2010-08-18 14:22:36NEED TO SUPPLY A LOAD CALCULATION PER 702.5 (B)
  
 IS METER AT SAME LOCATION AS PANEL "A"
  
 IF MAINS ARE NOT GROPUPED PER 230.71 A SIGN PER 702.8
 SHALL BE INSTALLED.
  