Plan Review Notes
Plan Review Notes For Permit 10080100
Permit Number 10080100
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2010-08-13 15:34:23*****REVIEW COMMENTS - FIRE*****
  
 1) PLANS AND HYDRAULIC CALCULATIONS NOT SIGNED AND
 SEALED BY A PROFESSIONAL ENGINEER. SPRINKLER DESIGN IS
 LESS THAN 50 SPRINKLERS, BUT PLANS WERE SUBMITTED FOR A
 SPRINKLER PERMIT; HOWEVER, SHEET 2 OF 3 (NOTE #4)
 STATES, "FIRE EXTINGUISHING CONTRACTOR SHALL ENGINEER,
 DESIGN..ALL COMPONENTS." PLEASE EXPLAIN.
  
 2) PROVIDE JOB ADDRESS IN TITLEBLOCK.
  
 3) PROVIDE LOCKABLE KNOX CAPS ON FIRE DEPARTMENT
 CONNECTION.
  
 4) WHAT IS THE CHURN PRESSURE OF THE 147 PSI RATED FIRE
 PUMP? WHAT IS THE STATIC PRESSURE OF THE WATER STORAGE
 TANK? SYSTEM PRESSURES MAY BE EXCEEDING 175 PSI.
  
 5) HYDRAULIC PLACARD INFORMATION: CALCULATED AREA IS
 NOT 3000 SQ.FT.
  
 6) PROVIDE NOTE ON THE DRAWING INDICATING IF EXPOSED
 STRUCTURE IS OBSTRUCTED CONSTRUCTION OR UNOBSTRUCTED
 CONSTRUCTION, AND INDICATE MIN/MAX SPRINKLER DISTANCE
 ALLOWED BELOW ROOF DECK.
  
 7) SPRINKLER INFORMATION (TEMPERATURE, K-FACTOR ETC.)
 FROM HYDRAULIC CALCULATIONS NOT SHOWN ON THE PLANS.
  
 MIKE CARSILLO, BATTALION CHIEF
 & WESLEY JOLIN
 WPB FIRE PLAN REVIEW
 561-805-6730