2010-08-24 17:11:20REVIEW #: 1ST
 ACTION: IN PROGRESS
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 REVIEW COMMENTS:
  
 1. PG M0.01: CODE COMPLIANCE NOTES INDICATE "MIAMI-DADE
 COUNTY AMENDMENTS." SUCH AMENDMENTS ARE NOT APPLICABLE
 WITHIN THIS JURISDICTION. SEE ABOVE FOR APPLICABLE
 CODES.
  
 2. PG M2.01: FLOOR PLAN AND KEY NOTE #2 CALL FOR A
 12X12 OUTDOOR LOUVER. NO PRODUCT APPROVAL FOR SUCH
 LOUVER HAS BEEN PROVIDED. SUBMIT PRODUCT APPROVAL
 APPROVED IN WRITING BY THE DESIGN PROFESSIONAL IN
 ACCORDANCE WITH FBC-B 106.3.3 AND FAC RULE 9N-3
 (FORMERLY 9B-72).
  
 3. PG M2.02: KEY NOTE #1 CALLS FOR FIRE DAMPER AT DUCT
 PENETRATION OF SHAFT. DUCT PENETRATIONS OF SHAFT
 ENCLOSURES SHALL BE PROTECTED WITH FIRE AND SMOKE
 DAMPERS IN ACCORDANCE WITH FBC-M 607.5.5.
  
 4. PG M2.02: KEY NOTE #12 CALLS FOR A FIRE DAMPER AT
 THE TRANSFER OPENING OF THE FILE STORAGE ROOM. THIS
 TRANSFER OPENING SHALL ALSO BE PROTECTED WITH A SMOKE
 DAMPER IN ACCORDANCE WITH FBC-B 508.2.2.1 AND FBC-B
 710.7.
  
 5. PG M2.02: SUPPLY REGISTER IN OFFICE 231 IS MISSING
 CFM AND GRILL DESIGNATION. THIS INFORMATION IS REQUIRED
 TO DETERMINE DUCT SIZE AND FACILITATE PROPER BALANCING
 OF AIRFLOWS. PROVIDE MISSING INFORMATION IN ACCORDANCE
 WITH FBC-M 603.1.
  
 6. PG M2.03: KEY NOTE #6 CALLS FOR FIRE DAMPER AT NEW
 DUCT PENETRATION OF SHAFT. DUCT PENETRATIONS OF SHAFT
 ENCLOSURES SHALL BE PROTECTED WITH FIRE AND SMOKE
 DAMPERS IN ACCORDANCE WITH FBC-M 607.5.5.
  
 7. PG M2.03: FLOOR PLAN SHOWS TWO DUCTS FROM
 UNIDENTIFIED RTU GOING THROUGH THE 3RD FLOOR ASSEMBLY
 DOWN TO THE SECOND FLOOR. THESE PENETRATIONS SHALL BE
 PROTECTED AT THE FLOOR ASSEMBLY IN ACCORDANCE WITH
 FBC-M 607.6.
  
 8. PG M2.03: FLOOR PLAN SHOWS TWO DUCTS FROM RTU-3-1
 GOING THROUGH THE 3RD FLOOR ASSEMBLY DOWN TO THE SECOND
 FLOOR. THESE PENETRATIONS SHALL BE PROTECTED AT THE
 FLOOR ASSEMBLY IN ACCORDANCE WITH FBC-M 607.6.
  
 9. PG M2.03: KEY NOTE #8 CALLS FOR A FIRE DAMPER AT THE
 TRANSFER OPENING OF STORAGE ROOM 344. THIS TRANSFER
 OPENING SHALL ALSO BE PROTECTED WITH A SMOKE DAMPER IN
 ACCORDANCE WITH FBC-B 508.2.2.1 AND FBC-B 710.7.
  
 10. PG M2.03: KEY NOTE #7 CALLS FOR A FIRE DAMPER AT
 THE TRANSFER OPENING OF FILE ROOM 312. THIS TRANSFER
 OPENING SHALL ALSO BE PROTECTED WITH A SMOKE DAMPER IN
 ACCORDANCE WITH FBC-B 508.2.2.1 AND FBC-B 710.7.
  
 11. PG M2.03: KEY NOTE #8 CALLS FOR A FIRE DAMPER AT
 THE TRANSFER OPENING OF STORAGE ROOM 355. THIS TRANSFER
 OPENING SHALL ALSO BE PROTECTED WITH A SMOKE DAMPER IN
 ACCORDANCE WITH FBC-B 508.2.2.1 AND FBC-B 710.7.
  
 12. 2ND AND 3RD FLOORS: IF RATED FILE AND STORAGE ROOMS
 ON 2ND AND 3RD FLOORS ARE CONSIDERED TO BE SEPARATE
 FIRE AREAS (SEE DEFINITION OF FIRE AREA IN FBC-B
 SECTION 702), THESE ROOMS MAY NOT SHARE A COMMON PLENUM
 WITH THE ADJACENT SPACES IN ACCORDANCE WITH FBC-M 602.1
  
 13. PG M5.01: DETAIL #3 SHOWS 12 GA. WIRE HANGERS FOR
 FLEXIBLE DUCT SUPPORT. FLEXIBLE DUCT SUPPORTS SHALL BE
 MIN. 1.5 INCHES WIDE PER FBC-M 63.5.6.6.
  
 14.PG M5.01: DETAIL #3 NOTE LIMITS FLEXIBLE DUCT LENGTH
 TO 3 FEET. FLOOR PLANS SHOW FLEXIBLE DUCT EXCEEDING
 THREE FEET IN LENGTH IN MULTIPLE LOCATIONS. COORDINATE
 FLOOR PLANS AND DETAILS IN ACCORDANCE WITH FBC-B
 106.1.1 AND 106.4.
  
 15. PG M5.02: DETAIL #3 SHOWS NEW CONDENSER STAND ON
 ROOF WHILE PAGE M2.04 CALLS FOR THE EXISTING, SITE
 FABRICATED STAND TO BE USED. PROVIDE ENGINEERING DETAIL
 SHOWING HOW THE NEW CONDENSERS ARE TO BE ATTACHED TO
 THE EXISTING STAND FOR WIND RESISTANCE IN ACCORDANCE
 WITH FBC-M 301.12.
  
 16. PG M5.03: DETAIL #6, IF GOOSENECK IS UTILIZED, THE
 OPEN END SHALL BE PROTECTED WITH CORROSION-RESISTANT
 SCREEN IN ACCORDANCE WITH FBC-M 401.5.
  
 17. PG M5.03: DETAIL #1, SHOW LOCATION OF DUCT SMOKE
 DETECTORS ON FLOOR PLAN PER FBC-M 606.2.1 AND FBC-B
 106.1.1.
  
 18. PG M5.03: DETAIL #2, PROVIDE MAXIMUM HANGER SPACING
 PER FBC-M 305.1.
  
 19. PG M5.04: DETAIL #2, THIS DETAIL DOES NOT
 CORRESPOND WITH STRUCTURAL DETAIL ON PAGE S3.00. PLEASE
 COORDINATE PLANS TO SHOW COMPLIANCE WITH FBC-M 301.12.
  
  