2010-07-29 13:53:29COMMUNITY HOSPITAL OF THE PALM BEACHES
 2201-45TH STREET
 PERMIT NUMBER 10070774
  
  
 1. THE PROPOSED FIRE ALARM INSTALLATION TO COMPLY WITH
 NFPA 72, THE NATIONAL FIRE ALARM CODE.
  
 2. FIRE WATCH ACTIVITIES ARE REQUIRED WHENEVER A
 REQUIRED SYSTEM IS OUT OF SERVICE FOR MORE THAN FOUR
 HOURS IN A TWENTY FOUR HOUR PERIOD. ALL FIRE WATCH
 REQUESTS ARE TO BE IN WRITING TO THE BATTALION CHIEF OF
 FIRE PREVENTION OR HIS DESIGNEE. PERSONS PERFORMING
 FIRE WATCH ACTIVITIES SHALL BE RADIO OR CELLULAR
 TELEPHONE EQUIPPED TO REPORT EMERGENCIES. SUFFICIENT
 NUMBER OF PERSONS ARE REQUIRED TO PERFORM FIRE WATCH
 ACTIVITIES AND ARE TO HAVE NO OTHER DUTIES.
  
 3. THE EXISTING FIRE ALARM EQUIPMENT SHALL REMAIN
 ACTIVE AS LONG AS POSSIBLE PRIOR TO THE SWITCH-OVER TO
 THE NEW EQUIPMENT. THE NEW SYSTEM COMPONENTS SHOULD BE
 INSTALLED WHILE THE EXISTING EQUIPMENT REMAINS IN
 SERVICE SO AS TO AVOID A POSSIBLE FIRE WATCH.
  
 4. NEW FIRE ALARM SYSTEM LOG BOOKS ARE TO BE
 ESTABLISHED FOR THE NEW EQUIPMENT.
  
 5. THE NEW EQUIPMENT IS TO BE TESTED WITH
 REPRESENTATIVES OF THIS OFFICE TO ENSURE PROPER
 FUNCTION.
  
 6. THE NEW FIRE ALARM SYSTEM COMPONENTS SHALL BE LISTED
 FOR THE PURPOSE FOR WHICH THEY ARE INTENDED.
  
 7. THE REMOTE ANNUNCIATOR PANELS SHALL BE PLACED IN
 AREAS WHERE THEY WILL NOT BECOME OBSTRUCTED OR DAMAGED.
  
 8. ALL FIRE ALARM WORK IS SUBJECT TO FIELD INSPECTION
 AND APPROVAL.
  
 9. PROPER COORDINATION IS TO BE PROVIDED DURING THE
 INSTALLATION OF THE NEW FIRE ALARM EQUIPMENT.