2010-08-31 10:34:39*****REVIEW COMMENTS - FIRE*****
  
 1) FOR SPRINKLER SYSTEM TO THE WEST (SUPPLIED BY OTHER
 RISER), ADD CROSS MAIN TO TREE SYSTEM NEAR COLUMN LINES
 L/N TO CONVERT TREE SYSTEM TO A GRID SYSTEM OR PROVIDE
 HYDRAULIC CALCULATION SUPPORTING THAT THE EXISTING
 LAYOUT IS SUFFICIENT FOR THE HAZARD BEING PROTECTED.
  
 2) IN ADDITION TO THE SCOPE OF WORK NOTE #2, SHOW ALL
 ADDITIONAL SPRINKLERS REQUIRED IN THE TENANT SPACES TO
 REDUCE THE AREA OF COVERAGE PER SPRINKLER TO 130 SQUARE
 FEET OR LESS. THE SXL METHOD MUST BE USED TO DETERMINE
 THE AREA OF COVERAGE PER SPRINKLER. APPROXIMATELY 45
 TENANT SPACES APPEAR TO HAVE SPRINKLERS COVERING MORE
 THAN 130 SQ.FT.
  
 MIKE CARSILLO, BATTALION CHIEF
 & WESLEY JOLIN
 WPB FIRE PLAN REVIEW