2010-08-18 08:38:32BUILDING PLAN REVIEW
 PERMIT: 10080159
 ADD:2139 PALM BEACH LAKES BLVD
 CONT: KNIGHT ELECTRIC CO
 TEL: (561)689-3500
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) EMERGENCY AND STANDBY POWER SYSTEMS SHALL BE
 INSTALLED IN ACCORDANCE WITH THE NFPA 70, NATIONAL
 ELECTRICAL CODE, NFPA 110 AND NFPA 111.
  
 7.4.1 ROTATING ENERGY CONVERTERS SHALL BE INSTALLED ON
 SOLID FOUNDATIONS TO PROHIBIT SAGGING OF FUEL, EXHAUST,
 OR LUBRICATING-OIL PIPING AND DAMAGE TO PARTS RESULTING
 IN LEAKAGE AT JOINTS.
  
 7.4.1.1 SUCH FOUNDATIONS OR STRUCTURAL BASES SHALL
 RAISE THE ENGINE AT LEAST 150 MM (6 IN.) ABOVE THE
 FLOOR OR GRADE LEVEL AND BE OF SUFFICIENT ELEVATION TO
 FACILITATE LUBRICATING-OIL DRAINAGE AND
 EASE OF MAINTENANCE.
  
 7.4.2 FOUNDATIONS SHALL BE OF THE SIZE (MASS) AND TYPE
 RECOMMENDED BY THE ENERGY CONVERTER MANUFACTURER.
  
 7.4.3 WHERE REQUIRED TO PREVENT TRANSMISSION OF
 VIBRATION DURING OPERATION, THE FOUNDATION SHALL BE
 ISOLATED FROM THE SURROUNDING FLOOR OR OTHER
 FOUNDATIONS, OR BOTH, IN ACCORDANCE WITH THE
 MANUFACTURER'S RECOMMENDATIONS AND ACCEPTED STRUCTURAL
 ENGINEERING PRACTICES.
  
 7.4.4 THE EPS SHALL BE MOUNTED ON A FABRICATED METAL
 SKID BASE OF THE TYPE THAT SHALL RESIST DAMAGE DURING
 SHIPPING AND HANDLING. AFTER INSTALLATION, THE BASE
 SHALL MAINTAIN ALIGNMENT OF THE UNIT DURING OPERATION.
 PLANS DO NOT PROVIDE INFORMATION FOR SECONDARY
 CONTAINMENT. NFPA 110: 7.9.12 LISTED GENERATOR SUBBASE
 SECONDARY CONTAINMENT FUEL TANKS OF 2498 L (660 GAL)
 CAPACITY AND BELOW SHALL BE PERMITTED TO BE INSTALLED
 OUTDOORS OR INDOORS WITHOUT DIKING OR REMOTE
 IMPOUNDING.
  
 2) MISSING WIND DESIGN CRITERIA:
 1609.6.2 WIND DESIGN PROCEDURES
 1) THE BASIC WIND SPEED, V, SHALL BE DETERMINED IN
 ACCORDANCE WITH SECTION 1609.3. THE WIND SHALL BE
 ASSUMED TO COME FROM ANY HORIZONTAL DIRECTION.
  
 2) AN IMPORTANCE FACTOR, IW, SHALL BE DETERMINED IN
 ACCORDANCE WITH SECTION1609.5.
  
 3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4.
  
 4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.6.2.1(4)
  
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  