2010-09-22 19:18:34ELECTRICAL PLAN REVIEW COMMENTS - 10070788
 9/21/2010
 DOUG WISE, 805-6650, [email protected]
  
 1. SHEET E0.02 NOTES 20 AND 21 - PLEASE NOTE THE DESIGN
 MUST SATISFY THE FOLLOWING CRITERIA:
 13-413.ABC.1.1 FEEDERS AND CUSTOMER-OWNED SERVICE
 CONDUCTORS. FEEDER AND CUSTOMER-OWNED SERVICE
 CONDUCTORS SHALL BE SIZED FOR A MAXIMUM VOLTAGE DROP OF
 2 PERCENT AT DESIGN LOAD.
 13-413.ABC.1.2 BRANCH CIRCUITS. BRANCH CIRCUIT
 CONDUCTORS SHALL BE SIZED FOR A MAXIMUM VOLTAGE DROP OF
 3 PERCENT AT DESIGN LOAD.
 THIS DESIGN RESPONSIBILITY CANNOT BE TRANSFERRED TO THE
 ELECTRICAL CONTRACTOR. THE DESIGN PROFESSIONAL SHALL
 PROVIDE A TABLE WITH WIRE SIZES AND MAXIMUM WIRE
 LENGTHS OR OTHER MEANS TO ENSURE THE DESIGN ITSELF
 SATISFIES THIS CRITERIA.
  
 2. SHEET E0.02 NOTE 39 - MULTIWIRE BRANCH CIRCUITS MAY
 BE PERMITTED IF THEY SHARE A COMMON BREAKER OR HANDLE
 TIE, FURTHER ALL CONDUCTORS SHALL BE "TIED" THAT SERVE
 SUCH A MULTI-WIRE BRANCH CIRCUIT WITHIN THE PANELBOARD
 PURSUANT TO SECTION 210.4(D).
  
 3. SHEET E2.01 - PROVIDE A PLAN WHICH DEMONSTRATES THE
 REQUIRED OPENING(S) AND RELATED ELECTRICAL FIXTURES FOR
 THE BREAK ROOM
  
 4. SHEET E2.01 - PROVIDE POWER DENSITY TABULATIONS OR
 OTHER DATA TO DEMONSTRATE COMPLIANCE WITH
 FBC13-415.ABC.5
  
 5. SHEET E2.02 - PROVIDE POWER DENSITY TABULATIONS OR
 OTHER DATA TO DEMONSTRATE COMPLIANCE WITH
 FBC13-415.ABC.5
  
 6. SHEET E2.03 - PROVIDE POWER DENSITY TABULATIONS OR
 OTHER DATA TO DEMONSTRATE COMPLIANCE WITH
 FBC13-415.ABC.5
  
 7. SHEET E3.01 - VENDING EQUIPMENT OR RECEPTACLES MUST
 COMPLY WITH NEC 422.51
  
 8. SHEET E3.02 - SERVER ROOM MUST COMPLY WITH NEC 645.4
 AND 645.10 INCLUDING FIRE RATED SEPARATION,
 ELECTRICALLY CONTROLLED DAMPERS, AND DISCONNECTING
 MEANS FOR SEPARATE HVAC AND EQUIPMENT. PLEASE
 DEMONSTRATE COMPLIANCE AND COORDINATE DESIGN WITH OTHER
 RELATED PLAN PAGES.
  
 9. SHEET E3.02 - DRINKING FOUNTAIN CIRCUIT MUST BE GFI
 PROTECTED PURSUANT TO NEC 422.52. PLEASE COORDINATE
 WITH E7.03 PANEL SCHEDULE 2TB
  
 10. SHEET E3.02 - ONLY TWO "SMALL APPLIANCE" BRANCH
 CIRCUITS ARE SHOWN FEEDING THE BREAK ROOM COUNTER. IF A
 MICROWAVE OVEN AND A COFFEE MACHINE ARE DESIRED,
 ADDITIONAL DEDICATED CIRCUITS MAY BE REQUIRED TO
 ADEQUATELY SERVICE THIS LOCATION. PLEASE VERIFY THESE
 REQUIREMENTS WITH THE CUSTOMER.
  
 11. SHEET E3.03 - PLEASE REVIEW RECEPTACLE LOCATIONS IN
 THE BREAK ROOM. IT APPEARS INSUFFICIENT RECEPTACLES
 HAVE BEEN SHOWN AND ARE BEING SHOWN IN THE WRONG
 LOCATIONS. PLEASE REVIEW CUSTOMER NEEDS IN
 CONSIDERATION OF COMMENT #10 ABOVE. ENSURE ADEQUATE
 CIRCUITS ARE PROVIDED TO SATISFY CUSTOMER'S NEEDS.
  
 12. SHEET E5.01 - RISER INDICATES TENANT SPACE IS TO BE
 SERVED BY SEPARATE 15 ELECTRICAL METERS AND SERVICES.
 PLEASE VERIFY THAT THIS IS THE ACTUAL DESIGN INTENT.
 SHEET A2.01, NOTE 2 INDICATES THE CONTRACTOR IS TO
 PERMIT AND INSTALL AN EMERGENCY GENERATOR. ALTHOUGH AN
 EMERGENCY GENERATOR WILL BE PERMITTED SEPARATELY,
 ADEQUATE PROVISION IN THE ELECTRICAL SERVICE DESIGN IS
 NECESSARY TO FACITILATE THIS INTENT. PLEASE RECONCILE
 THESE INTENTIONS OR CLARIFY.
  
 13. SHEET E5.01 - IT APPEARS THAT PANEL 2SR IS BEING
 FED FROM METER 2ST. PLEASE CLARIFY OR RECONCILE.
  
 14. SHEET E5.02 - PLEASE NOTE THAT SEPARATE
 APPLICATION, REVIEW AND PERMITTING IS REQUIRED FOR FIRE
 ALARM AND ACCESS CONTROL SYSTEMS PROPOSED WITHIN THIS
 STRUCTURE. A SEPARATE "SUB-PERMIT" SHALL BE REQUIRED
 FOR ALL CATV / TELECOM / LOW VOLTAGE SYSTEMS NOT
 PERFORMED DIRECTLY BY THE "PRIME" ELECTRICAL
 CONTRACTOR.
  
 15. SHEET E6.01 - PLEASE NOTE THAT PURSUANT TO NEC
 ARTICLE 285 AND SECTION 285.5 ALL SURGE PROTECTION
 DEVICES (SPDS) SHALL BE LISTED. DEVICES BEARING THE
 TVSS DESIGNATION MAY NOT BE LISTED. ALSO PLEASE REVIEW
 SECTION 285.12 WHICH GOVERNS THE ROUTING OF CONNECTIONS
 BETWEEN THE SPD AND THE BUS. DESIGN DOCUMENTS SHOULD
 DESIGNATE SPDS AS TYPE 1, TYPE 2, AND TYPE 3 TO
 FACILITATE COMPLIANCE WITH ARTICLE 285.
  
 16. SHEET E7.01 - PLEASE NOTE MY PREVIOUS COMMENT UNDER
 NOTE 1 (ABOVE) REGARDING VOLTAGE DROP AND
 RESPONSIBILITY FOR THE DESIGN TO SATISFY THE CODE
 CRITERIA.
  
 17. SHEET E7.01 - THE ELECTRICAL PLANS APPEAR TO BE
 LACKING A "SPECIAL PURPOSE RECEPTACLE SCHEDULE" TO
 INDICATE WHAT DEVICES WILL BE ATTACHED TO THE NUMBERED
 SPECIAL PURPOSE RECEPTACLES SHOWN ON THE THREE
 ELECTRICAL FLOOR PLANS. SHEET E7.01 MIGHT BE AN
 APPROPRIATE LOCATION FOR SUCH A SCHEDULE.
  
 18. SHEET ED2.04 NOTE 6 - NO EQUIPMENT IS TO BE
 ENERGIZED WITH THE WRITTEN CONSENT OF THE CITY
 ELECTRICAL INSPECTOR. NO WORK IS TO BE PERFORMED ON
 ENERGIZED EQUIPMENT. AFTER HOURS INSPECTIONS ARE
 AVAILABLE UPON REQUEST TO FACILITATE COORDINATION OF
 INSPECTION AND MINIMIZE ADVERSE IMPACTS.
  
 19. SHEET ED2.04 NOTE 9 - ALL TEMPORARY ELECTRICAL
 SYSTEMS ARE TO BE DOCUMENTED, REVIEWED, INSPECTED AND
 FOUND TO BE IN FULL COMPLIANCE WITH ARTICLE 590 OF THE
 NEC BEFORE UTILIZATION.
  
 PLEASE FEEL FREE TO CONTACT ME DIRECTLY WITH CONCERNS
 OR QUESTIONS ABOUT THIS REVIEW.
  
 I MAY BE REACHED DURING NORMAL BUSINESS HOURS AT THE
 NUMBER SHOWN AT TOP OR BY EMAIL.
  
 DOUG WISE
  
  
  
  
  