2010-08-18 08:38:32 | BUILDING PLAN REVIEW |
| PERMIT: 10080159 |
| ADD:2139 PALM BEACH LAKES BLVD |
| CONT: KNIGHT ELECTRIC CO |
| TEL: (561)689-3500 |
| |
| FL BLD CODE= 2007 FLORIDA BUILDING CODE |
| W/ 2009 FBC SUPPLEMENTS |
| * WEST PALM BEACH AMENDMENTS |
| |
| 1ST REVIEW |
| ACTION: DENIED |
| |
| 1) EMERGENCY AND STANDBY POWER SYSTEMS SHALL BE |
| INSTALLED IN ACCORDANCE WITH THE NFPA 70, NATIONAL |
| ELECTRICAL CODE, NFPA 110 AND NFPA 111. |
| |
| 7.4.1 ROTATING ENERGY CONVERTERS SHALL BE INSTALLED ON |
| SOLID FOUNDATIONS TO PROHIBIT SAGGING OF FUEL, EXHAUST, |
| OR LUBRICATING-OIL PIPING AND DAMAGE TO PARTS RESULTING |
| IN LEAKAGE AT JOINTS. |
| |
| 7.4.1.1 SUCH FOUNDATIONS OR STRUCTURAL BASES SHALL |
| RAISE THE ENGINE AT LEAST 150 MM (6 IN.) ABOVE THE |
| FLOOR OR GRADE LEVEL AND BE OF SUFFICIENT ELEVATION TO |
| FACILITATE LUBRICATING-OIL DRAINAGE AND |
| EASE OF MAINTENANCE. |
| |
| 7.4.2 FOUNDATIONS SHALL BE OF THE SIZE (MASS) AND TYPE |
| RECOMMENDED BY THE ENERGY CONVERTER MANUFACTURER. |
| |
| 7.4.3 WHERE REQUIRED TO PREVENT TRANSMISSION OF |
| VIBRATION DURING OPERATION, THE FOUNDATION SHALL BE |
| ISOLATED FROM THE SURROUNDING FLOOR OR OTHER |
| FOUNDATIONS, OR BOTH, IN ACCORDANCE WITH THE |
| MANUFACTURER'S RECOMMENDATIONS AND ACCEPTED STRUCTURAL |
| ENGINEERING PRACTICES. |
| |
| 7.4.4 THE EPS SHALL BE MOUNTED ON A FABRICATED METAL |
| SKID BASE OF THE TYPE THAT SHALL RESIST DAMAGE DURING |
| SHIPPING AND HANDLING. AFTER INSTALLATION, THE BASE |
| SHALL MAINTAIN ALIGNMENT OF THE UNIT DURING OPERATION. |
| PLANS DO NOT PROVIDE INFORMATION FOR SECONDARY |
| CONTAINMENT. NFPA 110: 7.9.12 LISTED GENERATOR SUBBASE |
| SECONDARY CONTAINMENT FUEL TANKS OF 2498 L (660 GAL) |
| CAPACITY AND BELOW SHALL BE PERMITTED TO BE INSTALLED |
| OUTDOORS OR INDOORS WITHOUT DIKING OR REMOTE |
| IMPOUNDING. |
| |
| 2) MISSING WIND DESIGN CRITERIA: |
| 1609.6.2 WIND DESIGN PROCEDURES |
| 1) THE BASIC WIND SPEED, V, SHALL BE DETERMINED IN |
| ACCORDANCE WITH SECTION 1609.3. THE WIND SHALL BE |
| ASSUMED TO COME FROM ANY HORIZONTAL DIRECTION. |
| |
| 2) AN IMPORTANCE FACTOR, IW, SHALL BE DETERMINED IN |
| ACCORDANCE WITH SECTION1609.5. |
| |
| 3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN |
| ACCORDANCE WITH 1609.4. |
| |
| 4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, * |
| SHALL BE DETERMINED FROM TABLE 1609.6.2.1(4) |
| |
| |
| JIM WITMER C. B. O. |
| COMMERCIAL COMBINATION PLAN REVIEW |
| |
| TEL: (561)805-6715 |
| FAX: (561)805-6731 |
| E-MAIL: [email protected] |
| |
| PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE |
| CUSTOMER SERVICE SURVEY AT: |
| WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES |
| |
| CONSTRUCTION SERVICES HOME PAGE |
| HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| |
| PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| |
| MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| |