Date Text
2010-09-07 11:18:561920 WEKIVA WAY
 PERMIT NUMBER 10070788
 CONSTRUCTION WORK FOR A POTION OF THE FIRST FLOOR,
 COMPLETE SECOND AND THIRD FLOORS
  
  
 1. CONSTRUCTION, DEMOLITION, AND RENOVATION ACTIVITIES
 TO COMPLY WITH NFPA 241.
  
 2. DEBRIS SHALL BE REMOVED DAILY FROM THE SITE OR AS
 OFTEN AS NECESSARY.
  
 3. ADEQUATE FIRE LANES AND SUITABLE FIRE AND
 PARAMEDICAL ACCESS SHALL BE PROVIDED DURING
 CONSTRUCTION ACTIVITIES.
  
 4. SEPARATE PLANS AND PERMITS REQUIRED FOR FIRE ALARM
 AND FIRE SPRINKLER SYSTEM REMODELING.
  
 5. WRONG EDITIONS OF FIRE CODES LISTED ON SHEET LS.O.
 THE CORRECT CODES ARE THE FLORIDA FIRE PREVENTION CODE
 2007 EDITION WHICH IS COMPRISED ON NFPA 1, 2006 EDITION
 AND THE LIFE SAFETY CODE, 2006 EDITION. ALSO NFPA 88A
 AND NFPA 20 ARE NOT APPLICABLE TO THIS PROJECT.
  
 6. ON SHEET AO.30, CARD READERS ARE MENTIONED IN ITEM #
 1. ELECTRONIC LOCKING DEVICES SHALL NOT INTERFERE WITH
 ANY EXITING. ANY SPECIAL LOCKING DEVICES ON EXIT DOORS
 SHALL COMPLY WITH CHAPTER 7 OF THE FLORIDA FIRE
 PREVENTION CODE, 2007 EDITION. ARE THESE DOORS FAIL
 SAFE OR FAIL SECURE.
  
 7. ON SHEET A0.30 CARD READER DEVICES NOT PERMITTED IN
 THE RATED STAIR ENCLOSURE PER SECTION 7.1.3.2 (6) OF
 NFPA 101, THE LIFE SAFETY CODE 2006 EDITION.
  
 8. DOOR # 110 A AND 116A IS SHOWN AS A 45 MINUTE RATING
 IN A 2 HOUR RATED WALL. NO DOOR CLOSER PROVIDED. CARD
 READER LOCKING DEVICES DO NOT CONFORM TO THE
 REQUIREMENTS OF 7.2.1.5 THROUGH 7.2.1.6.2 OF NFPA 101.
  
 9. ALL RATED FIRE DOORS ARE TO BE EQUIPPED WITH
 APPROVED SELF-CLOSING DEVICES.
  
 10. ON SHEET LS2.01 TWO MEANS OF EGRESS THROUGH THE
 MOVABLE PARTITION WALLS IN BREAK ROOM # 112 PER SECTION
 7.2.1.12 OF NFPA 101.
  
 11. ON SHEET LS2.01 TWO VESTIBULE / CORRIDOR DOORS ARE
 SHOWN AS 1 HOUR FIRE RATED IN TWO-HOUR FIRE RATED
 WALLS.
  
 12. ON SHEET LS2.01 DOOR SWING FROM FILE 118 BLOCKING
 EGRESS FROM STORAGE 119.
  
 13. TACTILE SIGNAGE REQUIRED AT ALL EXIT DOOR
 LOCATIONS.
  
 14. ON SHEET LS2.03 THE ORIENTATION OF THE EXIT SIGNS
 NEAR STAIR # 1 AND STAIR # 2 MAY BE DIFFICULT TO BE
 SEEN FROM CORRIDOR # 301.
  
 15. ON SHEET A2.02 CARD READERS ON DOOR 225A, 213A,
 247A, AND 250A DO NOT CONFORM TO THE LOCKING
 REQUIREMENTS OF SECTION 7.2.1.5 OF NFPA 101.
  
 16. ON SHEET E2.01 NO EXIT SIGN PROVIDED IN VESTIBULE #
 116.
  
 17. ON SHEET E2.01 PLEASE PROVIDE EXIT DISCHARGE
 LIGHTING LEADING TO A PUBLIC WAY PER SECTION 7.8.1.1 OF
 NFPA 101.
  
 18. ON SHEET E2.03 EXIT SIGN AT COLUMN INTERSECTION 2/B
 ONLY DIRECTS OCCUPANTS TO THE EAST EXIT (AWAY FROM THE
 CLOSEST EXIT).
  
 19. ON SHEET E3.02 PLEASE PROVIDE VISUAL NOTIFICATION
 APPLIANCE IN BREAK ROOM # 209.
  
 20. ON PAGE A2.01 REFERENCE IS MADE TO THE INSTALLATION
 OF A GENERATOR. SEPARATE PLANS AND PERMITS REQUIRED FOR
 THE INSTALLATION OF THE GENERATOR AND ALL APPURTENANT
 EQUIPMENT.
  
 21. ON PAGE LS2.02 IT APPEARS THAT AN ADDITIONAL EXIT
 SIGN IS NEEDED IN CORRIDOR (245). PLEASE EXAMINE BLIND
 CORNERS.
  
 22. NOTE 15 ON PAGE E5.02 IS INCORRECT. THE ACTIVATION
 OF DUCT SMOKE DETECTORS SHALL CAUSE A GENERAL ALARM AND
 NOT A SUPERVISORY SIGNAL.