Plan Review Notes
Plan Review Notes For Permit 10080108
Permit Number 10080108
Review Stop M
Sequence Number 1
Notes
Date Text
2010-08-30 16:33:342007 FBC W/2009 REVISIONS
  
 DENIED BY MECHANICAL
  
 1) THE NOTARIZED SIGNATURE OF THE MECHANICAL CONTRACTOR
 ON THE PERMIT APPLICATION IS REQUIRED.
  
 2) ACCORDING TO ITEM NUMBER 53 IN THE SCOPE OF WORK,
 THE AIR-HANDLER IS TO BE RELOCATED. THIS WILL REQUIRE
 THE EXISTING DUCTWORK TO BE RE-CONFIGURED, THEREFORE,
 THIS IS NOT CONSIDERED AN EXACT CHANGE-OUT. SUBMIT TWO
 SETS OF HVAC DRAWINGS. PROVIDE FLOOR PLANS SHOWING THE
 LOCATION OF THE UNITS, SUPPLY AND RETURN DUCT LOCATIONS
 AND SIZES, GRILL SIZES, CFMS AT EACH DROP, TRANSFER
 DUCTS OR GRILLS. SPECIFY THE SIZE AND MODEL NUMBERS OF
 THE HVAC EQUIPMENT ON THE PLANS.
  
 3) SUBMIT TWO COPIES OF MANUAL J CALCULATIONS OR OTHER
 APPROVED HEATING AND COOLING EQUIPMENT SIZING
 CALCULATIONS.
  
 4) INDICATE THE LOCATION OF THE GAS DRYER (ITEM 21).
 SHOW COMPLIANCE WITH FBCR M1701.1 FOR COMBUSTION AIR.
  
 5) THE DRAWINGS CAN BE DONE BY FLORIDA LICENSED DESIGN
 PROFESSIONALS OR A FLORIDA LICENSED HVAC CONTRACTOR. IF
 THEY ARE FROM A HVAC CONTRACTOR, THE NAME AND LICENSE
 NUMBER OF THE CONTRACTOR IS REQUIRED ON THE PLANS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]