Plan Review Notes
Plan Review Notes For Permit 10080108
Permit Number 10080108
Review Stop B
Sequence Number 1
Notes
Date Text
2010-08-31 08:03:292007 FBC W/2009 REVISIONS
  
 DENIED BY BUILDING
  
 1) THE WINDOW SCHEDULE THAT WAS SUBMITTED INDICATES
 OPENINGS THAT ARE 108", 112" AND 204" WIDE. THESE ARE
 WIDER THAN THE WIDTH OF THE WINDOWS LISTED IN THE
 PRODUCT APPROVAL. ARE THESE MULTIPLE WINDOWS THAT ARE
 MULLED TOGETHER? PLEASE CLARIFY.
  
 2) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE
 STRUCTURAL MULLIONS.
  
 3) SHOW COMPLIANCE WITH FBCR 313.2.1 AND 313.4 FOR
 REQUIRED SMOKE ALARMS AND CARBON MONOXIDE PROTECTION.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]