Plan Review Notes For Permit 10080004 |
Permit Number |
10080004 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2010-08-04 15:28:42 | 124 NORTH OLIVE AVENUE | | PERMIT NUMBER 10080004 | | INTERIOR RENOVATION | | | | | | 1. PLEASE DECLARE PROPOSED OCCUPANCY TYPE. | | | | 2. PLANS INDICATE INSTALLATION OF EXIT SIGNS AND | | EMERGENCY LIGHTS BUT THE DRAWINGS DO NOT SPECIFY ANY | | LOCATIONS FOR THESE DEVICES. | | | | 3. NO WALL INSTALLATION DETAIL TO REPAIR THE TWO HOUR | | FIRE WALL. | | | | 4. NO INTERIOR FINISH INFORMATION PROVIDED FOR WALLS | | AND CEILINGS. | | | | 5. IT IS BELIEVED THAT PREVIOUSLY THE SPACE WAS USED AS | | A NIGHTCLUB. PLEASE BE ADVISED THAT CERTAIN OCCUPANCY | | TYPES THAT INCLUDE NIGHTCLUBS WITH OCCUPANT LOADS OF | | 100 OR MORE PERSONS ARE NOW REQUIRED TO BE FIRE | | SPRINKLER PROTECTED. | | | | | | DENIED | | | | | | MIKE CARSILLO, BATTALION CHIEF | | BUREAU OF FIRE PREVENTION | | | | |
|