2010-08-24 12:28:502139 PALM BEACH LAKES BOULEVARD
 PERMIT NUMBER 10080159
 "PROVIDE 175KW DIESEL GENERATOR SET AND ATS"
  
  
 1. THE GENERATOR AND FUEL TANK SHALL BE INSTALLED IN
 ACCORDANCE WITH NFPA 30 AND NFPA 37. NO NOTES ON THE
 PLANS SEEM TO REFLECT THESE CODE REQUIREMENTS.
  
 2. NO WARNING SIGNS OR APPROPRIATE LABELING OBSERVED
 FOR THE STORAGE AND USE OF THE DIESEL FUEL. NO NFPA 704
 DIAMOND ILLUSTRATED FOR THE HAZARDS OF THE DIESEL FUEL.
  
 3. PLEASE ILLUSTRATE THE REQUIRED SETBACKS REQUIRED FOR
 THE DIESEL FUEL STORAGE TANK FROM OTHER PROPERTIES AND
 IMPORTANT BUILDINGS.
  
 4. PLEASE DESCRIBE WHAT EQUIPMENT THE GENERATOR WILL
 PROVIDE POWER FOR. DOES THE GENERATOR PROVIDE POWER TO
 NORMAL OR EMERGENCY SYSTEMS AND EQUIPMENT.
  
 DENIED
  
  
 MIKE CARSILLO, BATTALION CHIEF