Plan Review Notes
Plan Review Notes For Permit 10070689
Permit Number 10070689
Review Stop B
Sequence Number 1
Notes
Date Text
2010-09-08 08:02:152007 FBC W/2009 REVISIONS
  
 DENIED BY BUILDING
  
 1) THE PRODUCT APPROVALS THAT WERE SUBMITTED (FL11963)
 ARE NOT THE ONES SPECIFIED ON THE INSTALLATION SCHEDULE
 (FL11398). SUBMIT MATCHING INFORMATION. PER THE TABLE
 ON FL11398, THE ANCHOR SPACING OF 18" FOR MOUNT TYPE C1
 AND C4 IS ONLY GOOD FOR 33.0 PSF. THE OPENING PRESSURES
 ARE HIGHER THAN THAT.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]