2010-08-26 12:08:53 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| 561-805-6724 [email protected] |
| |
| FBC FLORIDA BUILDING CODE 2007 |
| FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING |
| CODE |
| FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL |
| FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2007 |
| FAC FLORIDA ADMINISTRATIVE CODE |
| FS FLORIDA STATUTE |
| |
| 1. PLEASE NOTIFY OWNER; THERE ARE EXPIRED PERMITS FOR |
| THIS ADDRESS. PLEASE REQUEST TO EITHER VOID OR REAPPLY |
| FOR THESE PERMITS. |
| |
| 2. BUSINESS TAX RECEIPTS ON RECORD SHOW SUITE 102 IS |
| OCCUPIED, BUT FLOOR PLAN SHOWS 102 AS STAIR 1. TENANT |
| 123 IS SHOWN. PLEASE ADVISE AS TO CORRECT SUITE NUMBERS |
| CURRENTLY OCCUPIED OR REVISE PLAN TO CORRELATE WITH OUR |
| RECORDS. |
| |
| 3. SEE FBC1008.1.9. LS0.0 STATES THAT OCCUPANCY |
| CLASSIFICATION IS B, BUT (A) IS SHOWN FOR TRAINING / |
| BREAK AREA. DOORS 111A AND 112A HAVE PANIC HARDWARE AND |
| CLOSER SPECIFIED ON SHEET A0.30, BUT THIS IS NOT SHOWN |
| FOR DOOR 110A WHICH IS ALSO LOCATED IN THE MEANS OF |
| EGRESS FOR THIS AREA. PLEASE REVISE OR CLARIFY DESIGN |
| INTENT. |
| |
| 4. DOOR 111B AND 112B, SHEET A2.01, PROVIDE INFORMATION |
| REGARDING THE DOOR. SHEET A0.30 SHOWS THIS AS A 24IN |
| DOOR, PLAN DOES NOT SHOW A SIDE HINGED DOOR. PLEASE SEE |
| FBC1003.6, FBC 1008.1.2, 1008.1.1. |
| |
| 5. SEE FBC1014.2, BREAK AREA ACCESS TO EXIT DOOR 112A |
| IS THROUGH AN UNMARKED ROOM. PLEASE REVISE. |
| |
| 6. PARTITION TYPE B IS NOT A RATED WALL, SHOWN AT |
| STORAGE 114, BUT DOOR 114A IS SHOWN AS A 45 MINUTE |
| DOOR. PLEASE CLARIFY DESIGN INTENT; SHOULD THE STORAGE |
| AREA BE FIRE RESISTANCE RATED? SEE ALSO DOOR 117A. FBC |
| 508. |
| 7. DOORS 312 A AND B, DOORS TO BE FIRE RATED IN |
| ACCORDANCE WITH FBC TABLE 715.4. |
| |
| 8. SEE FBC1008.1.3.4, ACCESS CONTROLLED EGRESS DOORS, |
| SHOW COMPLIANCE ON PLAN. THERE IS A NOTE REGARDING |
| POWER ON THE PLAN, BUT PLEASE SHOW COMPLIANCE FOR ALL |
| REQUIREMENTS. |
| |
| 9. EXIT SIGN IN CORRIDOR 213 IS SHOWN DIRECTS OCCUPANTS |
| THROUGH CORRIDOR 214 WHICH LEADS TO WORKSTATION 218. |
| SEE FBC 1008.1.2, CANNOT USE THE SLIDING DOOR IN THE |
| MEANS OF EGRESS EXCEPT AS PERMITTED IN EXCEPTIONS. |
| |
| 10. FBC 1008.1.2, SHEETS LS2.01, LS2.02, LS2.03, |
| CONFERENCE ROOMS MUST HAVE A SIDE HINGED DOOR FOR MEANS |
| OF EGRESS. THE EXCEPTION (PRIVATE GARAGES, OFFICE |
| AREAS, FACTORY AND STORAGE AREAS) DOES NOT APPLY TO |
| THIS TYPE OF AREA. FOR EXAMPLE, SEE CONFERENCE ROOMS |
| 228, 248, 315, AND 340. PLEASE CHECK ALL. |
| |
| 11. FBC11 4.24, SEE DETAIL 3 A8.03. A TOE KICK IS SHOWN |
| FASTENED TO THE CABINET BASE, PLEASE SHOW HOW THIS |
| COMPLIES WITH ACCESSIBILITY REQUIREMENTS. PLEASE CHECK |
| ALL. |
| |
| 12. FBC11 4.24, PLEASE SHOW ALL REQUIRED DIMENSIONS. |
| NOTE THAT SINK DEPTH DOES NOT APPEAR TO COMPLY, 3 |
| A8.03, CHECK ALL. |
| |
| 13. FLORIDA STATE OR LOCAL PRODUCT APPROVAL (REVIEWED |
| BY DESIGNER OF RECORD) REQUIRED FOR EXTERIOR DOOR, |
| FAC9B72. |
| |
| 14. D2.03 NOTE 13 REFERS TO DETAILS ON STRUCTURAL |
| SHEETS, PLEASE PROVIDE. |
| |
| 15. PLANS STATE TO SEE CIVIL DRAWINGS FOR DETAIL FOR |
| NEW RAMP ON EAST SIDE OF BUILDING 1ST FLOOR, NO CIVILS |
| SUBMITTED. PLEASE PROVIDE A DETAIL FBC11 4.8. |
| |
| |