Plan Review Notes
Plan Review Notes For Permit 10080154
Permit Number 10080154
Review Stop B
Sequence Number 1
Notes
Date Text
2010-09-13 12:56:49****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. APPLICATION STATES THIS MASTER IS FOR FLAGLER MODEL
 DCA #FMP 3526I, BUT THE PLANS SUBMITTED ARE FOR
 FMT3626D. DATURA MODEL WAS REVISED TO DCA FMP3526I.
 PLEASE CORRELATE.
  
 2. THE MATING DETAIL PACKAGE PROVIDES MANY DETAILS
 WHICH ARE NOT RELEVANT TO THIS JOB. PLEASE PROVIDE
 DETAILS APPLICABLE TO THIS PROJECT, AND REMOVE DETAILS
 WHICH DO NOT APPLY TO THIS PROJECT (FOR INSTANCE,
 FOUNDATION DETAILS WHICH ARE IN CONFLICT WITH THE
 FOUNDATION PLANS SUBMITTED DESIGNED BY ROBERT C.
 SCROGGINS, PE).
  
  
 MASTER WILL BE ISSUED WITH FOLLOWING PROVISO:
  
  
 ***FLAGLER MODEL*** DCA?????? ***
 PROVISO - SITE PERMITS WILL REQUIRE:
  
 1. SOILS INVESTIGATION REPORT, 2000 PSF BEARING MINIMUM
 2. CURRENT SURVEY
 3. SITE PLAN SHOWING PROPOSED LOCATION (ZONING REVIEW
 REQUIRED)
 4 SEPARATE PERMITS FOR ELECTRIC, PLUMBING, MECHANICAL,
 IMPACT PROTECTION (IF SITE INSTALLED), ROOF (IF SITE
 INSTALLED)
 5. LOAD CALCS & SITE SPECIFIC ENERGY CALCS (IF
 REQUIRED) TO BE SUBMITTED WITH MECHANICAL PERMIT
 6. IMPACT FEE ASSESSMENT - PLANS ARE TO BE STAMPED AND
 THE RECEIPT ATTACHED TO APPLICATION
  