Notes |
Date |
Text |
2010-09-08 08:02:15 | 2007 FBC W/2009 REVISIONS | | | | DENIED BY BUILDING | | | | 1) THE PRODUCT APPROVALS THAT WERE SUBMITTED (FL11963) | | ARE NOT THE ONES SPECIFIED ON THE INSTALLATION SCHEDULE | | (FL11398). SUBMIT MATCHING INFORMATION. PER THE TABLE | | ON FL11398, THE ANCHOR SPACING OF 18" FOR MOUNT TYPE C1 | | AND C4 IS ONLY GOOD FOR 33.0 PSF. THE OPENING PRESSURES | | ARE HIGHER THAN THAT. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|