-ROOF, BUILDING REVIEW CHECKLIST.
 2007 FBC WITH 2009 REVISIONS.
  
 1- SPECIFY WHICH APPROVED ASSEMBLY IS GOING TO BE
 INSTALLED TO VERIFY COMPLIANCE WITH THE DESIGN
 PRESSURES OF SEC. R301.
  
 2- PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS AS
 REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE OF NOA
 06-0410.06 SUBMITTED.
 (NOTE: APPROVED ASSEMBLIES THAT ARE LIMITATED BY
 GENERAL LIMITATION #9 CAN'T BE USED IN THIS AREA
 BECAUSE THEY DON'T MEET THE DESIGN PRESSURES).
  
 ***NOTE: DESIGN PROFESSIONAL DOING THE RAS 117
 CALCULATIONS TO TAKE INTO CONSIDERATION THAT ACCORDING
 TO THE 2009 REVISIONS, THIS BUILDING IS LOCATED ON
 EXPOSURE "C".
  
 3- ACCORDING TO MIAMI-DADE WEBSITE THE FILE FOR NOA
 06-0410.06 IS CLOSED. NEED TO PROVIDE CURRENT NOA.
  
 ***NOTE: PROVIDE TWO COPIES. ONLY ONE WAS SUBMITTED.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712