Plan Review Notes For Permit 10080317 |
Permit Number |
10080317 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2010-08-12 11:48:27 | RESIDENTIAL (R3) RE-ROOF, BUILDING REVIEW CHECKLIST. | | 2007 FBC WITH 2009 REVISIONS. | | | | 1- FLAT ROOF: A) PROVIDE SIGNED AND SEALED RAS 117 | | CALCULATIONS AS REQUIRED BY GENERAL LIMITATION #7 ON | | LAST PAGE OF NOA 09-0224.01 SUBMITTED. | | | | B) DESIGN PROFESSIONAL DONG THE RAS 117 CALCULATIONS TO | | TAKE INTO CONSIDERATION THAT ACCORDING TO THE 2009 | | REVISIONS, THIS BUILDING IS LOCATED ON EXPOSURE "C". | | | | 2- ACCORDING TO MIAMI-DADE WEBSITE THE FILE FOR THE | | ROOF TILE NOA 08-0204.07 SUBMITTED IS CLOSED. NEED TO | | PROVIDE CURRENT NOA. | | | | 3- PROVIDE PRODUCT APPROVAL (2 COPIES) FOR POLYFOAM TO | | BE USED AS REQUIRED BY DCA RULE 9B-72. | | | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561)805-6712 |
|