Plan Review Notes
Plan Review Notes For Permit 10070788
Permit Number 10070788
Review Stop B
Sequence Number 1
Notes
Date Text
2010-08-26 12:08:53****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2007
 FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2007
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. PLEASE NOTIFY OWNER; THERE ARE EXPIRED PERMITS FOR
 THIS ADDRESS. PLEASE REQUEST TO EITHER VOID OR REAPPLY
 FOR THESE PERMITS.
  
 2. BUSINESS TAX RECEIPTS ON RECORD SHOW SUITE 102 IS
 OCCUPIED, BUT FLOOR PLAN SHOWS 102 AS STAIR 1. TENANT
 123 IS SHOWN. PLEASE ADVISE AS TO CORRECT SUITE NUMBERS
 CURRENTLY OCCUPIED OR REVISE PLAN TO CORRELATE WITH OUR
 RECORDS.
  
 3. SEE FBC1008.1.9. LS0.0 STATES THAT OCCUPANCY
 CLASSIFICATION IS B, BUT (A) IS SHOWN FOR TRAINING /
 BREAK AREA. DOORS 111A AND 112A HAVE PANIC HARDWARE AND
 CLOSER SPECIFIED ON SHEET A0.30, BUT THIS IS NOT SHOWN
 FOR DOOR 110A WHICH IS ALSO LOCATED IN THE MEANS OF
 EGRESS FOR THIS AREA. PLEASE REVISE OR CLARIFY DESIGN
 INTENT.
  
 4. DOOR 111B AND 112B, SHEET A2.01, PROVIDE INFORMATION
 REGARDING THE DOOR. SHEET A0.30 SHOWS THIS AS A 24IN
 DOOR, PLAN DOES NOT SHOW A SIDE HINGED DOOR. PLEASE SEE
 FBC1003.6, FBC 1008.1.2, 1008.1.1.
  
 5. SEE FBC1014.2, BREAK AREA ACCESS TO EXIT DOOR 112A
 IS THROUGH AN UNMARKED ROOM. PLEASE REVISE.
  
 6. PARTITION TYPE B IS NOT A RATED WALL, SHOWN AT
 STORAGE 114, BUT DOOR 114A IS SHOWN AS A 45 MINUTE
 DOOR. PLEASE CLARIFY DESIGN INTENT; SHOULD THE STORAGE
 AREA BE FIRE RESISTANCE RATED? SEE ALSO DOOR 117A. FBC
 508.
 7. DOORS 312 A AND B, DOORS TO BE FIRE RATED IN
 ACCORDANCE WITH FBC TABLE 715.4.
  
 8. SEE FBC1008.1.3.4, ACCESS CONTROLLED EGRESS DOORS,
 SHOW COMPLIANCE ON PLAN. THERE IS A NOTE REGARDING
 POWER ON THE PLAN, BUT PLEASE SHOW COMPLIANCE FOR ALL
 REQUIREMENTS.
  
 9. EXIT SIGN IN CORRIDOR 213 IS SHOWN DIRECTS OCCUPANTS
 THROUGH CORRIDOR 214 WHICH LEADS TO WORKSTATION 218.
 SEE FBC 1008.1.2, CANNOT USE THE SLIDING DOOR IN THE
 MEANS OF EGRESS EXCEPT AS PERMITTED IN EXCEPTIONS.
  
 10. FBC 1008.1.2, SHEETS LS2.01, LS2.02, LS2.03,
 CONFERENCE ROOMS MUST HAVE A SIDE HINGED DOOR FOR MEANS
 OF EGRESS. THE EXCEPTION (PRIVATE GARAGES, OFFICE
 AREAS, FACTORY AND STORAGE AREAS) DOES NOT APPLY TO
 THIS TYPE OF AREA. FOR EXAMPLE, SEE CONFERENCE ROOMS
 228, 248, 315, AND 340. PLEASE CHECK ALL.
  
 11. FBC11 4.24, SEE DETAIL 3 A8.03. A TOE KICK IS SHOWN
 FASTENED TO THE CABINET BASE, PLEASE SHOW HOW THIS
 COMPLIES WITH ACCESSIBILITY REQUIREMENTS. PLEASE CHECK
 ALL.
  
 12. FBC11 4.24, PLEASE SHOW ALL REQUIRED DIMENSIONS.
 NOTE THAT SINK DEPTH DOES NOT APPEAR TO COMPLY, 3
 A8.03, CHECK ALL.
  
 13. FLORIDA STATE OR LOCAL PRODUCT APPROVAL (REVIEWED
 BY DESIGNER OF RECORD) REQUIRED FOR EXTERIOR DOOR,
 FAC9B72.
  
 14. D2.03 NOTE 13 REFERS TO DETAILS ON STRUCTURAL
 SHEETS, PLEASE PROVIDE.
  
 15. PLANS STATE TO SEE CIVIL DRAWINGS FOR DETAIL FOR
 NEW RAMP ON EAST SIDE OF BUILDING 1ST FLOOR, NO CIVILS
 SUBMITTED. PLEASE PROVIDE A DETAIL FBC11 4.8.
  
  