Plan Review Notes For Permit 10070755 |
Permit Number |
10070755 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2010-08-02 09:11:18 | RE-ROOF BUILDING REVIEW CHECKLIST. | | 2007 FBC WITH 2009 REVISIONS. | | | | 1- ACCORDING TO THE MIAMI-DADE WEBSITE FLAT ROOF NOA | | 07-0730.03 SUBMITTED IS SUPERSEDED. NEED TO PROVIDE | | CURRENT NOA. | | | | 2- RAS 117 CALCULATIONS SUBMITTED: | | A) ENGINEER TO REVISE ALL CALCULATIONS USING ASCE 7-05 | | NOT ASCE 7-02. ASCE 7-05 IS THE CODE ADOPTED BY THE | | 2007 FBC. | | | | B) ENGINEER TO REVISE THE FASTENER SPACING FOR ROOF | | ZONE #3. 3 1/2" SPACING IS NOT ALLOWED BY SEC. 8.1 OF | | RAS 117 CALCULATIONS. THE MINIMUM FASTENER SEPARATION | | SHALL NOT BE LESS THAN 4" O.C. | | | | C) ENGINEER TO REVISE FASTENER SPACING. ALL FRACTIONS | | SHALL BE ROUNDED DOWN TO THE NEXT WHOLE NUMBER AS | | REQUIRED BY SEC. 10.4.5 OF RAS 117 CALCULATIONS. | | | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561)805-6712 |
|