Plan Review Notes For Permit 10080235 |
Permit Number |
10080235 |
|
Review Stop |
FIRE |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2010-08-31 10:34:39 | *****REVIEW COMMENTS - FIRE***** | | | | 1) FOR SPRINKLER SYSTEM TO THE WEST (SUPPLIED BY OTHER | | RISER), ADD CROSS MAIN TO TREE SYSTEM NEAR COLUMN LINES | | L/N TO CONVERT TREE SYSTEM TO A GRID SYSTEM OR PROVIDE | | HYDRAULIC CALCULATION SUPPORTING THAT THE EXISTING | | LAYOUT IS SUFFICIENT FOR THE HAZARD BEING PROTECTED. | | | | 2) IN ADDITION TO THE SCOPE OF WORK NOTE #2, SHOW ALL | | ADDITIONAL SPRINKLERS REQUIRED IN THE TENANT SPACES TO | | REDUCE THE AREA OF COVERAGE PER SPRINKLER TO 130 SQUARE | | FEET OR LESS. THE SXL METHOD MUST BE USED TO DETERMINE | | THE AREA OF COVERAGE PER SPRINKLER. APPROXIMATELY 45 | | TENANT SPACES APPEAR TO HAVE SPRINKLERS COVERING MORE | | THAN 130 SQ.FT. | | | | MIKE CARSILLO, BATTALION CHIEF | | & WESLEY JOLIN | | WPB FIRE PLAN REVIEW | | 561-805-6730 |
|