Plan Review Notes
Plan Review Notes For Permit 10070802
Permit Number 10070802
Review Stop B
Sequence Number 1
Notes
Date Text
2010-08-18 14:41:542007 FBC W/2009 REVISIONS
  
 DENIED BY BUILDING
  
 1) PER FLORIDA STATUES 471 AND F.A.C. 61G15-23.002, THE
 SLAB AND ANCHORING FOR WINDLOAD FROM THE ENGINEER,
 RONALD WILSON, IS REQUIRED TO HAVE THE ORIGINAL
 SIGNATURE AND SEAL OF THE ENGINEER AND THE DATE THAT HE
 SIGNED AND SEALED THE DRAWINGS.
  
 2) THE EXPOSURE CATEGORY IS INCORRECT ON THE PLANS. IT
 IS LOCATED IN EXPOSURE CATEGORY C. PLEASE CORRECT.
  
 3) PER NFPA 37, THE GENERATOR MUST BE LOCATED A MINIMUM
 OF 5 FEET FROM OPENINGS IN WALLS AND 5 FEET FROM
 STRUCTURES HAVING COMBUSTIBLE WALLS. GENERATORS SHALL
 BE INSTALLED IN ACCORDANCE WITH MANUFACTURER'S
 INSTALLATION INSTRUCTIONS AND NFPA 37.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]