Plan Review Notes For Permit 10080159 |
Permit Number |
10080159 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2010-08-24 12:28:50 | 2139 PALM BEACH LAKES BOULEVARD | | PERMIT NUMBER 10080159 | | "PROVIDE 175KW DIESEL GENERATOR SET AND ATS" | | | | | | 1. THE GENERATOR AND FUEL TANK SHALL BE INSTALLED IN | | ACCORDANCE WITH NFPA 30 AND NFPA 37. NO NOTES ON THE | | PLANS SEEM TO REFLECT THESE CODE REQUIREMENTS. | | | | 2. NO WARNING SIGNS OR APPROPRIATE LABELING OBSERVED | | FOR THE STORAGE AND USE OF THE DIESEL FUEL. NO NFPA 704 | | DIAMOND ILLUSTRATED FOR THE HAZARDS OF THE DIESEL FUEL. | | | | 3. PLEASE ILLUSTRATE THE REQUIRED SETBACKS REQUIRED FOR | | THE DIESEL FUEL STORAGE TANK FROM OTHER PROPERTIES AND | | IMPORTANT BUILDINGS. | | | | 4. PLEASE DESCRIBE WHAT EQUIPMENT THE GENERATOR WILL | | PROVIDE POWER FOR. DOES THE GENERATOR PROVIDE POWER TO | | NORMAL OR EMERGENCY SYSTEMS AND EQUIPMENT. | | | | DENIED | | | | | | MIKE CARSILLO, BATTALION CHIEF | | BUREAU OF FIRE PREVENTION |
|