2010-09-07 11:18:56 | 1920 WEKIVA WAY |
| PERMIT NUMBER 10070788 |
| CONSTRUCTION WORK FOR A POTION OF THE FIRST FLOOR, |
| COMPLETE SECOND AND THIRD FLOORS |
| |
| |
| 1. CONSTRUCTION, DEMOLITION, AND RENOVATION ACTIVITIES |
| TO COMPLY WITH NFPA 241. |
| |
| 2. DEBRIS SHALL BE REMOVED DAILY FROM THE SITE OR AS |
| OFTEN AS NECESSARY. |
| |
| 3. ADEQUATE FIRE LANES AND SUITABLE FIRE AND |
| PARAMEDICAL ACCESS SHALL BE PROVIDED DURING |
| CONSTRUCTION ACTIVITIES. |
| |
| 4. SEPARATE PLANS AND PERMITS REQUIRED FOR FIRE ALARM |
| AND FIRE SPRINKLER SYSTEM REMODELING. |
| |
| 5. WRONG EDITIONS OF FIRE CODES LISTED ON SHEET LS.O. |
| THE CORRECT CODES ARE THE FLORIDA FIRE PREVENTION CODE |
| 2007 EDITION WHICH IS COMPRISED ON NFPA 1, 2006 EDITION |
| AND THE LIFE SAFETY CODE, 2006 EDITION. ALSO NFPA 88A |
| AND NFPA 20 ARE NOT APPLICABLE TO THIS PROJECT. |
| |
| 6. ON SHEET AO.30, CARD READERS ARE MENTIONED IN ITEM # |
| 1. ELECTRONIC LOCKING DEVICES SHALL NOT INTERFERE WITH |
| ANY EXITING. ANY SPECIAL LOCKING DEVICES ON EXIT DOORS |
| SHALL COMPLY WITH CHAPTER 7 OF THE FLORIDA FIRE |
| PREVENTION CODE, 2007 EDITION. ARE THESE DOORS FAIL |
| SAFE OR FAIL SECURE. |
| |
| 7. ON SHEET A0.30 CARD READER DEVICES NOT PERMITTED IN |
| THE RATED STAIR ENCLOSURE PER SECTION 7.1.3.2 (6) OF |
| NFPA 101, THE LIFE SAFETY CODE 2006 EDITION. |
| |
| 8. DOOR # 110 A AND 116A IS SHOWN AS A 45 MINUTE RATING |
| IN A 2 HOUR RATED WALL. NO DOOR CLOSER PROVIDED. CARD |
| READER LOCKING DEVICES DO NOT CONFORM TO THE |
| REQUIREMENTS OF 7.2.1.5 THROUGH 7.2.1.6.2 OF NFPA 101. |
| |
| 9. ALL RATED FIRE DOORS ARE TO BE EQUIPPED WITH |
| APPROVED SELF-CLOSING DEVICES. |
| |
| 10. ON SHEET LS2.01 TWO MEANS OF EGRESS THROUGH THE |
| MOVABLE PARTITION WALLS IN BREAK ROOM # 112 PER SECTION |
| 7.2.1.12 OF NFPA 101. |
| |
| 11. ON SHEET LS2.01 TWO VESTIBULE / CORRIDOR DOORS ARE |
| SHOWN AS 1 HOUR FIRE RATED IN TWO-HOUR FIRE RATED |
| WALLS. |
| |
| 12. ON SHEET LS2.01 DOOR SWING FROM FILE 118 BLOCKING |
| EGRESS FROM STORAGE 119. |
| |
| 13. TACTILE SIGNAGE REQUIRED AT ALL EXIT DOOR |
| LOCATIONS. |
| |
| 14. ON SHEET LS2.03 THE ORIENTATION OF THE EXIT SIGNS |
| NEAR STAIR # 1 AND STAIR # 2 MAY BE DIFFICULT TO BE |
| SEEN FROM CORRIDOR # 301. |
| |
| 15. ON SHEET A2.02 CARD READERS ON DOOR 225A, 213A, |
| 247A, AND 250A DO NOT CONFORM TO THE LOCKING |
| REQUIREMENTS OF SECTION 7.2.1.5 OF NFPA 101. |
| |
| 16. ON SHEET E2.01 NO EXIT SIGN PROVIDED IN VESTIBULE # |
| 116. |
| |
| 17. ON SHEET E2.01 PLEASE PROVIDE EXIT DISCHARGE |
| LIGHTING LEADING TO A PUBLIC WAY PER SECTION 7.8.1.1 OF |
| NFPA 101. |
| |
| 18. ON SHEET E2.03 EXIT SIGN AT COLUMN INTERSECTION 2/B |
| ONLY DIRECTS OCCUPANTS TO THE EAST EXIT (AWAY FROM THE |
| CLOSEST EXIT). |
| |
| 19. ON SHEET E3.02 PLEASE PROVIDE VISUAL NOTIFICATION |
| APPLIANCE IN BREAK ROOM # 209. |
| |
| 20. ON PAGE A2.01 REFERENCE IS MADE TO THE INSTALLATION |
| OF A GENERATOR. SEPARATE PLANS AND PERMITS REQUIRED FOR |
| THE INSTALLATION OF THE GENERATOR AND ALL APPURTENANT |
| EQUIPMENT. |
| |
| 21. ON PAGE LS2.02 IT APPEARS THAT AN ADDITIONAL EXIT |
| SIGN IS NEEDED IN CORRIDOR (245). PLEASE EXAMINE BLIND |
| CORNERS. |
| |
| 22. NOTE 15 ON PAGE E5.02 IS INCORRECT. THE ACTIVATION |
| OF DUCT SMOKE DETECTORS SHALL CAUSE A GENERAL ALARM AND |
| NOT A SUPERVISORY SIGNAL. |