Plan Review Notes
Plan Review Notes For Permit 10070802
Permit Number 10070802
Review Stop B
Sequence Number 3
Notes
Date Text
2010-10-08 14:59:362007 FBC W/2009 REVISIONS
  
 DENIED BY BUILDING
  
 1) PER FLORIDA STATUES 471 AND F.A.C. 61G15-23.002, THE
 SLAB AND ANCHORING FOR WINDLOAD FROM THE ENGINEER,
 RONALD WILSON, IS REQUIRED TO HAVE THE ORIGINAL
 SIGNATURE AND SEAL OF THE ENGINEER AND THE DATE THAT HE
 SIGNED AND SEALED THE DRAWINGS.
  
 2) THE EXPOSURE CATEGORY IS INCORRECT ON THE PLANS. IT
 IS LOCATED IN EXPOSURE CATEGORY C. PLEASE CORRECT.
  
 THIS IS THE THIRD TIME THIS PERMIT HAS BEEN DENIED FOR
 THESE SAME TWO COMMENTS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved